Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-09-10 Cont ID  
Sent By dharvey Date 2013-09-10 Time 16:01 Rev Time 0.00
Received By dharvey Date 2013-09-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-08-06 Cont ID  
Sent By dharvey Date 2013-08-06 Time 15:42 Rev Time 0.00
Received By dharvey Date 2013-08-06 Time 15:22 Sent To  
Notes
2013-08-06 15:37:44POLE ANALYSIS IS NOT SEALED BY A FLORIDA REGISTERED
 ENGINEER. PROVIDE LISTING INFORMATION FOR LUMINAIRES
 FROM A RECOGNIZED TESTING LAB. SECURITY CAMERAS REQUIRE
 A SEPARATE PERMIT. ADDRESS CAMERA WINDLOAD ON POLES
 THAT WILL HAVE CAMERAS. SECTION 4 APPEARS TO BE THE
 ONLY SECTION PROVIDED THAT IS RELATED TO SITE LIGHTING.
 DIFFERENT ENGINEERS HAVE SEALED THE PAGES RELATED TO
 THE LIGHTING, ATTACHEMENT, WINDLOAD AND BASES. PLEASE
 PROVIDE CONFIRMATION THE ENGINEERS ARE IN AGREEMENT
 THAT THE POLE BASE DETAIL WILL PROVIDE THE NEEDED
 UPLIFT, OVERTURN AND OTHER LOADS ASSOCIATED WITH THE
 POLES SPECIFIED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 10:45 Rev Time 0.00
Received By dharvey Date 2013-07-01 Time 10:04 Sent To  
Notes
2013-07-01 10:47:3313051078
 4001 S DIXIE HWY
 WALGREEN?S SITE LIGHTING
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE SPECIFICATIONS AND THE LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) FOR THE
 POLES AND FIXTURES. NEC 110.3
  
 WIND LOAD ENGINEERING FOR THE LIGHT POLES AND FIXTURES
 NEEDS TO REFERENCE THE ACTUAL FIXTURE TYPE OR MODEL
 WITH ITS EPA AND ALSO VERIFY THE EXISING FOOTER IS
 STRUCTURALLY ADEQUATE. FBC 1609.1
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-10 Cont ID  
Sent By dharvey Date 2013-09-10 Time 16:01 Rev Time 0.00
Received By dharvey Date 2013-09-05 Time 08:07 Sent To  
Notes
2013-09-06 08:08:34SENT TO ELECTRICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2013-08-06 Cont ID  
Sent By dharvey Date 2013-08-06 Time 15:46 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 16:44 Sent To  
Notes
2013-08-06 15:47:02FILED UNDER "TBD" DH
2013-08-05 16:44:20TO ELEC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-01 Cont ID  
Sent By dharvey Date 2013-07-01 Time 10:47 Rev Time 0.00
Received By dharvey Date 2013-07-01 Time 10:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-20 Cont ID  
Sent By eschneid Date 2013-06-20 Time 16:27 Rev Time 0.25
Received By eschneid Date 2013-06-20 Time 16:26 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved