Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-03 Cont ID  
Sent By hmoser Date 2013-06-03 Time 13:10 Rev Time 0.00
Received By hmoser Date 2013-06-03 Time 13:00 Sent To  
Notes
2013-06-03 13:10:03PLANS DENIED
 1) REFER TO SECTION M1602.4 BALANCED
 RETURN AIR 2010 RESIDENTIAL BUILDING CODE.
 2) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS
 3) PROVIDE SIGNATURE AND LICENSE NUMBER OF
 WHO DID THE PLANS ON THE PLANS
 4) PROVIDE A COPY OF THE ARI WITH THE PLANS.
 2,3 AND 4 REFER TO SECTION 107 FBC 2010