Plan Review Details - Permit 13050856
Plan Review Stops For Permit 13050856
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2013-06-21 Time 06:50 Sent To  
Notes
2013-06-24 09:54:342010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R4101.17 RESIDENTIAL
 BARRIER REQUIREMENT FOR THE METHOD THAT WILL BE USED AS
 A BARRIER BETWEEN THE RESIDENCE AND THE POOL.
  
 2) THE PERMT VALUE FOR THE POOL, GAS HEATER AND PAVERS
 WAS TOO LOW AND HAS BEEN ADJUSTED BASED ON THE MARSHALL
 AND SWIFT VALUATION GUIDE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 12:59 Rev Time 0.00
Received By rmcdouga Date 2013-06-12 Time 12:59 Sent To  
Notes
2013-06-12 13:17:042010 FBC
  
 DENIED BY BUILDING
  
 1) SHOW COMPLIANCE WITH FBC R4101.17 RESIDENTIAL
 BARRIER REQUIREMENT FOR THE METHOD THAT WILL BE USED AS
 A BARRIER BETWEEN THE RESIDENCE AND THE POOL.
  
 2) THE PLANS REFERENCE THE 2001 FBC SECTION 424.2.6.1.
 THIS PROJECT IS REQUIRED TO BE DESIGNED TO COMPLY WITH
 THE 2010 FBC RESIDENTIAL CHAPTER 41 AND SECTION
 R4101.6.1 FOR DESIGN, CONSTRUCTION AND WORKMANSHIP.
 PLEASE UPDATE THE INFORMATION ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-03 Cont ID  
Sent By dharvey Date 2013-06-03 Time 15:32 Rev Time 0.00
Received By dharvey Date 2013-06-03 Time 15:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 12:53 Rev Time 0.00
Received By rmcdouga Date 2013-06-12 Time 12:53 Sent To  
Notes
2013-06-12 12:54:15A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED
 FOR A GAS PERMIT.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-05-30 Cont ID  
Sent By jroach Date 2013-05-30 Time 08:50 Rev Time 0.00
Received By jroach Date 2013-05-30 Time 08:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 10:21 Rev Time 0.00
Received By rmcdouga Date 2013-06-15 Time 09:07 Sent To  
Notes
2013-06-15 09:07:37INCOMING SENT TO ROBERT MCGOUGALS' DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 13:54 Rev Time 0.00
Received By rmcdouga Date 2013-05-24 Time 10:31 Sent To  
Notes
2013-05-30 10:32:35IN ELECTRIC BOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 15:30 Sent To  
Notes
2013-06-28 15:31:42REDLINED PLANS. CHANGED BRANCH PIPING TO 3" AND OTHER
 SUCTION PIPING TO 2-1/2" TO COMPLY WITH ANSI/APSP-7
 2006 SECTION 4.4

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 09:54 Rev Time 0.00
Received By rmcdouga Date 2013-06-21 Time 06:50 Sent To  
Notes
2013-06-24 10:21:462010 FBC
  
 DENIED BY PLUMBING
  
 1) THE PENTAIR WHISPERFLO 1HP, 2-SPEED POOL PUMP
 (WFE-24) HAS A FLOW RATE OF APPROXIMATELY 110 GPM WITH
 A TDH OF 30 FT. ON HIGH SPEED. THE WATER VELOCITY IN
 THE 2" PIPE THAT IS SPECIFIED IS 11.25 FT/SEC AT THAT
 RATE. THIS EXCEEDS THE MAXIMUM WATER VELOCITY ALLOWED
 IN FIELD FABRICATED BRANCH SUCTION PIPING WHICH IS 6
 FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED AND THE 8
 FEET/SEC FOR SUCTION PIPING. PLEASE CORRECT. FBC
 R4101.6.3 AND ANSI / APSP-7 2006 SECTION 4.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 13:17 Rev Time 0.00
Received By rmcdouga Date 2013-06-12 Time 13:17 Sent To  
Notes
2013-06-12 13:54:152010 FBC
  
 DENIED BY PLUMBING
  
 1) THE ATMOSPHERIC VENT ARRANGEMENT IS NO LONGER AN
 ACCEPTABLE METHOD OF ENTRAPMENT PROTECTION FOR NEW
 POOLS. SEE ANSI/APSP-7 2006 SECTION 7.
  
 2) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS
 WITH THE PUMP CURVE FOR THE 3/4 HP POOL PUMP IN ORDER
 TO VERIFY THE WATER VELOCITY IN THE POOL PIPING. THE
 WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION
 PIPING IS 6 FEET PER SECOND WHEN ONE OF A PAIR IS
 BLOCKED. ANSI / APSP-7 2006 SECTION 4.4
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-30 Cont ID  
Sent By jroach Date 2013-05-30 Time 08:50 Rev Time 0.00
Received By jroach Date 2013-05-30 Time 08:50 Sent To  
Notes
2013-05-30 08:52:06ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.30.2013
 PERMIT NO.: 13050856
 ADDRESS: 3225 VINCENT ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: POOL AND DECK.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. POOL EQUIPMENT SHALL BE LOCATED ON THE NORTH SIDE OF
 THE EXISTING RESIDENCE, BETWEEN THE HOUSE AND THE
 EXISTING EASEMENT.
  
 2. SEPARATE PERMITS SHALL BE REQUIRED FOR THE FENCING.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved