Plan Review Details - Permit 13050846
Plan Review Stops For Permit 13050846
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-29 Cont ID  
Sent By jwitmer Date 2013-05-29 Time 08:06 Rev Time 0.00
Received By jwitmer Date 2013-05-29 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-11 Cont ID  
Sent By dharvey Date 2013-06-11 Time 13:37 Rev Time 0.00
Received By dharvey Date 2013-06-11 Time 13:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-30 Cont ID  
Sent By dharvey Date 2013-05-30 Time 08:55 Rev Time 0.00
Received By dharvey Date 2013-05-30 Time 08:55 Sent To  
Notes
2013-05-30 08:59:225-30-13 - FIRST REVIEW
  
 PLEASE CHECK DRAWING SCALE. SEEMS INCORRECT. COULD NOT
 CHECK RECEPT DISTANCES
 ADD NOTES FOR THE FOLLOWING :
 TAMPER RESISTANT RECEPTS REQUIRED AS PER NEC 406.11
 SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE 314
 CHANGE NOTE UNDER PANEL SCHEDULE FROM AFCI REQUIRED IN
 "BEDROOMS" TO "ALL AREAS".
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By wjolin Date 2013-06-07 Time 14:48 Rev Time 0.00
Received By wjolin Date 2013-06-07 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 10:10 Rev Time 0.00
Received By hmoser Date 2013-06-10 Time 16:12 Sent To  
Notes
2013-06-10 16:13:40*EXPEDITED*
 GAVE TO VINNY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-08 Cont ID  
Sent By lmartine Date 2013-06-07 Time 09:49 Rev Time 0.00
Received By lmartine Date 2013-05-24 Time 13:58 Sent To  
Notes
2013-05-24 13:58:38EXPEDITED
 B--7

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By hmoser Date 2013-06-14 Time 10:10 Rev Time 0.00
Received By hmoser Date 2013-06-14 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-05 Cont ID  
Sent By hmoser Date 2013-06-05 Time 09:28 Rev Time 0.00
Received By hmoser Date 2013-06-05 Time 08:47 Sent To  
Notes
2013-06-05 09:28:31PLAN DENIED
 1) PROVIDE GRILL SIZE AND CFM ON NEW 5IN DUCT
 ON THE PLANS.PER SECTION 107 FBC 2010
 2) PLEASE EXPLAIN WHAT IS GOING ON WITH THE A/C DUCT
 IN THE NEW SOFFIT IN BEDROOM # 2.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By lwagner Date 2013-05-28 Time 16:31 Rev Time 0.00
Received By lwagner Date 2013-05-28 Time 16:10 Sent To  
Notes
***NONE***