| Plan Review Stops For Permit 13050856 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2013-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-28 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-28 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-24 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-21 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2013-06-24 09:54:34 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SHOW COMPLIANCE WITH FBC R4101.17 RESIDENTIAL | | | BARRIER REQUIREMENT FOR THE METHOD THAT WILL BE USED AS | | | A BARRIER BETWEEN THE RESIDENCE AND THE POOL. | | | | | | 2) THE PERMT VALUE FOR THE POOL, GAS HEATER AND PAVERS | | | WAS TOO LOW AND HAS BEEN ADJUSTED BASED ON THE MARSHALL | | | AND SWIFT VALUATION GUIDE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-06-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-12 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-12 |
Time |
12:59 |
Sent To |
|
|
| Notes |
| 2013-06-12 13:17:04 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SHOW COMPLIANCE WITH FBC R4101.17 RESIDENTIAL | | | BARRIER REQUIREMENT FOR THE METHOD THAT WILL BE USED AS | | | A BARRIER BETWEEN THE RESIDENCE AND THE POOL. | | | | | | 2) THE PLANS REFERENCE THE 2001 FBC SECTION 424.2.6.1. | | | THIS PROJECT IS REQUIRED TO BE DESIGNED TO COMPLY WITH | | | THE 2010 FBC RESIDENTIAL CHAPTER 41 AND SECTION | | | R4101.6.1 FOR DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | PLEASE UPDATE THE INFORMATION ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-06-03 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-06-03 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-06-03 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2013-06-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-12 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-12 |
Time |
12:53 |
Sent To |
|
|
| Notes |
| 2013-06-12 12:54:15 | A SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED | | | FOR A GAS PERMIT. |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-05-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2013-05-30 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2013-05-30 |
Time |
08:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-24 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-15 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2013-06-15 09:07:37 | INCOMING SENT TO ROBERT MCGOUGALS' DESK . JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-06-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-12 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-05-24 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2013-05-30 10:32:35 | IN ELECTRIC BOX |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2013-06-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-28 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-28 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2013-06-28 15:31:42 | REDLINED PLANS. CHANGED BRANCH PIPING TO 3" AND OTHER | | | SUCTION PIPING TO 2-1/2" TO COMPLY WITH ANSI/APSP-7 | | | 2006 SECTION 4.4 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2013-06-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-24 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-21 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2013-06-24 10:21:46 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PENTAIR WHISPERFLO 1HP, 2-SPEED POOL PUMP | | | (WFE-24) HAS A FLOW RATE OF APPROXIMATELY 110 GPM WITH | | | A TDH OF 30 FT. ON HIGH SPEED. THE WATER VELOCITY IN | | | THE 2" PIPE THAT IS SPECIFIED IS 11.25 FT/SEC AT THAT | | | RATE. THIS EXCEEDS THE MAXIMUM WATER VELOCITY ALLOWED | | | IN FIELD FABRICATED BRANCH SUCTION PIPING WHICH IS 6 | | | FEET PER SECOND WHEN ONE OF A PAIR IS BLOCKED AND THE 8 | | | FEET/SEC FOR SUCTION PIPING. PLEASE CORRECT. FBC | | | R4101.6.3 AND ANSI / APSP-7 2006 SECTION 4.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-06-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-06-12 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-06-12 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2013-06-12 13:54:15 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) THE ATMOSPHERIC VENT ARRANGEMENT IS NO LONGER AN | | | ACCEPTABLE METHOD OF ENTRAPMENT PROTECTION FOR NEW | | | POOLS. SEE ANSI/APSP-7 2006 SECTION 7. | | | | | | 2) PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS | | | WITH THE PUMP CURVE FOR THE 3/4 HP POOL PUMP IN ORDER | | | TO VERIFY THE WATER VELOCITY IN THE POOL PIPING. THE | | | WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION | | | PIPING IS 6 FEET PER SECOND WHEN ONE OF A PAIR IS | | | BLOCKED. ANSI / APSP-7 2006 SECTION 4.4 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-05-30 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2013-05-30 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2013-05-30 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2013-05-30 08:52:06 | ZONING PLAN REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 05.30.2013 | | | PERMIT NO.: 13050856 | | | ADDRESS: 3225 VINCENT ROAD | | | CONTRACTOR/CONTACT: | | | TELEPHONE NO.: | | | SCOPE OF REVIEW: POOL AND DECK. | | | ___________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ___________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. POOL EQUIPMENT SHALL BE LOCATED ON THE NORTH SIDE OF | | | THE EXISTING RESIDENCE, BETWEEN THE HOUSE AND THE | | | EXISTING EASEMENT. | | | | | | 2. SEPARATE PERMITS SHALL BE REQUIRED FOR THE FENCING. | | | ___________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN ROACH, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | PHONE: 561.822.1448 | | | FAX: 561.822.1460 | | | | | | EMAIL: [email protected] | | | | | | WWW.WPB.ORG | | | |
|
|