Plan Review Details - Permit 13050983
Plan Review Stops For Permit 13050983
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-07-15 Cont ID  
Sent By shill Date 2013-07-15 Time 17:15 Rev Time 0.00
Received By shill Date 2013-07-15 Time 17:15 Sent To  
Notes
2013-07-15 17:16:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS PERMIT HAS ALREADY BEEN ISSUED. REVIEW PROVIDED
 WAS REVIEW #2; THERE WAS A 3RD REVIEW AND THE PERMIT
 WAS ISSUED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-10 Cont ID  
Sent By shill Date 2013-07-10 Time 16:50 Rev Time 0.00
Received By shill Date 2013-07-10 Time 16:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 08:14 Rev Time 0.00
Received By shill Date 2013-06-29 Time 08:14 Sent To  
Notes
2013-06-29 08:19:04****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM REVIEW #1:
  
 1-2. OK
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 2ND REVIEW, RADIANT FLUX TEST NFPA 253 PROVIDED. FBC
 803.1.1 REQUIRES TEST ASTM E 84 OR UL 723. PLEASE
 ADDRESS.
  
 4-7. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-30 Cont ID  
Sent By shill Date 2013-05-30 Time 15:10 Rev Time 0.00
Received By shill Date 2013-05-30 Time 15:10 Sent To  
Notes
2013-05-30 15:16:45****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 5. "SCOPE OF WORK" REFERS TO FRAMING, ENLARGING
 OPENINGS, BUT NOTHING SHOWN ON THE PLAN. SEE FBC 107
 REGARDING MINIMUM PLAN REVIEW CRITERIA. PROVIDE
 LOCATION AND SCOPE (DETAIL MAY BE REQUIRED).
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. VALUE IS TO INCLUDE ALL LABOR AND MATERIALS,
 INCLUDING MATERIALS SUPPLIED BY OTHERS.
  
 7. ON THE STOREFRONT PRODUCT APPROVAL, INDICATE OPTIONS
 PROPOSED TO SHOW COMPLIANCE WITH WIND DESIGN PRESSURE
 REQUIRMENTS FBC 1609.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 14:39 Rev Time 0.00
Received By dharvey Date 2013-07-05 Time 14:36 Sent To  
Notes
2013-07-05 14:39:56NO ELECTRIC SHOWN OR PROPOSED. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-06-08 Cont ID  
Sent By wjolin Date 2013-06-08 Time 10:45 Rev Time 0.00
Received By wjolin Date 2013-06-08 Time 10:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-07-15 Cont ID  
Sent By shill Date 2013-07-15 Time 17:16 Rev Time 0.00
Received By shill Date 2013-07-10 Time 09:01 Sent To  
Notes
2013-07-11 09:13:37SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-10 Cont ID  
Sent By shill Date 2013-07-10 Time 16:50 Rev Time 0.00
Received By shill Date 2013-07-03 Time 10:59 Sent To  
Notes
2013-07-08 10:59:44SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 14:40 Rev Time 0.00
Received By dharvey Date 2013-06-17 Time 10:09 Sent To  
Notes
2013-06-18 10:09:39RESUBMITTAL SENT TO B17 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-05 Cont ID  
Sent By dharvey Date 2013-07-05 Time 14:40 Rev Time 0.00
Received By dharvey Date 2013-05-29 Time 12:45 Sent To  
Notes
2013-05-30 15:09:575/30 TO B17
  
2013-05-29 12:46:11INCOMING SENT TO MISC BOX # 1. JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-04 Cont ID  
Sent By lwagner Date 2013-06-04 Time 12:37 Rev Time 0.00
Received By lwagner Date 2013-06-04 Time 11:11 Sent To  
Notes
2013-06-04 12:37:53OK TO REPLACE FIXTURES