| 2013-06-19 12:58:09 | 3620 S. DIXIE HWY, BUILDING 2 |
| | PERMIT #13050894 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO***** |
| | |
| | 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK |
| | INFORMATION. |
| | 2. SHEET E-1.2: SHOW COMBINATION CO/SMOKE ALARM OUTSIDE |
| | GARAGE DOOR FOR RETAIL/OFFICE FLOOR PLAN AS SHOWN IN |
| | PRIOR FLOOR PLANS. |
| | 3. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION |
| | OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | 4. ALL CONSTRUCTION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | 5. PROVIDE BUILDING AND UNIT ADDRESSES VISIBLE FROM THE |
| | STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND |
| | BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND |
| | SHALL CONTRAST THE BACKGROUND (REFERENCE: SECTION |
| | 10.12.1.2 OF THE FLORIDA FIRE PREVENTION CODE - NFPA |
| | 1). |
| | 6. STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER "RF" |
| | (ROOF-FLOOR) DESIGNATION PER FLORIDA STATUTE 633.027 |
| | AND FLORIDA ADMINISTRATIVE CODE 69A-60.0081. |
| | 7. SHEET A-1UA: DOORS SUCH AS #9 SHOULD HAVE A FIRE |
| | RESISTANCE RATING OF 90 MINUTES WHEN LOCATED WITHIN A |
| | 2-HOUR FIRE BARRIER. |
| | 8. COMMERCIAL SPACE: PROVIDE PORTABLE FIRE |
| | EXTINGUISHERS. EXTINGUISHERS SHALL HAVE A MINIMUM |
| | RATING OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED |
| | FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO |
| | EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | 9. FIRE SPRINKLER: INDICATE THE LOCATION OF THE FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | |
| | LAUREN PHILMORE |
| | FIRE INSPECTOR II / INVESTIGATOR I |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 804-4783 |
| | |
| | |