Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-24 Cont ID  
Sent By jwitmer Date 2013-07-24 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2013-07-24 Time 12:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-18 Cont ID  
Sent By jwitmer Date 2013-06-18 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2013-06-18 Time 08:30 Sent To  
Notes
2013-06-18 10:10:42BUILDING PLAN REVIEW
 PERMIT: 13051091
 ADD: 1400 VILLAGE BLVD
 CONT: TBD
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JUNE 18/2013
 ACTION: DENIED
  
 1) THE SUBMITTED MODULAR PLAN IS A STATE APPROVED PLAN.
 SHEET C1LIST THE STATE APPROVED PLAN # DBI 12605 AS A
 APPROVED PLAN WITH THE APPROVAL NUMBER ON EVERY SHEET
 ON THE MODULAR BUILDING PORTION OF THE STATE WEBSITE.
 THE COVER LETTER THAT TIES TO THE MODULAR BUILDING
 REVIEW IS ALSO DIFFERENT FROM THE LETTER SUBMITTED.
 PLEASE INDICATE WHAT THE PURPOSE OF SIGNED AND SEALED
 PLANS ARE AND WHY ALL OF THE PLANS DO NOT HAVE THE
 STATE APPROVAL? IF THE APPROVAL IS GOING TO BE REMOVED
 FROM THIS UNIT AND A TOTAL REVIEW OF ALL TRADES TO
 OCCUR?
  
 2) SHEET C1 UNDER THE HEADING OF AS BUILT LIST THIS
 MODULAR BUILDING WAS BUILT UNDER THE 2004 FBC-B BUT
 REFERENCES THE CURRENT CODE BASICALLY AS EQUAL. THE 170
 MPH VULT = TO 132 VASD NOT THE 130 NOTED ON THE PLAN.
 FIGURE 1609A NOTE # 2 DOES ALLOW FOR LINEAR
 INTERPOLATION, PLEASE PROVIDE MORE INFORMATION?
  
 3) PLEASE PROVIDE THE LENGTH OF TIME THE MANUFACTURED
 BUILDING IS TO BE ON SITE, NOTE THE TERM TEMORARY IN
 THE BUILDING CODE IS FOR NOT MORE THAN 6 MONTHS. 108.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 08:41 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 08:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 11:30 Rev Time 0.00
Received By dharvey Date 2013-07-01 Time 11:04 Sent To  
Notes
2013-07-01 11:31:05PROVIDE AN ELECTRICAL PERMIT WITH A RISER PLAN FOR THE
 ELECTRIC SERVICE TO THE TRAILER. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-17 Cont ID  
Sent By wjolin Date 2013-07-17 Time 16:26 Rev Time 0.00
Received By wjolin Date 2013-07-17 Time 16:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-14 Cont ID  
Sent By wjolin Date 2013-06-14 Time 14:14 Rev Time 0.00
Received By wjolin Date 2013-06-14 Time 13:39 Sent To  
Notes
2013-06-14 14:14:451400 VILLAGE BOULEVARD
 PERMIT #13051091
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 241 (TABLE 4.2.1), THE TEMPORARY MODULAR
 BUILDING SHALL BE LOCATED AT LEAST 50 FEET AWAY FROM
 ADJACENT STRUCTURES. CURRENTLY THERE APPEARS TO ONLY BE
 APPROXIMATELY 20 FEET OF SEPARATION.
  
 PROVIDE STAIR AND HANDRAIL DETAILS. HANDRAILS ARE
 REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE
 LOCATED NOT LESS THAN 34 INCHES AND NOT MORE THAN 38
 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES. STAIR
 RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER.
  
 PROVIDE PORTABLE FIRE EXTINGUISHER(S). EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-07 Cont ID  
Sent By shill Date 2013-08-07 Time 18:25 Rev Time 0.00
Received By shill Date 2013-07-03 Time 08:55 Sent To  
Notes
2013-08-07 08:42:16TO S HILL
2013-07-09 08:55:56SENT TO C8 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 11:32 Rev Time 0.00
Received By dharvey Date 2013-05-31 Time 18:13 Sent To  
Notes
2013-05-31 18:17:50C6

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By lwagner Date 2013-07-11 Time 10:34 Rev Time 0.00
Received By lwagner Date 2013-07-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-07-16 Cont ID  
Sent By ajones Date 2013-07-16 Time 12:05 Rev Time 0.00
Received By ajones Date 2013-07-11 Time 14:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-06-07 Cont ID  
Sent By ajones Date 2013-06-07 Time 13:14 Rev Time 0.00
Received By ajones Date 2013-06-03 Time 14:54 Sent To  
Notes
2013-06-07 13:16:356/7/13- FAILED A MINOR PD AMENDMENT IS REQUIRED TO BE
 FILED WITH THE PLANNING DIVISION BEFORE ZONING CAN
 APPROVE THIS PERMIT.
  