| 2013-06-13 15:25:15 | BUILDING PLAN REVIEW |
| | PERMIT: 13050986 |
| | ADD: 550 OKEECHOBEE BLVD # 1701 |
| | CONT: D'ANGELO BUILDERS INC |
| | TEL: (561)582-2028 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 6/13/13 |
| | ACTION: DENIED |
| | |
| | 1) SHEET D1.0 PROJECT DATA |
| | 1A) CONSTTRUCTION TYPE IS LISTED AS IB TABLE 503 WOULD |
| | ONLY ALLOW A 11 STORY BUILDING AND 1 EXTRA STORY FOR |
| | FIRE SPRINKLERS. THIS IS A TYPE IA CONSTRUCTION. 2010 |
| | FBC-B TABLE 503. |
| | 1B) OCCUPANCY CLASSIFICATION IS NOT R-3 THIS IS SINGLE |
| | FAMILY UN-ATTACHED, SEE 2010 FBC-B 310 R-2. |
| | |
| | 2) SHEET A-1.0 NOTE "H" INDICATES THE USE OF TRAVERTINE |
| | FLOORING, PROVIDE CODE COMPLIANCE FOR ECB PRODUCTS: |
| | 2A) FBC-B 2010 603.2 EXCEPTION (1) |
| | FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | |
| | 2B) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) SHEET A-1.0 NOTE E INDICATES THE USE OF MR BOARD IN |
| | WET AREAS, |
| | 2010 FBC-B 2509.2 BASE FOR TILE. |
| | GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| | DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| | SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| | SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| | OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| | RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| | IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| | SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| | SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| | COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| | GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| | REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| | WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| | |
| | 2509.3 LIMITATIONS. |
| | WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| | IN THE FOLLOWING LOCATIONS: |
| | |
| | 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| | COMPARTMENTS. |
| | |
| | 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| | AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| | |
| | 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| | (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| | INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| | WATER-RESISTANT GYPSUM BACKING BOARD. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |