Plan Review Details - Permit 13051012
Plan Review Stops For Permit 13051012
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2014-08-06 Cont ID  
Sent By skennedy Date 2014-08-06 Time 11:33 Rev Time 0.00
Received By skennedy Date 2013-07-30 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status N Date 2014-08-15 Cont ID  
Sent By shill Date 2014-08-15 Time 15:11 Rev Time 0.00
Received By shill Date 2014-07-23 Time 09:44 Sent To  
Notes
2014-07-23 09:46:30GENERATED A SUBMITTAL NUMBER FOR LIGHT POLE CALCS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status N Date 2014-05-15 Cont ID  
Sent By skennedy Date 2014-05-15 Time 13:59 Rev Time 0.00
Received By skennedy Date 2014-05-15 Time 13:59 Sent To  
Notes
2014-05-15 14:01:20SEE SUBMITTAL 1405****

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 14:12 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 14:52 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 13:32 Sent To  
Notes
2013-09-25 14:59:18BUILDING PLAN REVIEW
 PERMIT: 13051012
 ADD: 300 CORTNEY LAKES
 CONT:TO BE DETERMINED
 TEL: (561)###-#### CONTACT?
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SEPT 25/2013
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2)SEMI-COMPLIED. 9/12/13 KEN CONRAD IS STILL AWAITING
 RECEIPT OF THE COMPLETED SPECIAL INSPECTOR AGREEMENT.
 FBC* 110.3.9 RESIDENT INSPECTOR (ON SITE INSPECTOR
 REQUIRED). SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO KEN CONRAD, MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM. A RESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT, DUE TO BUILDINGS OVER 2
 STORIES IN HEIGHT.
 KEN CONRAD
 TEL: 561-805-6666
 E:MAIL: KCONRAD @WPB.ORG
  
 3-4) COMPLIED.
  
 5) SHEET A0.10 SITE PLAN;
  
 5A) 2ND REQUEST, RESPONCE INDICATES SEE CIVIL SHEETS
 BUT THERE IS NO CIVIL SHEETS TO REVIEW. PLEASE PROVIDE
 THE PARKING COUNT, PLEASE BREAK OUT BY SECTION PLEASE
 PROVIDE COUNT FOR FAIR HOUSING AND FOR FL ACCESSIBILITY
 FOR COMMON AREAS, RENTAL OR SALES OFFICE. FAIR HOUSING
 ANSI A117.1 4.32010 FL ACCESS TABLE 208.2
  
 5B-5C) COMPLIED.
  
 5D) 2ND REQUEST. NO CIVIL PLANS UPLOADED. THE SITE
 PLANS DO NOT PROVIDE CLARITY OR DETAILS IF THERE IS
 DROPPED CURBS OR CURB CUTS, CURB RAMPS FOR ACCESS
 AISLES OR CROSS WALKS, ANSI A 117.1 1986
 4.7 CURB RAMPS.
  
 6-10) COMPLIED.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-20 Cont ID  
Sent By jwitmer Date 2013-07-20 Time 12:24 Rev Time 0.00
Received By jwitmer Date 2013-07-17 Time 12:58 Sent To  
Notes
2013-07-20 10:24:59BUILDING PLAN REVIEW
 PERMIT: 13051012
 ADD: LAMBERTON
 CONT:TO BE DETERMINED
 TEL: (561)###-#### CONTACT?
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: JULY 20/2013
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) FBC* 110.3.9 RESIDENT INSPECTOR (ON SITE INSPECTOR
 REQUIRED). SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO KEN CONRAD, MANAGER OF THE RESIDENT
 INSPECTOR PROGRAM. A RESIDENT INSPECTOR PROGRAM IS
 REQUIRED, ON THIS PROJECT, DUE TO BUILDINGS OVER 2
 STORIES IN HEIGHT.
 KEN CONRAD
 TEL: 561-805-6666
 E:MAIL: KCONRAD @WPB.ORG
  
 3) PROJECT DOCS HEADING VIEW FOLDERS INDICATES THAT
 SPEC BOOKS WERE LOADED FOR REVIEW, PLEASE DELETE THESE
 FROM THE NEXT SUBMITTAL, THEY WILL NOT BE REVIEWED NOR
 WILL THEY RECEIVE A BATCH STAMP.
  
 4) SHEET A0.02 INDEX OF DRAWINGS INDICATES A1.10,
 A1.20, A1.30, A1.40 & A1.50 SHOLD BE IN THIS SET OF
 PLANS, THEY ARE MISSING? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 5) SHEET A0.10 SITE PLAN;
  
 5A) PLEASE PROVIDE THE PARKING COUNT, PLEASE BREAK OUT
 BY SECTION PLEASE PROVIDE COUNT FOR FAIR HOUSING AND
 FOR FL ACCESSIBILITY FOR COMMON AREAS, RENTAL OR SALES
 OFFICE.
 FAIR HOUSING ANSI A117.1 4.3
 2010 FL ACCESS TABLE 208.2
  
 5B) PLEASE PROVIDE THE DISTANCE BETWEEN BUILDINGS, AND
 TTHE DISTANCE BETWEEN BUILDINGS FOR ASSUMED PROPERTY
 LINES TO COMPLY WITH 20 10 FBC-B TABLE 602 & T 705.8.
  
 5C) BUILDING TYPE 8 DOES NOT HAVE ACCESSIBLE PARKING,
 FAIR HOUSING ANSI A117.1 1986 4.6 PARKING SPACES.
  
 5D) THE SITE PLANS DO NOT PROVIDE CLARITY OR DETAILS IF
 THERE IS DROPPED CURBS OR CURB CUTS, CURB RAMPS FOR
 ACCESS AISLES OR CROSS WALKS, ANSI A 117.1 1986
 4.7 CURB RAMPS.
  
 6) SHEET A4.00 SERIES WOOD VINYL PLANK, TILE FLOORING
 PLEASE PROVIDE TTHE REQUIRED STC RATING SHOWING
 COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE
 SOUND.
  
 7) SHEET A5.00 UNIT TO UNIT AND UNIT TO CORRIDOR
 DETAILS DO NOT LIST THERE STC RATING, PLEASE SHOW
 COMPLIANCE WITH 2010 FBC-B 1207.2 AIR BORNE SOUND.
  
 8) SHEET A7.01 DOOR SCHEDULE FOR UNIT EXTERIOR DOOR
 SCHEDULE DOOR MARK U-003 A PAIR OF FRENCH DOORS, WHERE
 WILL THIS BE USED ON THE EXTERIOR OF A UNIT, IT DOES
 NOT SHOW UP ON ANY OF THE FOUR HUNDRED SERIES OF
 DRAWINGS FOR UNITS. THE CONCERN IS THE PRODUCT APPROVAL
 SUBMITTED INDICATES PRESSURES OF +/- 90 WHICH INDICATES
 A 2 INCH HIGH THRESHOLD WILL BE INSTALLED, WILL FAIR
 HOUSING BE A CONCERN FOR THE LOCATION IT WIL BE
 INSTALLED? ANS A117.1 1986 4.13 DOORS.
  
 9) SHEET A7.01 UNIT EXTERIOR DOOR SCHEDULE IS MISSING
 THE NOMINAL DESIGN WIND PRESSURES.
  
 10) SHEET SG-N1 ROOF PRESSURE ZONES (1-3) AND OVER HANG
 ZONES (2 &5) ARE IN PSF, THE SUBMITTED NOA 12-0222.02
 SHEET 5 OF 7 FOR ATTACHMENT IS EXPRESSED A MOMENT- MF
 (FT-LBS) PLEASE CONVERT TO PSF . THE NOA IS HIGHLIGHTED
 2-10D RING SHANK NAILS 41.2 MF.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2014-08-14 Cont ID  
Sent By dhayes Date 2014-08-14 Time 10:34 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2014-08-14 11:35:18DATE: 8/14/2014
 PROJECT: JEFFERSON APTS, COURTNEY LAKES. WIND LOADING
 ON SITE LIGHTING.
 PERMIT#: (MASTER) 13051012 (ELECTRICAL) 14050863
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 PREVIUSLY PASSED. NOT REQUIRED. PER DOUG HARVEY
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2014-08-06 Cont ID  
Sent By dhayes Date 2014-08-06 Time 11:27 Rev Time 0.00
Received By dhayes Date   Time   Sent To  
Notes
2014-08-06 11:28:28PREVIUSLY PASSED. NOT REQUIRED. PER DOUG HARVEY

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-09-10 Cont ID  
Sent By dharvey Date 2013-09-10 Time 13:16 Rev Time 0.00
Received By dharvey Date 2013-09-10 Time 12:15 Sent To  
Notes
2013-09-10 12:24:26THE REVIEW COMMENTS FROM THE FIRST REVIEW HAD BEEN
 ADDRESSED.
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 11:26 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 09:37 Sent To  
Notes
2013-08-05 11:26:40SHEET E1001 - ARE "POWER COMPANY FEEDERS" PROVIDED BY
 FPL OR CUSTOMER? IF BY CUSTOMER, COMPLY WITH 240.4
 NOTES ADDED TO PLANS FOR LOCATIONS OF SMOKE ALARMS IN
 UNITS TO BE PER MANUFACTURERS INSTRUCTIONS AND TO
 PROVIDE BEST EARLY DETECTION WITHOUT NUISANCE ALARMING
 ALL CONDUCTORS TO BE SIZED PER NEC 310.15 AND
 ASSOCIATED NOTES
 CONDUCTOR SETS PROTECTED IN EXCESS OF 800 TO BE FULL
 SIZE RATED FOR THE OVERCURRENT DEVICE
 SIZE GROUNDING ELECTRODE CONDUCTORS BASED ON TOTAL
 SERVICE CONDUCTOR SIZE (250.66) AND EQUIPMENT GROUNDING
 CONDUCTORS BASED ON OCP (250.122)
 FIELD INSPECTOR TO VERIFY COMPLIANCE WITH FAIR HOUSING
 GUIDELINES FOR HEIGHT OF RECEPTACLES AND SWITCHES
 NUMEROUS NOTES ADDED TO PLANS AS "TYPICAL" NOTES TO BE
 COMPLIED WITH
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2013-11-07 Cont ID  
Sent By mgonzale Date 2013-11-07 Time   Rev Time 1.00
Received By mgonzale Date 2013-11-07 Time   Sent To I
Notes
2013-11-07 10:28:53PASSED

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2013-09-18 Cont ID  
Sent By Mgonzale Date 2013-09-18 Time   Rev Time 0.50
Received By mgonzale Date 2013-09-18 Time   Sent To I
Notes
2013-09-18 13:36:32CITY OF WPB ENGINEERING AND PUBLICWORKS DEPARTMENT
 WAITING ON APPROVAL LETTER FROM SOUTH FLORIDA WATER
 MANAGEMENT AND PAYMENT FOR DEVELOPMENT PERMIT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-08-07 Cont ID  
Sent By Mgonzale Date 2013-08-07 Time   Rev Time 1.00
Received By mgonzale Date 2013-08-07 Time   Sent To I
Notes
2013-08-07 09:05:11THE JEFFERSON IS BEING REVIEWED THRU ENGINEERING SITE
 DEVELOPMENT PROCESS.
 EOR IS INCORPORATING COMMENTS SPECIFIC TO ENGINEERING.
 THANKS!
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-11-07 Cont ID  
Sent By wjolin Date 2013-11-07 Time 12:39 Rev Time 0.00
Received By wjolin Date 2013-11-07 Time 12:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-10-05 Cont ID  
Sent By wjolin Date 2013-10-05 Time 18:14 Rev Time 0.00
Received By wjolin Date 2013-10-05 Time 16:54 Sent To  
Notes
2013-10-05 18:14:42300 COURTNEY LAKES CIRLCE
 (PREVIOUSLY: O LAMBERTON DRIVE)
 PERMIT #13051012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NEW COMMENT: THE PLANS INDICATE AN ADDRESS OF 344
 COURTNEY LAKES CIRCLE; HOWEVER, NONE OF THE SITE
 DRAWINGS SHOW A ROAD NAMED COURTNEY LAKES CIRCLE.
  
 FD RESPONSE: CITY PROJECT #E13040012 IS A COMPLETELY
 SEPARATE DEPARTMENT (ENGINEERING). BECAUSE THIS IS
 PRIVATE PROPERTY, THE CIVIL ENGINEERING DRAWINGS WILL
 ALSO NEED TO BE SUBMITTED TO THE BUILDING DEPARTMENT IF
 A PERMIT IS TO BE ISSUED. THE MAIN ENTRANCE ROAD INTO
 THE COMPLEX IS A FIRE LANE AND NEEDS TO MARKED.
 ADDITIONALLY AREAS NEAR FIRE HYDRANTS AND FIRE
 DEPARTMENT CONNECTIONS NEED TO BE MARKED AS WELL.
 ORIGINAL COMMENT: NO FIRE FLOW CALCULATIONS OR CIVIL
 ENGINEERING PLANS SUBMITTED SHOWING FIRE WATER, FIRE
 HYDRANTS, FIRE DEPARTMENT ACCESS ROADS (FIRE LANES),
 ETC. PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND
 FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH
 CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4' TO
 THE BACKSIDE. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE
 DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED
 TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32
 TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF
 NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. PER
 SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE MARKED
 WITH FREESTANDING SIGNS READING, "FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL
 BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 FD RESPONSE: EMERGENCY VEHICLES MAY USE THE ENTIRE
 DEAD-END LENGTH FOR STAGING OR FIRE AND RESCUE
 OPERATIONS; THEREFORE PROVISIONS TO TURN AROUND ARE
 REQUIRED.
 ORIGINAL COMMENT: SHEET A0.10 - BUILDING #4: DEAD-END
 FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF 150 FEET IN
 LENGTH SHALL BE PROVIDED WITH APPROVED PROVISIONS FOR
 THE FIRE APPARATUS TO TURN AROUND.
  
 FD RESPONSE: PER NFPA 1 SECTION 18.3.3, FIRE HYDRANTS
 SHALL BE PROVIDED AT LOCATIONS APPROVED BY THE AHJ.
 ORIGINAL COMMENT: NO FIRE HYDRANTS PROVIDED ON SOUTH
 SIDE OF BUILDINGS #10 AND #11.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By wjolin Date 2013-07-02 Time 15:16 Rev Time 0.00
Received By wjolin Date 2013-06-29 Time 16:49 Sent To  
Notes
2013-06-29 19:44:17O LAMBERTON DRIVE
 PERMIT #13051012
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK
 SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH
 AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 NO FIRE FLOW CALCULATIONS OR CIVIL ENGINEERING PLANS
 SUBMITTED SHOWING FIRE WATER, FIRE HYDRANTS, FIRE
 DEPARTMENT ACCESS ROADS (FIRE LANES), ETC. PER SECTION
 18.3.4.1 (NFPA 1), FIRE HYDRANTS AND FIRE DEPARTMENT
 CONNECTIONS SHALL BE PROVIDED WITH CLEARANCES OF 7'-6"
 TO THE FRONT AND SIDES AND 4' TO THE BACKSIDE. PER
 SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 32 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
 SHEET A0.10: PROVIDE A KNOX KEY SWITCH TO ALLOW GATE
 ACCESS TO EMERGENCY RESPONDERS. KEY SWITCH CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET A0.10 - BUILDING #4: DEAD-END FIRE DEPARTMENT
 ACCESS ROADS IN EXCESS OF 150 FEET IN LENGTH SHALL BE
 PROVIDED WITH APPROVED PROVISIONS FOR THE FIRE
 APPARATUS TO TURN AROUND.
  
 SHEET F1.001: ALL FIRE SPRINKLER SYSTEMS SHALL BE
 MONITORED BY AN APPROVED SUPERVISING STATION IN
 ACCORDANCE WITH NFPA 72.
  
 SHEET F1.11 (TYPICAL): THE APARTMENT BUILDING CORRIDORS
 WILL BE REQUIRED TO BE PROTECTED BY SPRINKLERS BECAUSE
 THE CORRIDORS ARE NOT AT LEAST 50% OPEN. THE CORRIDOR
 SPRINKLERS ARE PERMITTED TO BE RESIDENTIAL STYLE PER
 NFPA 13R.
  
 SHEET F6.01: THE SPRINKLER RISER DETAIL INDICATES THE
 FIRE DEPARTMENT CONNECTION CONNECTED TO THE UNDERGROUND
 FIRE MAIN. CHECK VALVES WILL BE NEEDED IN THE
 UNDERGROUND FIRE MAIN PIPING TO PREVENT THE FIRE
 DEPARTMENT FROM PRESSURIZING THE UNDERGROUND FIRE MAIN
 LOOP SUPPLYING THE SITE. RECOMMEND CONNECTING THE FIRE
 DEPARTMENT CONNECTION DOWNSTREAM OF THE RISER BUTTERFLY
 VALVE.
  
 SHEET E401: SMOKE ALARM MISSING FROM OUTSIDE OF BEDROOM
 DOORS IN UNIT A01.
  
 SHEET E402: SMOKE ALARM MISSING FROM OUTSIDE OF WEST
 BEDROOM DOORS IN UNIT B02.
  
  
 NOTES:
 NO FIRE HYDRANTS PROVIDED ON SOUTH SIDE OF BUILDINGS
 #10 AND #11.
  
 FIRE DEPARTMENT CONNECTIONS ARE TO BE LOCATED WITHIN
 150 FEET OF A FIRE HYDRANT.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-08-15 Cont ID  
Sent By shill Date 2014-08-15 Time 15:23 Rev Time 0.00
Received By shill Date 2014-07-23 Time 09:38 Sent To  
Notes
2014-07-23 09:38:49TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-05-15 Cont ID  
Sent By skennedy Date 2014-05-15 Time 14:00 Rev Time 0.00
Received By skennedy Date 2014-05-13 Time 09:23 Sent To  
Notes
2014-05-15 09:24:30STRUCTURAL PACKAGE SUBMITTED ON 5/13/14 SENT TO JIM'S
 DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-12 Cont ID  
Sent By shill Date 2013-11-12 Time 17:30 Rev Time 0.00
Received By shill Date 2013-10-22 Time 11:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-15 Cont ID  
Sent By shill Date 2013-10-09 Time 18:01 Rev Time 0.00
Received By shill Date 2013-08-28 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-07 Cont ID  
Sent By rregueir Date 2013-08-06 Time 10:30 Rev Time 0.00
Received By rregueir Date 2013-06-17 Time 14:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 14:24 Rev Time 0.00
Received By jwitmer Date 2013-10-24 Time 14:23 Sent To  
Notes
2013-11-04 14:25:3610/24/2013
 IMPACT FEES PAID
 $1,647,080.64

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 15:00 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 15:00 Sent To  
Notes
2013-09-25 15:00:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-07-20 Cont ID  
Sent By jwitmer Date 2013-07-20 Time 12:24 Rev Time 0.00
Received By jwitmer Date 2013-07-20 Time 12:24 Sent To  
Notes
2013-07-20 12:24:45BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-07-17 Cont ID  
Sent By hmoser Date 2014-07-17 Time 08:32 Rev Time 0.00
Received By hmoser Date 2014-07-17 Time 08:32 Sent To  
Notes
2014-07-17 08:51:33OK TO INSTALL BRASS WATER MEATIER # NM15P IN RETURN AIR
 PLENUM
 HM. 7/17/14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-08 Cont ID  
Sent By rregueir Date 2013-10-08 Time 16:31 Rev Time 0.00
Received By rregueir Date 2013-10-08 Time 16:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-08-06 Cont ID  
Sent By rregueir Date 2013-08-06 Time 15:45 Rev Time 0.00
Received By rregueir Date 2013-08-05 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-17 Cont ID  
Sent By lwagner Date 2013-09-17 Time 14:57 Rev Time 0.00
Received By lwagner Date 2013-09-17 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By lwagner Date 2013-06-27 Time 15:52 Rev Time 0.00
Received By lwagner Date 2013-06-24 Time 12:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-01-17 Cont ID  
Sent By rregueir Date 2014-01-17 Time 16:34 Rev Time 0.00
Received By rregueir Date 2014-01-17 Time 16:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-07-31 Cont ID  
Sent By ajones Date 2014-07-31 Time 16:44 Rev Time 0.00
Received By ajones Date 2014-07-31 Time 16:44 Sent To E
Notes
2014-07-24 14:45:357/24/14 ZONING SENT TO AV. SG

Review Stop Z ZONING
Rev No 2 Status P Date 2013-10-09 Cont ID  
Sent By avann Date 2013-10-09 Time 12:47 Rev Time 0.00
Received By ajones Date 2013-10-09 Time 12:47 Sent To  
Notes
2013-09-16 19:00:249/16/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-07-23 Cont ID  
Sent By avann Date 2013-07-23 Time 11:41 Rev Time 0.00
Received By ajones Date 2013-07-23 Time 11:40 Sent To  
Notes
2013-07-23 12:52:397/23/13- FAILED
 1. PARKING COUNTS IN EACH AREA NEEDS TO BE SHOWN ON
 THE SITE PLAN.
 2. ALL WIDTH AND SETBACKS NEED TO BE SHOWN ON THE SITE
 PLAN.
 3. THE PARKING ALIGNMENT IN FRONT OF THE MAIL KIOSK
 APPEARED TO HAVE CHANGED. PLEASE INDICATE HOW THE
 PARKING LAYOUT AND COUNTY HAS CHANGED.
 4. THE FOLLOWING BUILDING HEIGHTS HAVE INCREASE OVER
 THE ORIGINAL APPROVAL:
 BUILDING TYPE 1- 34?9?? TO 36?6??
 BUILDING TYPE 2- 34?9? TO 34?10?
 BUILDING TYPE 3- 34?9? TO 36?7?
 BUILDING TYPE 4- 34?9? TO 36?6?
 BUILDING TYPE 5- 35?71/2? TO 37?4?
  
 5. THE SITE PLAN SHOWS A BUILDING TYPE 9 WHICH WAS NOT
 PART OF THE ORIGINAL APPROVAL.
 6. IT APPEARS THAT BUILDING TYPE 1 LEFT ELEVATION HAS
 CHANGED FROM THE ORIGINAL APPROVAL. PLEASE VERIFY
 ALL OF THE ABOVE CHANGES TO THE SITE PLAN APPROVED BY
 THE CITY COMMISSION REQUIRE THAT A MINOR PLANNED
 DEVELOPMENT BE PROCESSED BY THE PLANNING DIVISION. YOU
 CAN CONTACT ME FOR ADDITIONAL INFORMATION ABOUT THE
 PROCESS.
  
 ANGELLA VANN, PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]
  
2013-06-20 09:25:366/20/13