| 2013-06-04 07:50:58 | BUILDING PLAN REVIEW |
| | PERMIT: 13051109 |
| | ADD: 2707 OKEECHOBEE BLVD |
| | CONT: TBD |
| | TEL: (305)663-1970 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JUNE 04/2013 |
| | |
| | ACTION:PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) THE PLANS SHOW REPLACEMENT OF EXTERIOR DOORS & |
| | FRAMES ON BUILDINGS 2 & 3, PLEASE PROVIDE WIND DESIGN |
| | CRITERIA & ASSOCIATED PRESSURE: |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 1.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 1.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 1.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 1.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |
| | 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 4) BUILDING # 4 INDICATES A NEW PAINT MIXING ROOM AND |
| | SPRAY BOOTH. THESE ITEMS REQUIRE A SEPERATE PREMIT, |
| | REVIEW AND ASSOCIATED FEES. 109.3 BUILDING PERMIT |
| | VALUATION. |
| | MIXING ROOM & SPRAY BOOTH TO COMPLY WITH: |
| | 416.2 SPRAY ROOMS. |
| | SPRAY ROOMS SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR |
| | FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION |
| | 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED |
| | AND DRAINED IN AN APPROVED MANNER. |
| | |
| | [F] 416.2.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH |
| | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE |
| | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| | FACILITATE WASHING AND CLEANING, AND SHALL BE SO |
| | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | [F] 416.3 SPRAYING SPACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR |
| | VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL. WHERE SUCH SPACES ARE NOT SEPARATELY |
| | ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE |
| | PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS. |
| | |
| | [F] 416.3.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE |
| | SMOOTH AND CONTINUOUS WITHOUT EDGES; SHALL BE SO |
| | CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR |
| | FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE |
| | WASHING AND CLEANING; AND SHALL BE SO DESIGNED TO |
| | CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | [F] 416.4 SPRAY BOOTHS. |
| | SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND |
| | OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | [F] 416.5 FIRE PROTECTION. |
| | AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE |
| | PROVIDED IN ALL SPRAY, DIP AND IMMERSING SPACES AND |
| | STORAGE ROOMS AND SHALL BE INSTALLED IN ACCORDANCE WITH |
| | CHAPTER 9. |
| | SECTION 417 |
| | DRYING ROOMS |
| | |
| | 903.2.11.6 OTHER REQUIRED SUPPRESSION SYSTEMS. IN |
| | ADDITION TO THE REQUIREMENTS OF SECTION 903.2, THE |
| | PROVISIONS INDICATED IN TABLE 903.2.11.6 ALSO REQUIRE |
| | THE INSTALLATION OF A FIRE SUPPRESSION SYSTEM FOR |
| | CERTAIN BUILDINGS AND AREAS. FLAMMABLE FINISHES. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |