Plan Review Details - Permit 13050755
Plan Review Stops For Permit 13050755
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-03 Cont ID  
Sent By shill Date 2013-07-03 Time 10:06 Rev Time 0.00
Received By shill Date 2013-07-03 Time 10:06 Sent To  
Notes
2013-07-03 10:07:26OBTAINED UPDATED VALUE FROM CONTRACTOR OVER THE
 TELPEHONE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-06-29 Cont ID  
Sent By SHILL Date 2013-06-29 Time 08:03 Rev Time 0.00
Received By shill Date 2013-06-29 Time 08:03 Sent To  
Notes
2013-06-29 08:04:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. OK.
  
 2. FBC 109, VALUE IS TO INCLUDE ALL LABOR AND
 MATERIALS. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
 THIS MAY BE SUBMITTED VIA EMAIL.
  
 NEW COMMENT: BE ADVISED THAT A PLUMBING PERMIT IS
 REQUIRED FOR THIS JOB.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-30 Cont ID  
Sent By shill Date 2013-05-30 Time 14:03 Rev Time 0.00
Received By shill Date 2013-05-30 Time 14:03 Sent To FIRE
Notes
2013-05-30 14:06:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. REGARDING THE OAK T&G CEILINGS SHOWN ON SHEET A100,
 PLEASE SEE FBC 603.1(7), 803.1.1, TABLE 803.9, CEILING
 FINISH TO BE CLASS C. ALSO SEE FBC 803.10 AND 803.11
 (STABILITY AND FIRE RESISTANT CONSTRUCTION) FOR OTHER
 REQUIREMENTS. REVISE PLAN TO SHOW COMPLIANCE AND
 PROVIDE TEST DATA FOR CEILINGS.
  
 2. FBC 109, VALUE IS TO INCLUDE ALL LABOR AND
 MATERIALS. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 10:35 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 10:29 Sent To  
Notes
2013-07-02 10:36:04BY RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-03 Cont ID  
Sent By dharvey Date 2013-06-03 Time 16:46 Rev Time 0.00
Received By dharvey Date 2013-06-03 Time 16:46 Sent To  
Notes
2013-06-03 16:49:586-3-13
  
 FIRST REVIEW
 1. CHECK NOTE 16.14. CALLS FOR ALL ROMEX WIRING. IS
 THAT CORRECT?
 2. PLEASE COMPLY THE THE FOLLOWING NEC SECTIONS:
 210.12B AFCI PROTECTION; 210.8A GFCI RECEPTS WITHIN 6
 FEET OF SINKS; 210.52 REQUIRED RECEPTS AT KITCHEN
 ISLANDS; 406.11 TAMPER RESISTANT RECEPTS; 408.4 PROVIDE
 PANEL DIRECTORY
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-15 Cont ID  
Sent By wjolin Date 2013-06-15 Time 12:30 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By rferguso Date 2013-05-31 Time 11:43 Rev Time 0.00
Received By rferguso Date 2013-05-31 Time 11:43 Sent To E
Notes
2013-05-31 11:45:08SEE BUILDING COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-02 Cont ID  
Sent By shill Date 2013-07-02 Time 16:00 Rev Time 0.00
Received By shill Date 2013-06-11 Time 09:40 Sent To  
Notes
2013-06-12 09:40:34SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-12 Cont ID  
Sent By jgomez Date 2013-06-03 Time 09:26 Rev Time 0.00
Received By jgomez Date 2013-05-22 Time 14:32 Sent To  
Notes
2013-06-12 09:27:24LAST REVIEW DONE ON 6/3/13. JG.
2013-05-23 14:33:22MISC. #1

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-06-29 Cont ID  
Sent By shill Date 2013-06-29 Time 08:04 Rev Time 0.00
Received By shill Date 2013-06-29 Time 08:04 Sent To  
Notes
2013-06-29 08:05:22PLUMBING FIXTURE REPLACEMENT IN SAME LOCATIONS