Plan Review Details - Permit 13051030
Plan Review Stops For Permit 13051030
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-09-23 Cont ID  
Sent By rmcdouga Date 2013-09-23 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2013-09-23 Time 10:29 Sent To  
Notes
2013-09-23 10:30:41BUILDING PROVISO
  
 1) SUBMIT TWO COPIES OF MIAMI-DADE NOAS OR FLORIDA
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS (THE FRONT
 DOOR, THE GLAZED KITCHEN DOOR AND THE GLAZED FRENCH
 DOORS) AS REQUIRED BY DCA RULE 9N-3. THE PRODUCT
 APPROVALS ARE REQUIRED TO INCLUDE THE INSTALLATION
 INSTRUCTIONS, THE MAXIMUM DESIGN PRESSURES AND SPECIFY
 IMPACT RATING.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 18:03 Sent To  
Notes
2013-09-18 18:14:382010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF MIAMI-DADE NOAS OR FLORIDA
 PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS (THE FRONT
 DOOR, THE GLAZED KITCHEN DOOR AND THE GLAZED FRENCH
 DOORS) AS REQUIRED BY DCA RULE 9N-3. THE PRODUCT
 APPROVALS ARE REQUIRED TO INCLUDE THE INSTALLATION
 INSTRUCTIONS, THE MAXIMUM DESIGN PRESSURES AND SPECIFY
 IMPACT RATING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2013-07-11 Time 11:13 Sent To  
Notes
2013-07-11 15:16:44REVISION REQUIRED
  
 1) SUBMIT PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS
 AS REQUIRED BY DCA RULE 9N-3.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-07-08 Cont ID  
Sent By dharvey Date 2013-07-08 Time 10:51 Rev Time 0.00
Received By dharvey Date 2013-07-08 Time 10:18 Sent To  
Notes
2013-07-08 10:51:32 
 13051030
 3015 OLIVE AVENUE
 SF REMODEL
  
 THE FOLLOWING ITEMS WERE NOTED ON THE PLAN.
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-06-05 Cont ID  
Sent By fmittner Date 2013-06-05 Time 13:50 Rev Time 0.00
Received By fmittner Date 2013-06-03 Time 14:52 Sent To  
Notes
2013-06-05 13:50:50R5

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-09-23 Cont ID  
Sent By rmcdouga Date 2013-09-23 Time 10:31 Rev Time 0.00
Received By rmcdouga Date 2013-09-20 Time 08:53 Sent To  
Notes
2013-09-20 08:53:49SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 18:14 Rev Time 0.00
Received By rmcdouga Date 2013-09-11 Time 16:37 Sent To  
Notes
2013-09-12 16:39:16SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-28 Cont ID  
Sent By rmcdouga Date 2013-08-28 Time 15:56 Rev Time 0.00
Received By rmcdouga Date 2013-08-16 Time 14:46 Sent To  
Notes
2013-08-16 14:46:59TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-05 Cont ID  
Sent By rmcdouga Date 2013-08-05 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2013-07-25 Time 15:14 Sent To  
Notes
2013-07-26 15:14:57SENT TO MCDOUGAL'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2013-05-30 Time 14:46 Sent To  
Notes
2013-05-30 14:47:14SENT TO R5 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2013-09-23 Cont ID  
Sent By rmcdouga Date 2013-09-23 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2013-09-23 Time 09:54 Sent To  
Notes
2013-09-23 10:29:24CONTRACTOR REDLINED CHANGES TO HIS PLANS. CHANGED THE
 SECOND FLOOR SYSTEM ON THE EQUIPMENT SCHEDULE FROM 2.5
 TON TO 2 TON TO MATCH EQUIPMENT SIZING CALCULATIONS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2013-09-18 Cont ID  
Sent By rmcdouga Date 2013-09-18 Time 17:50 Rev Time 0.00
Received By rmcdouga Date 2013-09-18 Time 16:41 Sent To  
Notes
2013-09-18 18:03:072010 FBC
  
 DENIED BY BUILDING
  
 1) THE NEW EQUIPMENT SIZING CALCULATIONS AND ENERGY
 CALCULATIONS DO NOT MATCH THE MECHANICAL PLANS. THE NEW
 CALCULATIONS SPECIFY 2 - TON UNITS ON BOTH FLOORS. THE
 OLD EQUIPMENT SIZING CALCULATIONS AND THE EQUIPMENT
 SCHEDULE ON THE MECHANICAL PLANS SPECIFY A 2 - TON UNIT
 ON THE FIRST FLOOR AND A 2.5 TON UNIT ON THE SECOND
 FLOOR. THE EQUIPMENT SCHEDULE ON THE PLANS HAS TO MATCH
 THE SIZING CALCULATIONS AND THE ENERGY CALC. FORM. FBC
 ENERGY CONSERVATION SECTION 405 & FBCR M1401.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2013-08-28 Cont ID  
Sent By rmcdouga Date 2013-08-28 Time 15:41 Rev Time 0.00
Received By rmcdouga Date 2013-08-28 Time 15:41 Sent To  
Notes
2013-08-28 15:56:442010 FBC
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW
 COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS. THE FBC
 ENERGY CONSERVATION TABLE 101.4.1 FOR RENOVATIONS,
 SPECIFIES THAT THE MINIMUM CODE ENVELOPE, EQUIPMENT AND
 LIGHTING EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS
 BEING CHANGED.
  
 THE INSTALLED VALUE INFORMATION SHOWN ON FORM 402-2010
 THAT WAS SUBMITTED DOES NOT MEET THE REQUIRED
 EFFICIENCY LEVELS OF TABLE 402A AND 402B OF THE FORM
 FOR U-FACTOR, SHGC OR DUCT INSULATION LOCATED IN
 ATTICS. PLEASE SUBMIT TWO COPIES THE COMPLIANCE REPORT
 REQUIRED BY SECTION 405 SHOWING COMPLIANCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-08-05 Cont ID  
Sent By rmcdouga Date 2013-08-05 Time 07:44 Rev Time 0.00
Received By rmcdouga Date 2013-08-02 Time 11:19 Sent To  
Notes
2013-08-05 07:17:122010 FBC
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW
 COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS. THE FBC
 ENERGY CONSERVATION TABLE 101.4.1 FOR RENOVATIONS,
 SPECIFIES THAT THE MINIMUM CODE ENVELOPE, EQUIPMENT AND
 LIGHTING EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS
 BEING CHANGED. THE FORM THAT WAS SUBMITTED IS OUTDATED
 (FORM 600C-01) AND IS FOR CENTRAL FLORIDA , THE WRONG
 CLIMATE ZONE. PLEASE SUBMIT TWO COPIES OF FORM 402-2010
 OR THE COMPLIANCE REPORT REQUIRED BY SECTION 405
 SHOWING COMPLIANCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2013-07-11 Time 14:15 Sent To  
Notes
2013-07-11 15:05:172010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC ENERGY SECTIONS 101.4.1 AND 401.2 OR SHOW
 COMPLIANCE WITH PRESCRIPTIVE REQUIREMENTS.
  
 2) THE RETURN AIR FOR THE FIRST FLOOR APPEARS TO BE
 THROUGH THE LOUVERED DOOR OF THE A/H CLOSET LOCATED IN
 THE FLEX ROOM. THIS ROOM HAS DOORS THAT WHEN CLOSED
 WILL RESTRICT RETURN AIR FROM THE OTHER AREAS OF THE
 FLOOR. SHOW COMPLIANCE WITH FBCR M1602.4 FOR REQUIRED
 BALANCED RETURN AIR.
  
 3) THE RETURN AIR AT THE SECOND FLOOR DOES NOT COMPLY
 WITH FBCR M1602.4 FOR REQUIRED BALANCED RETURN AIR FOR
 THE BEDROOMS AND MASTER SUITE. PLEASE CORRECT.
  
 4) SPECIFY THE LOCATION OF THE SECOND FLOOR AIR
 HANDLER. IF IT IS LOCATED IN THE ATTIC, SHOW THAT IT
 COMPLIES WITH FBCR M1305.1.3.
  
 5) ON SHEET AIR-1 A 12 X 6 GRILL IS SHOWN NEAR THE
 KITCHEN EATING AREA WITH NO DUCT CONNECTED TO IT AND ON
 SHEET AIR-2 THE DUCT CONNECTED TO THE 12 X 6 GRILL IN
 BED ROOM # 2 IS NOT SHOWN. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-07-08 Cont ID  
Sent By lwagner Date 2013-07-08 Time 12:57 Rev Time 0.00
Received By lwagner Date 2013-07-08 Time 11:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-05 Cont ID  
Sent By fmittner Date 2013-06-05 Time 13:50 Rev Time 0.00
Received By fmittner Date 2013-06-03 Time 14:51 Sent To  
Notes
***NONE***