| Plan Review Stops For Permit 13050990 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2013-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-26 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-26 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2013-10-26 12:34:18 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | PLAYGROUND EQUIPMENT PASSED PER RB. | | | | | | FBC 2010 ACCESSIBILITY 1008.2.6 | | | | | | GROUND SURFACES ON ACCESSIBLE ROUTES, CLEAR FLOOR OR | | | GROUND SPACES, AND TURNING SPACES SHALL COMPLY WITH | | | 1008.2.6. | | | | | | GROUND SURFACES SHALL COMPLY WITH ASTM F 1951. | | | | | | 1008.2.6.2, GROUND SURFACES LOCATED WITHIN USE ZONES | | | SHALL COMPLY WITH ASTM F 1292. | | | | | | SITE PLAN TO INDICATE WHICH SURFACE(S) IS OR ARE | | | PROPOSED. PROVIDE SPECS SHOWING COMPLIANCE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2013-10-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2013-10-09 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2013-10-09 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2013-10-09 15:55:39 | PROVISO: PLAYGROUND SURFACE IS ENGINEERED WOOD FIBER | | | FOR WHEELCHAIR ACCESSIBILITY, PER TROY KUNKEL, FORM | | | KOMPAN, (EMAIL: [email protected]), AND ADAM HODES, | | | FROM IBIS BUILDING CORP (EMAIL: [email protected]). | | | | | | GALAXY CUSTOM CONFIGURATION COMPLIES WITH TABLE | | | 240.2.1.2 OF FLORIDA ACCESSIBILITY CODE (2012 EDITION). | | | OF THE 17 PLAY COMPONENTS PROVIDED, 4 ARE CONSIDERED | | | ELEVATED PLAY COMPONENTS BECAUSE THEY CANNOT BE | | | APPROACHED AND EXITED WITHIN THE REACH RANGE OF 16 | | | INCHES TO 44 INCHES ABOVE GRADE FOR AGES 9 THROUGH 12, | | | AND THE REMAINING 13 ARE CONSIDERED GROUND LEVEL PLAY | | | COMPONENTS BECAUSE THEY CAN BE APPROACHED AND EXITED | | | WITHIN THE REACH RANGE OF 16 INCHES TO 44 INCHES ABOVE | | | GRADE FOR AGES 9 THROUGH 12. | | | | | | | | | REVIEW LEFT IN FAILED STATUS UNTIL THE FOLLOWING TWO | | | ITEMS HAVE BEEN ADDRESSED. ADAM HODES, FROM IBIS | | | BUILDING CORP., ADVISED THAT HE WILL PROVIDE THE | | | FOLLOWING DOCUMENTS: | | | | | | 1) PLEASE PROVIDE ORIGINAL SIGNED AND SEALED WIND LOAD | | | CERTIFICATION LETTER FROM THOMAS SADLER, P.E. THE TWO | | | COPIES PROVIDED ARE COLOR COPIES OR SCANS MADE FROM THE | | | ORIGINAL. | | | | | | 2) THE SUBMITTED SURVEY DRAWING STATES THAT THE | | | PLAYGROUND EQUIPMENT IS TO BE INSTALLED IN A "MULCHED | | | AREA". A MULCHED AREA IS NOT ACCESSIBLE BY WHEELCHAIR. | | | ADAM HODES, FROM IBIS BUILDING CORP (EMAIL: | | | [email protected]), AND TROY KUNKEL, FORM KOMPAN | | | (EMAIL: [email protected]), BOTH ADVISED THAT THE | | | PLAYGROUND SURFACE IS ENGINEERED WOOD FIBER FOR | | | WHEELCHAIR ACCESSIBILITY. ADAM WILL SUBMIT THE | | | MANUFACTURER'S SPECIFICATION FOR THE ENGINEERED WOOD | | | FIBER. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | TELEPHONE: (561) 805 6652 ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2013-09-27 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-27 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-27 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2013-09-27 16:19:32 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FLORIDA BUILDING CODE 2010 ACCESSIBILITY: | | | | | | 1. SEE SECTION 240.2.2 ADVISORY, "SOME PLAY COMPONENTS | | | THAT ARE ATTACHED TO A COMPOSITE PLAY STRUCTURE CAN BE | | | APPROACHED OR EXITED AT THE GORUND LEVEL OR ABOVE GRADE | | | FROM A PLATFORM OR DECK. FOR EXAMPLE, A CLIMBER | | | ATTACHED TO A COMPOSITE PLAY STRUCTURE CAN BE | | | APPROACHED OR EXITED AT THE GROUND LEVEL OR ABOVE GRADE | | | FROM A PLATFORM OR DECK ON A COMPOSITE PLAY STRUCTURE. | | | PLAY COMPONENTS THAT ARE ATTACHED TO A COMPOSITE PLAY | | | STRUCTURE AND CAN BE APPROACHED FROM A PLATFORM OR DECK | | | (E.G. CLIMBERS AND OVERHEAD PLAY COMPONENTS) ARE | | | CONSIDERED ELEVATED PLAY COMPONENTS. | | | | | | THE PLAY EQUIPMENT AS DESIGNED IS CONSIDERED ELEVATED | | | PER DEFINITION AND ADVISORY IN THE FLORIDA BUILDING | | | CODE/ ADA. | | | | | | SEE ALSO THE DEFINITION OF "ELEVATED PLAY COMPONENT" - | | | A PLAY COMPONENT THAT IS APPROACHED ABOVE OR BELOW | | | GRADE AND THAT IS PART OF A COMPOSITE PLAY STRUCTURE | | | CONSISTING OF TWO OR MORE PLAY COMPONENTS ATTACHED OR | | | FUNCTIONALLY LINKED TO CREATE AN INTEGRATED UNIT | | | PROVIDING MORE THAN ONE PLAY ACTIVITY. | | | | | | 2. SEE PREVIOUS LISTS, COMPLY WITH TABLE 240.2.1, | | | SECTION 240, 1008. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2013-09-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-11 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-11 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2013-09-11 18:59:38 | ****CORRECTIONS**** | | | | | | COMMENT LIST BASED ON MANUFACTURER'S REQUEST FOR A MORE | | | DETAILED PLAN REVIEW WITH SPECIFICS AS TO WHY THIS IS | | | NOT CONSIDERED A GROUND LEVEL COMPONENT | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC107, PROVIDE ARCHITECTURAL DRAWINGS, TO SCALE, | | | WITH DIMENSIONS AND MATERIALS PROPOSED. PLANS PROVIDED | | | DO NOT PROVIDE DIMENSIONS, REACH RANGES, MATERIALS. | | | COMPONENTS ARE NAMED BUT NO PLANS PROVIDED WHICH SHOW | | | IN DETAIL THE MATERIALS, DIMENSIONS, AND ACTIVITIES | | | PROPOSED. | | | | | | PLANS ARE TO BE A MINIMUM OF 1/8" SCALE BUT MAY NEED TO | | | BE LARGER IF CLARITY BECOMES AN ISSUE. I TOOK A QUICK | | | GLANCE AT THE NEW DRAWING ATTACHED AND IT DOES NOT | | | INCLUDE ANY INFORMATION REGARDING DIMENSIONS OR | | | MATERIALS. | | | | | | 2. SEE FLORIDA STATUTE 481.229, EXEMPTIONS TO | | | LICENSURE. I WAS IN ERROR IN NEGLECTING TO REQUIRE | | | PLANS PREPARED, SIGNED AND SEALED BY AN ARCHITECT AS I | | | AM UNABLE TO LOCATE AN EXEMPTION FOR THIS APPLICATION. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-22 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-22 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2013-08-22 17:29:11 | RECEIVED REPLY FROM DEPARTMENT OF JUSTICE TECHNICAL | | | SUPPORT, MARY ADAMS. SHE CONFIRMED THAT THIS IS A | | | COMPOSITE PLAY STRUCTURE WITH ELEVATED COMPONENTS AND | | | COMPONENTS DO NOT COMPLY WITH REACH RANGE REQUIREMENTS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-07-25 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-07-25 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2013-07-25 16:37:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC 2010 ACCESSIBILITY: | | | | | | 1. SEE 106.1, DEFINITIONS, "ELEVATED PLAY COMPONENT" | | | AND "GROUND LEVEL PLAY COMPONENT". THE MANUFACTURER | | | PROVIDED DATA SHEETS WHICH STATE THAT ALL COMPONENTS | | | ARE "GROUND LEVEL" AND NONE ARE ELEVATED. PLEASE SEE | | | DEFINITIONS AND PROVIDE FURTHER EXPLANATION AS THE | | | EQUIPMENT PROPOSED APPEARS TO BE AN ELEVATED PLAY | | | COMPONENT. SEE ALSO SECTION 240. | | | | | | 2. PROVIDE DETAILS ON ACCESSIBLE ROUTE 1008.2.6 | | | INCLUDING DIMENSIONS AND SPECIFICATIONS. PROVIDE SPEC | | | SHEETS TO SHOW THAT IT COMPLIES WITH ASTM F 1951. | | | | | | 3. PROVIDE DETAILS ON THE USE ZONES, 1008.2.6.2. | | | PROVIDE SPEC SHEETS TO SHOW THAT PROPOSED GROUND | | | SURFACES COMPLY WITH ASTM F 1292. | | | | | | 4. SEE 240.2.2, AT LEAST 50% OF ELEVATED PLAY | | | COMPONENTS ARE TO BE ON AN ACCESSIBLE ROUTE AND SHALL | | | COMPLY WITH 1008.4. REVISE PLAN TO SHOW COMPLIANCE. | | | | | | 5. THE LINK PROVIDED PREVIOUSLY HAS CHANGED. SEE THE | | | FOLLOWING SITE FOR FURTHER GUIDANCE: | | | | | | HTTP://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/RE | | | CREATION-FACILITIES/GUIDES/PLAY-AREAS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-06-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-06-26 |
Time |
12:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-06-26 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2013-06-26 12:22:51 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. NO INFORMATION PROVIDED REGARDING ACCESSIBLE ROUTE | | | AND COMPLIANCE WITH FBC 2010 ACCESSIBILITY 1008. I WAS | | | UNABLE TO LOCATE PLAYGROUND EQUIPEMENT DETAILS FOR ALL | | | OF THE EQUIPMENT IN THE PACKAGE SUBMITTED. THERE WERE | | | TWO DETAILS, BUT THE PLAN APPEARS TO SHOW ADDITIONAL | | | EQUIPMENT TO BE INSTALLED. DETAILS DID NOT CORRELATE | | | WITH THE EQUIPMENT SITE PLAN. | | | | | | AN "ADA VIEWING AREA" IS SHOWN ON THE SURVEY. DOES THIS | | | MEAN THE INTENT IS THAT DISABLED MAY WATCH BUT NOT USE | | | THE EQUIPMENT? THIS DOES NOT MEET REQUIRMENTS OF FBC | | | ACCESSIBILITY 1008. | | | | | | NOT ENOUGH INFORMATION PROVIDED TO PROVIDE A COMPLETE | | | CHECKLIST. | | | | | | YOU MAY FIND THE FOLLOWING GUIDANCE HELPFUL: | | | | | | HTTP://WWW.ACCESS-BOARD.GOV/PLAY/GUIDE/GUIDE.PDF | | | | | | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-10-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2013-10-01 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2013-10-01 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2013-10-01 14:30:30 | FILED UNDER SMALL PLANS DENIED "I" FOR IBIS | | | CONSTRUCTION. | | 2013-09-30 08:16:17 | ZONING RECEIVED. ROUTED TO FM FOR HIST REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2013-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-26 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-18 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2013-10-18 15:13:14 | TO SH DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-10-09 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2013-10-09 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2013-09-17 |
Time |
07:39 |
Sent To |
|
|
| Notes |
| 2013-09-27 16:20:15 | TO ZONING (HISTORIC) | | | | | 2013-09-17 07:39:47 | INCOMING SENT TO S HILL. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-07-25 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-07-10 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2013-07-10 12:11:20 | INCOMING SENT TO SAMANTHAS' DESK . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-06-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-06-26 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-05-30 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2013-05-30 07:49:42 | INCOMING SENT TO ZONING BOX. JW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-06-19 |
|
|
Cont ID |
|
| Sent By |
eschnid |
Date |
2013-06-19 |
Time |
12:03 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2013-06-03 |
Time |
16:59 |
Sent To |
B |
|
| Notes |
| 2013-06-19 12:04:17 | PASSED | | | | | | EXISTING EQUIPMENT IS 8 FEET FROM NORTH PROPERTY LINE | | | | | | PROPOSED EQUIPMENT IS 8 FEET FROM NORTH PROPERTY LINE, | | | 20 FEET FROM WEST PROPERTY LINE. |
|
|