Plan Review Details - Permit 13051007
Plan Review Stops For Permit 13051007
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2013-07-10 Time 16:14 Sent To  
Notes
2013-07-11 09:46:562010 FBC
  
 REVISION REQUIRED
  
 1) SUBMIT TWO COPIES OF RAS 117 CALCULATIONS FOR
 ENHANCED FASTENING FOR THE GAF BUILT-UP ROOFING SYSTEM
 (NOA NO. 07-1219.09). FBC EXISTING BUILDING SECTION
 611.1 AND FBC R905.1
  
  
 NOTE: IMPACT PROTECTION FOR GLAZED OPENINGS IS
 EXISTING. SEE PERMIT # 09020357
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-18 Cont ID  
Sent By rmcdouga Date 2013-06-18 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2013-06-17 Time 07:48 Sent To  
Notes
2013-06-18 10:02:342010 FBC
  
 DENIED BY BUILDING
  
 1) SPECIFY THE DESIGN DATA ON THE PLANS. THE WIND-SPEED
 FOR THIS PROJECT IS 170 MPH VULT / 132 VASD AND THE
 EXPOSURE CATEGORY IS B. SEE FBC R301.2.1.1
  
 2) THE ROOF UPLIFT PRESSURES ON SHEET A.2 ARE LOW.
 PLEASE REVISE. FBC R301.2.1.1
  
 3) PLEASE UPDATE THE EDITION OF ASCE 7 TO THE CURRENT
 REFERENCED ADDITION, WHICH IS ASCE 7-10. FBCR CHAPTER
 43.
  
 4) THIS PROJECT IS NOT LOCATED IN DADE COUNTY ( HVHZ )
 AS INDICATED ON SHEET A.1. THE PROJECT IS LOCATED IN
 THE CITY OF WEST PALM BEACH IN PALM BEACH COUNTY.
 PLEASE CORRECT.
  
 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE
 PROTECTION.
  
 6) SHOW COMPLIANCE WITH FBC R403.1.4 WHICH REQUIRES
 EXTERIOR FOOTINGS TO BE 12" BELOW GRADE.
  
 7) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES
 EXTERIOR FOUNDATION WALLS TO EXTEND A MINIMUM 6 INCHES
 ABOVE ADJACENT FINISHED GRADE.
  
 8) SHOW COMPLIANCE WITH FBC R 703.2 FOR REQUIRED
 WEATHER-RESISTIVE BARRIER.
  
 9) SPECIFY THE ROOF OVERHANG TO SHOW COMPLIANCE WITH
 FBC R 318.6 FOR GUTTERS WITH DOWNSPOUTS THAT DISCHARGE
 AT LEAST ONE FOOT AWAY FROM EXTERIOR WALLS ON BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES OF HORIZONTAL
 PROJECTION.
  
 10) SHOW COMPLIANCE WITH FBC R 806.1 FOR ROOF
 VENTILATION.
  
 11) THE PLANS SPECIFY R-30 BATT INSULATION IN THE 2 X 6
 SINGLE ASSEMBLY ROOF/CEILING AND R-19 BATT INSULATION
 IN THE 2 X 4 FRAME WALLS. BATT INSULATION OF THESE R
 VALUES REQUIRE MORE SPACE THAN THE SPECIFIED ASSEMBLIES
 PROVIDE. PLEASE CORRECT. FBC ENERGY CONSERVATION
 CHAPTER 4 AND CITY AMENDMENTS 107.2.1
  
 12) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS, AS
 REQUIRED BY DCA RULE 9N-3, FOR THE ROOF COVERING
 (SIGNED AND SEALED RAS117 CALCULATIONS IF REQUIRED),
 THE EXTERIOR DOOR, THE STRUCTURAL CONNECTORS AND THE
 DUROCK SHEATHING.
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 14) PRODUCT APPROVALS WERE SUBMITTED FOR A SLIDING
 GLASS DOOR AND SINGLE HUNG WINDOWS. HOWEVER, THE SCOPE
 OF WORK DID NOT INDICATE ANY OF THESE BEING INSTALLED.
 PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 15) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. CITY
 AMENDMENTS 107.2.1.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-17 Cont ID  
Sent By rmcdouga Date 2013-06-17 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2013-06-17 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 09:47 Rev Time 0.00
Received By rmcdouga Date 2013-07-05 Time 15:31 Sent To B
Notes
2013-07-05 15:32:39PULLED DENIED PLANS & ROUTED TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-18 Cont ID  
Sent By rmcdouga Date 2013-06-18 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2013-05-30 Time 16:03 Sent To  
Notes
2013-05-30 16:04:05R12
  
2013-05-30 07:54:02INCOMING SENT TO MISC BOX # 1. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-17 Cont ID  
Sent By rmcdouga Date 2013-06-17 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2013-06-17 Time 08:13 Sent To  
Notes
2013-06-17 08:20:48VENT FOR CLOTHES DRYER IS THE ONLY WORK SHOWN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-17 Cont ID  
Sent By rmcdouga Date 2013-06-17 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2013-06-17 Time 07:33 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-07-11 Cont ID  
Sent By rmcdouga Date 2013-07-11 Time 09:39 Rev Time 0.00
Received By rmcdouga Date 2013-07-11 Time 09:39 Sent To  
Notes
2013-07-11 09:41:41PRODUCT APPROVAL FOR GAF BUILT-UP ROOF NOA NO.
 07-1219.09 WAS SUBMITTED. HOWEVER, RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING ARE REQUIRED TO BE SUBMITTED AS
 A REVISION.