Plan Review Details - Permit 13050772
Plan Review Stops For Permit 13050772
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 10:08 Rev Time 0.00
Received By hmoser Date 2013-05-22 Time 14:34 Sent To  
Notes
2013-05-23 14:35:21IN MECH BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 13:59 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 13:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 10:08 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 09:53 Sent To  
Notes
2013-05-28 10:08:01PLAN DENIED
 PROVIDE GRILL SIZE ON THE PLANS ALSO PROVIDE
 THE SIGNATURE AND LICENSE NUMBER OF WHO DID
 THE PLANS ON THE PLANS. PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER OR MANUFACTURER
 ON CONDENSER TIE DOWN TO THE SLAB. PER SECTION 301.12
 WIND RESISTANCE 2010 FBC (M) .
 PLAN REVIEW BY HAROLD MOSER
 OFFICE 561-805-6732
 FAX 561-805-6676
  