| 2013-05-23 14:35:21 | IN MECH BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-05-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-05-28 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-05-28 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-05-28 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-05-28 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-05-28 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2013-05-28 10:08:01 | PLAN DENIED | | | PROVIDE GRILL SIZE ON THE PLANS ALSO PROVIDE | | | THE SIGNATURE AND LICENSE NUMBER OF WHO DID | | | THE PLANS ON THE PLANS. PER SECTION 107 FBC 2010 | | | 2) PROVIDE A DETAIL FROM THE ENGINEER OR MANUFACTURER | | | ON CONDENSER TIE DOWN TO THE SLAB. PER SECTION 301.12 | | | WIND RESISTANCE 2010 FBC (M) . | | | PLAN REVIEW BY HAROLD MOSER | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|
|
|