| 2013-06-12 12:33:34 | BUILDING PLAN REVIEW |
| | PERMIT: 13050713 |
| | ADD: 313 DATURA ST |
| | CONT: ANDEERSON-MOORE CONSTRUCTION |
| | TEL: (561)753-7400 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JUNE 12/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) ) SHEET LS-01 EXISTING STAIR # 1 THE PLANS SHOW A |
| | DOORWAY UNDER THE STAIR, PLEASE PROVIDE A CROSS SECTION |
| | AND CODE COMPLIANCE FOR 2010 FBC-B 1009.6.3 ENCLOSURES |
| | UNDER STAIRS. |
| | |
| | 2) SHEET LS-01 THE ELEVATOR LOBBY RESTROOMS DOORS |
| | 107-108, PLEASE REVIEW 2010 FL ACCESSIBILITY CODE |
| | SECTION DOORS IN SERIES 404.2.6, SEE 603.2.3 EX # 2 |
| | THIS MAY HELP. |
| | |
| | 3) SHEET A-1.01 DOOR # 11 VERSES A-6.01 INDICATES A ? |
| | HR DOOR. PLEASE REVIEW 2010 FBC-B |
| | 1026.6, 1022.3 SECTION 715 TABLE 715.4 1 HR EXIT |
| | ENCLOSURES, 1 HR OPENING PROTECTIVE?S, ALSO REVIEW 2007 |
| | FBC-B COMMENTARY FIGURE 1023.6(1) CROSS HATCHED AREA |
| | REQUIRES 1 HOUR OPENING PROTECTIVE?S WITHIN 10 FOOT OF |
| | DOORWAY AND LANDINGS. |
| | |
| | 4) COMPLIED. 6/20/2013 SHEET A-1.01 EXIT FROM 3RD FLOOR |
| | TO 2ND FLOOR STAIR # 1, YOU HAVE TO LEAVE THE STAIR |
| | ENCLOSURE AND THEN GO BECK INTO THE STAIR ENCLOSE FROM |
| | THE 2ND FLOOR TO 1ST FLOOR. 2010 FEBC- 705.2, EXCEPTION |
| | # 2 MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF |
| | THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA |
| | FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS |
| | CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF |
| | EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO |
| | NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.BUIULDING & |
| | FIRE OFFICIALS AGREE CONSIDERED TO BE CODE COMPLIANT AT |
| | TIME BUILDING WAS BUILT. |
| | |
| | 5) LS-02 VERSES A-1.01 2ND FLOOR THE PATH THAT LEADS TO |
| | THE NEW EXTERIOR STAIR. THE WINDOWS APPEAR TO SHOW A |
| | FIRE RATING AND ALSO A WATER CURTAIN. SHEET A-6.01 |
| | INDICATES 45 MINUTE RATED, PLEASE SEE 2007 FBC-B CODE |
| | COMMENTARY FIGURE 1023.6(1). |
| | |
| | 6) COMPLIED 6/20/2013. THIS IS A BUILDING TYPE V-B. |
| | ZERO LOT LINE EXTERIOR WALLS TO BE 1 HOUR FIRE SISTANCE |
| | RATED. THE GLASS BLOCK WILL BE CONSIDERED INFILL WALL |
| | AND WILL ALSO BE REQUIRED TO BE 1 HOUR RATED SINCE 2010 |
| | FBC-B TABLE 705.8 DOES NOT ALLOW OPENINGS IN WALLS 0-3 |
| | FEET FROM THE PROPERTY LINE. |
| | |
| | 7) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, |
| | PLEASE PROVIDE THE ATTACHMENT OF THE STANDS TO THE ROOF |
| | STRUCTURE AS WELL AS THE EQUIPMENT TO THE STAND. |
| | PLEASE REVIEW 2010 FBC-B SECTION 1609.8 ROOFTOP |
| | STRUCTURES AND EQUIPMENT. |
| | |
| | 8) SHEET A-1.01 INDICATES NEW ROOF TOP A/C STANDS, THE |
| | ROOF TOP STANDS ARE WITHIN 3?-0? OF THE PARAPET, |
| | SECTION 5/ A-1.03 DOES NOT INDICATE HOW TALL THE |
| | PARAPET IS? SEE 2010 FBC-B |
| | 1013.5 MECHANICAL EQUIPMENT. |
| | |
| | 9) SHEET A-1.02 THIRD FLOOR, WINDOW # 17 AND DOOR 304 |
| | WILL NEED TO BE 1 HOUR FIRE RATED, AGAIN 1026.6, 1022.3 |
| | SECTION 715 TABLE 715.4 1 HR EXIT ENCLOSURES, 1 HR |
| | OPENING PROTECTIVE?S, ALSO REVIEW 2007 FBC-B COMMENTARY |
| | FIGURE 1023.6(1) CROSS HATCHED AREA REQUIRES 1 HOUR |
| | OPENING PROTECTIVE?S WITHIN 10 FOOT OF DOORWAY AND |
| | LANDINGS. |
| | |
| | 10) SHEET A-5.10 KITCHEN ROOM 303 MICROWAVE HEIGHT MUST |
| | MEET THE REACH RANGES, PROVIDE COMPLIANCE WITH 2010 FL |
| | ACCESSIBILITY CODE 308 REACH RANGES AND 309 OPERABLE |
| | PARTS. |
| | |
| | 11) A-1.01 AND S-1.01 BOTH INDICATE WHAT APPEARS TO BE |
| | SLOPED FLOORS, PLEASE PROVIDE THE HEIGHT DIFFERENCE IN |
| | FLOORS AND THE DISTANCE THE SLOPED FLOOR WILL BE, TO |
| | DETERMINE IF CONSIDERED GRADE OR RAMP WITH REQUIRED |
| | HANDRAILS. ACCESSIBILITY CODE ADVISORY 505.1 GENERAL. |
| | HANDRAILS ARE REQUIRED ON RAMP RUNS WITH A RISE GREATER |
| | THAN 6 INCHES (150 MM) (SEE 405.8) AND ON CERTAIN |
| | STAIRWAYS (SEE 504). HANDRAILS ARE NOT REQUIRED ON |
| | WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20. |
| | HOWEVER, HANDRAILS ARE REQUIRED TO COMPLY WITH 505 WHEN |
| | THEY ARE PROVIDED ON WALKING SURFACES WITH RUNNING |
| | SLOPES LESS THAN 1:20 (SEE 403.6). SECTIONS 505.2, |
| | 505.3, AND 505.10 DO NOT APPLY TO HANDRAILS PROVIDED ON |
| | WALKING SURFACES WITH RUNNING SLOPES LESS THAN 1:20 AS |
| | THESE SECTIONS ONLY REFERENCE REQUIREMENTS FOR RAMPS. |
| | |
| | 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 13) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |