Plan Review Details - Permit 13050982
Plan Review Stops For Permit 13050982
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-07-22 Cont ID  
Sent By shill Date 2013-07-22 Time 19:10 Rev Time 0.00
Received By shill Date 2013-07-22 Time 19:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-07-10 Cont ID  
Sent By shill Date 2013-07-10 Time 16:57 Rev Time 0.00
Received By shill Date 2013-07-10 Time 16:57 Sent To  
Notes
2013-07-10 16:58:38****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LISTS NOT FULLY ADDRESSED:
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 TO REPHRASE IN CASE THE FIRST COMMENT WAS NOT CLEAR -
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
 3RD REVIEW - A LETYTER FROM THE MANUFACTURER WAS
 PROVIDED BUT FLOOR PLAN NOT REVISED WITH REQUESTED
 INFORMATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-06-25 Cont ID  
Sent By shill Date 2013-06-25 Time 09:57 Rev Time 0.00
Received By shill Date 2013-06-25 Time 09:57 Sent To  
Notes
2013-06-25 09:59:50****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LISTS NOT FULLY ADDRESSED:
  
 1. REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 CONTRACTOR HAS STATED THAT EXISTING CLEAR OPENING IS
 29.5", PROPOSED IS 29.5". SINGLE HUNG IN A 50" HIGH
 OPENING CANNOT PROVIDE A CLEAR OPENING WHICH IS GREATER
 THAN HALF OF THE WINDOW SIZE. PLEASE EXPLAIN.
  
 2. REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
 THIS IS STATED AS 29.5". PROVIDE DOCUMENTATION FROM THE
 MANUFACTURER TO SHOW THAT A 50 5/8" HIGH SINGLE HUNG
 WINDOW WILL PROVIDE AN EGRESS CLEAR OPENING OF 29.5".
 IF THIS IS PROVIDED, DISREGARD ITEM 1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-03 Cont ID  
Sent By shill Date 2013-06-03 Time 14:35 Rev Time 0.00
Received By shill Date 2013-06-03 Time 14:35 Sent To  
Notes
2013-06-03 14:36:09****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENT FROM PREVIOUS LIST NOT FULLY ADDRESSED:
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 TO REPHRASE IN CASE THE FIRST COMMENT WAS NOT CLEAR -
  
 REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW
 IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG?
  
 REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING
 DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH
 EXISTS WHEN THE WINDOW IS FULLY OPEN.
  
 REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING
 DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE
 MANUFACTURER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-29 Cont ID  
Sent By shill Date 2013-05-29 Time 15:40 Rev Time 0.00
Received By shill Date 2013-05-29 Time 15:40 Sent To  
Notes
2013-05-29 15:43:54****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS. IF
 NON COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 2. THE "PRODUCT APPROVAL REVIEW FORM" HAS A COLUMN
 TITLED "EGRESS REQUIREMENT" AND ALL WINDOWS INDICATE
 "YES" BUT NONE APPEAR TO MEET CURRENT EGRESS
 REQUIREMENTS. IT IS SUGGESTED TO REMOVE THIS COLUMN AS
 IT IS UNLIKELY THAT ALL WINDOWS ARE REQUIRED TO MEET
 EGRESS (APPLIES TO SLEEPING ROOMS ONLY).
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2013-07-22 Cont ID  
Sent By shill Date 2013-07-22 Time 19:11 Rev Time 0.00
Received By shill Date 2013-07-19 Time 16:42 Sent To  
Notes
2013-07-19 16:43:26INCOMING SENT TO SAMANTHAS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-07-10 Cont ID  
Sent By shill Date 2013-07-10 Time 16:58 Rev Time 0.00
Received By shill Date 2013-07-08 Time 15:36 Sent To  
Notes
2013-07-08 15:37:11SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-25 Cont ID  
Sent By shill Date 2013-06-25 Time 09:59 Rev Time 0.00
Received By shill Date 2013-06-14 Time 14:13 Sent To  
Notes
2013-06-14 14:13:22TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-03 Cont ID  
Sent By shill Date 2013-06-03 Time 14:37 Rev Time 0.00
Received By shill Date 2013-05-31 Time 18:21 Sent To  
Notes
2013-05-31 18:21:49TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-29 Cont ID  
Sent By shill Date 2013-05-29 Time 15:43 Rev Time 0.00
Received By shill Date 2013-05-29 Time 12:45 Sent To  
Notes
2013-05-29 12:45:33INCOMING SENT TO MISC BOX # 1. JW