| 2013-06-10 10:38:03 | BUILDING PLAN REVIEW |
| | PERMIT: 13050866 |
| | ADD: 1220 ORTEGA RD |
| | CONT: WILBUR HOBGOOD CONST. |
| | TEL: (561)691-9686 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 6/10/2013 |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) SHEET A-5: |
| | 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS. |
| | THE NEW DOORWAY SWINGS OUT OVER THE LANDING. |
| | |
| | 2B) THE NEW ACCESS RAMP AND DOORWAY THE TOP LANDING |
| | FROM THE LATCH SIDE OF THE DOOR TO THE EDGE OF THE TOP |
| | LANDING IS INDICATED AS 1'-4" PLEASE SEE FIGURE |
| | 404.2.4.1(I) FOR DOOR WITH SIDE APPROACH, DOOR PROVIDED |
| | WITH DOOR CLOSER. |
| | |
| | 2C) TOP LANDING WILL NEED TO BE A MINIMUM OF 5'0" WIDE |
| | SINCE THERE IS A 90 DEGREE TURN REQUIRED TO ENTER THE |
| | NEW ADDITION. |
| | |
| | 2D) THE PLANS DO NOT PROVIDE ANY STRUCTURAL DETAILS |
| | (FOUNDATION OR REINFORCING, SLAB) FOR THE NEW |
| | ACCESSIBLE RAMP NOR THE NEW STAIR LEADING INTO THE NEW |
| | OFFICE. 2010 WPB ADMINISTRATIVE CODE |
| | COMMERCIAL PLAN REVIEW: STRUCTURAL REQUIREMENTS, |
| | ACCESSIBLITY REQUIREMENTS. 2010 FBC-ACCESSIBILITY |
| | 405.1-9. |
| | |
| | 2E) PLEASE PROVIDE A DETAIL WITH DIMENSIONING, IT |
| | APPEARS THE WATER CLOSET IS LOCATED 2'-0" CENTERED FROM |
| | THE WALL, AND THERE IS ONLY 4'-3" FROM THE WALL TO THE |
| | LAVATORY. 2010 FBC- ACCESSIBILITY CODE 604.2 & 604.3.1 |
| | & FIGURE 604.3.1. |
| | |
| | 2F) ATTIC STORAGE ABOVE, AND SHEET A-8 TRUSS LOADING NO |
| | LOADING CRITERIA FOR ATTIC STORAGE PLEASE REVIEW 2010 |
| | FBC-B TABLE 1607.1 (29) ROOFS- ALL OTHER OCCUPANCIES |
| | 300 PSF OR (36) LIGHT 125 PSF. |
| | |
| | 3) SHEET A-8: |
| | 3A) THIS SHEET LIST THE WIND EXPOSURE AS "B" PLEASE |
| | CORRECT TO "C" EXPOSURE. 2010 FBC-B 1609.4.2 SURFACE |
| | ROUGHNESS C THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO |
| | ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE |
| | TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET |
| | HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE |
| | ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN |
| | 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN |
| | THE UPWIND DIRECTION... TO THE EAST EXPOSURE "C". THIS |
| | WILL CREATE HIGHER PRESSURES WITH THE EXPOSURE & HEIGHT |
| | FACTORS. |
| | |
| | 3B) TYPICAL WALL SECTION, THE LEDGER FOR THE 2 X 12S' |
| | DOES NOT INDICATE TYPE OR SIZE OF ANCHOR OR IF THERE IS |
| | A BEAM THAT IT IS BEING ATTACHED TO? THE SAME PROBLEM |
| | WITH THE ROOF LEDGER NO INFORMATION AS TO WHAT THE |
| | LEDGERS ARE ATTACHING TO? ADDITIONAL INFORMATION |
| | REQUIRED, PART OF THE MWFRS. |
| | |
| | 3C) ADDITIONAL INFORMATION REQUIRED A8 VERSES A6, THE |
| | PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE BEAM OR |
| | LINTEL. |
| | 4 DOORS ARE DRAWN TO A 7'-0" ELEVATION |
| | 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF |
| | BEAM |
| | ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR |
| | 12'-9" APPPROX. |
| | SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE |
| | LANDING. |
| | |
| | 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. INSULATED ROLL UP-DOORS |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) SHEET SHEET M-1 INDICATE THE USE OF ROOF STANDS, M2 |
| | INDICATES THE ROOF STANDS BEING TIED DOWN TO A CONCRETE |
| | DECK PLEASE PROVIDE LOCATION OR ARE THEY BEING PLACED |
| | ON THE NEW WOOD DECKS? ADDITIONAL INFORMATION REQUIRED. |
| | 107.2.1.3. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |