Plan Review Details - Permit 13050866
Plan Review Stops For Permit 13050866
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-10 Cont ID  
Sent By jwitmer Date 2013-06-10 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2013-06-10 Time 07:03 Sent To  
Notes
2013-06-10 10:38:03BUILDING PLAN REVIEW
 PERMIT: 13050866
 ADD: 1220 ORTEGA RD
 CONT: WILBUR HOBGOOD CONST.
 TEL: (561)691-9686
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 6/10/2013
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 2) SHEET A-5:
 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS.
 THE NEW DOORWAY SWINGS OUT OVER THE LANDING.
  
 2B) THE NEW ACCESS RAMP AND DOORWAY THE TOP LANDING
 FROM THE LATCH SIDE OF THE DOOR TO THE EDGE OF THE TOP
 LANDING IS INDICATED AS 1'-4" PLEASE SEE FIGURE
 404.2.4.1(I) FOR DOOR WITH SIDE APPROACH, DOOR PROVIDED
 WITH DOOR CLOSER.
  
 2C) TOP LANDING WILL NEED TO BE A MINIMUM OF 5'0" WIDE
 SINCE THERE IS A 90 DEGREE TURN REQUIRED TO ENTER THE
 NEW ADDITION.
  
 2D) THE PLANS DO NOT PROVIDE ANY STRUCTURAL DETAILS
 (FOUNDATION OR REINFORCING, SLAB) FOR THE NEW
 ACCESSIBLE RAMP NOR THE NEW STAIR LEADING INTO THE NEW
 OFFICE. 2010 WPB ADMINISTRATIVE CODE
 COMMERCIAL PLAN REVIEW: STRUCTURAL REQUIREMENTS,
 ACCESSIBLITY REQUIREMENTS. 2010 FBC-ACCESSIBILITY
 405.1-9.
  
 2E) PLEASE PROVIDE A DETAIL WITH DIMENSIONING, IT
 APPEARS THE WATER CLOSET IS LOCATED 2'-0" CENTERED FROM
 THE WALL, AND THERE IS ONLY 4'-3" FROM THE WALL TO THE
 LAVATORY. 2010 FBC- ACCESSIBILITY CODE 604.2 & 604.3.1
 & FIGURE 604.3.1.
  
 2F) ATTIC STORAGE ABOVE, AND SHEET A-8 TRUSS LOADING NO
 LOADING CRITERIA FOR ATTIC STORAGE PLEASE REVIEW 2010
 FBC-B TABLE 1607.1 (29) ROOFS- ALL OTHER OCCUPANCIES
 300 PSF OR (36) LIGHT 125 PSF.
  
 3) SHEET A-8:
 3A) THIS SHEET LIST THE WIND EXPOSURE AS "B" PLEASE
 CORRECT TO "C" EXPOSURE. 2010 FBC-B 1609.4.2 SURFACE
 ROUGHNESS C THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN
 THE UPWIND DIRECTION... TO THE EAST EXPOSURE "C". THIS
 WILL CREATE HIGHER PRESSURES WITH THE EXPOSURE & HEIGHT
 FACTORS.
  
 3B) TYPICAL WALL SECTION, THE LEDGER FOR THE 2 X 12S'
 DOES NOT INDICATE TYPE OR SIZE OF ANCHOR OR IF THERE IS
 A BEAM THAT IT IS BEING ATTACHED TO? THE SAME PROBLEM
 WITH THE ROOF LEDGER NO INFORMATION AS TO WHAT THE
 LEDGERS ARE ATTACHING TO? ADDITIONAL INFORMATION
 REQUIRED, PART OF THE MWFRS.
  
 3C) ADDITIONAL INFORMATION REQUIRED A8 VERSES A6, THE
 PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE BEAM OR
 LINTEL.
 4 DOORS ARE DRAWN TO A 7'-0" ELEVATION
 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF
 BEAM
 ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR
 12'-9" APPPROX.
 SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE
 LANDING.
  
 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS. INSULATED ROLL UP-DOORS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 7) SHEET SHEET M-1 INDICATE THE USE OF ROOF STANDS, M2
 INDICATES THE ROOF STANDS BEING TIED DOWN TO A CONCRETE
 DECK PLEASE PROVIDE LOCATION OR ARE THEY BEING PLACED
 ON THE NEW WOOD DECKS? ADDITIONAL INFORMATION REQUIRED.
 107.2.1.3.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By dharvey Date 2013-06-07 Time 13:41 Rev Time 0.00
Received By dharvey Date 2013-06-07 Time 13:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 09:26 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 08:50 Sent To  
Notes
2013-06-15 09:26:461220 ORTEGA ROAD
 PERMIT #13050866
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 LOADING DOCK INDOOR STORAGE AREA APPEARS TO ONLY HAVE
 ONE EXIT (SIDE SWINGING DOOR). NFPA 101 CHAPTER 40
 (STORAGE OCCUPANCIES) PERMITS A SINGLE MEANS OF EGRESS
 WHEN THE STORAGE HAZARD IS "LOW." HOWEVER, MOST STORAGE
 OCCUPANCIES ARE DEEMED TO BE ORDINARY HAZARD IF ANY
 COMBUSTIBLES ARE PRESENT. IN ORDER TO CLASSIFY AS LOW
 HAZARD, BOTH THE COMMODITY AND THE STORAGE METHOD
 (METAL RACKS, PILED, ETC.) WOULD HAVE TO BE
 NONCOMBUSTIBLE. ANY PALLETIZED, BOXED, ENCAPSULATED
 STORAGE WOULD BE CLASSIFIED AS ORDINARY HAZARD. SITE
 PLAN SHEET INDICATES LOW HAZARD STORAGE. PLEASE
 INDICATE WHAT COMMODITIES WILL BE STORED AND HOW THEY
 WILL BE STORED TO JUSTIFY THE LOW HAZARD
 CLASSIFICATION; OTHERWISE A SECOND SWINGING EXIT DOOR
 WILL BE REQUIRED IF THE COMMON PATH OF TRAVEL EXCEEDS
 50 FEET.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NEW 3068 DOOR SWINGS OVER THE STAIR TREAD.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND
 NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD,
 MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE
 LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE
 RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. PROVIDE DETAIL.
  
 STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN
 HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A
 MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE
 ACCUMULATION OF WATER. PROVIDE DETAIL.
  
 PROVIDE RAMP DETAIL INDICATING ANY HANDRAILS,
 GUARDRAILS OR CURBS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-02 Cont ID  
Sent By hmoser Date 2013-07-02 Time 14:52 Rev Time 0.00
Received By hmoser Date 2013-05-24 Time 11:55 Sent To  
Notes
2013-05-28 11:57:34C--12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-06-10 Cont ID  
Sent By jwitmer Date 2013-06-10 Time 10:38 Rev Time 0.00
Received By jwitmer Date 2013-06-10 Time 10:38 Sent To  
Notes
2013-06-10 10:38:22BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By hmoser Date 2013-07-02 Time 14:52 Rev Time 0.00
Received By hmoser Date 2013-07-02 Time 13:43 Sent To  
Notes
2013-07-02 14:52:30PLANS DENIED
 1) REFER TO SECTION 606.2.2 COMMON RETURN AIR AND
 SUPPLY
 SYSTEMS. 2010 FBC (M)
 2) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-04 Cont ID  
Sent By lwagner Date 2013-06-04 Time 09:12 Rev Time 0.00
Received By lwagner Date 2013-06-03 Time 10:32 Sent To  
Notes
2013-06-04 09:00:20***PROVISO***
 1. RESTROOM SHALL BE A MINIMUM OF 7'-1" WIDTH
 FBC ACCESSIBILITY 2010 604.3.2
  
 2. LOUNGE SINK TOP 34" A.F.F. MAXIMUM WITH ACCESSABLE
 FRONT APROACH.
 FBC ACCESSIBILITY 2010 606.3

Review Stop Z ZONING
Rev No 1 Status F Date 2013-06-14 Cont ID  
Sent By jroach Date 2013-06-14 Time 11:12 Rev Time 0.00
Received By ajones Date 2013-06-03 Time 14:47 Sent To  
Notes
2013-06-14 11:13:306/14/13 FAILED. APPLICANT NEEDS TO PROVIDE A SITE PLAN
 SHOWING EXISTING PARKING SPACES AND ANY ADDITIONAL
 PARKING SPACES THAT ARE BEING CREATED FOR THE
 ADDITIONAL SQUARE FOOTAGE.
  
 THE VALUE OF THE JOB EXCEEDS 50% OF THE VALUE OF THE
 STRUCTURE ON THE PROPERTY; THEREFORE LANDSCAPING NEEDS
 TO BE BROUGHT UP TO CODE OR AS CLOSE AS POSSIBLE
 WITHOUT LOSING PARKING SPACES OR DRIVE ASILE AREAS.
  
 ANGELLA VANN
 561-822-1441
 PLANNING AND ZONING ADMINISTRATOR