Plan Review Details - Permit 13050679
Plan Review Stops For Permit 13050679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-07-22 Cont ID  
Sent By rmcdouga Date 2013-07-22 Time 16:36 Rev Time 0.00
Received By rmcdouga Date 2013-07-22 Time 16:27 Sent To E
Notes
2013-07-22 16:39:031) THE ELEVATION CERTIFICATE THAT WAS SUBMITTED FOR THE
 MAIN HOUSE INDICATES THAT THE EXISTING DWELLING AND
 EQUIPMENT COMPLY WITH ELEVATION REQUIREMENTS AND ARE
 ABOVE 7.5' BFE.
  
 2) THE WINDOWS AND DOORS WERE REPLACED UNDER PERMIT
 NUMBER 13040417.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-02 Cont ID  
Sent By rmcdouga Date 2013-07-02 Time 14:06 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 14:57 Sent To  
Notes
2013-07-02 09:51:022010 FBC
  
 DENIED BY BUILDING
  
 1) THIS PRE-FIRM STRUCTURE IS LOCATED IN AN A5 FLOOD
 ZONE. THE VALUE OF THE WORK IS $1,000,000.00 WHICH IS
 MORE THAN 50% OF THE IMPROVEMENT VALUE OF THE STRUCTURE
 LISTED ON THE PBC PROPERTY APPRAISER'S WEB SITE. THIS
 IS CONSIDERED A SUBSTANTIAL IMPROVEMENT AND THE
 EXISTING STRUCTURE IS REQUIRED TO HAVE IT'S LOWEST
 FLOOR ELEVATED TO OR ABOVE THE BFE. THE BFE FOR THIS
 LOCATION IS 7 FEET PLUS THE 6 INCH FREE BOARD PER FEMA
 FLOOD INSURANCE RATE MAPS AND CITY OF WPB FLOOD
 ORDINANCE. PLEASE SUBMIT AN ELEVATION CERTIFICATE
 SHOWING THAT THE EXISTING LOWEST FLOOR ELEVATIONS ARE
 AT OR ABOVE 7' 6" BFE OR SUBMIT A FLOOR PLAN SHOWING
 PROPOSED FIRST FLOOR ELEVATIONS WITH DETAILS OF HOW THE
 FLOORS WILL BE ELEVATED. CITY AMENDMENTS 107.2.1 AND
 FBC R322.
  
 2) THE OCCUPANCY TYPE SPECIFIED ON SHEET CVR IS
 INCORRECT. THIS IS A SINGLE FAMILY RESIDENCE THE
 CORRECT OCCUPANCY TYPE IS R3. FBC SECTION 310
  
 3) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS
 AND R315.1 FOR CARBON MONOXIDE ALARMS.
  
 4) THE ENERGY CALCULATION FORM IS REQUIRED TO BE SIGNED
 BY THE OWNER OR HIS AGENT FBC ENERGY 405.4.2
  
 5) THERE APPEARS TO BE DISCREPANCIES BETWEEN THE
 ARCHITECTURAL DRAWINGS AND THE STRUCTURAL DRAWINGS WITH
 RELATION THE REPLACEMENT OF THE EXISTING WINDOWS AND
 DOORS. THE ELEVATIONS AND DOOR SCHEDULE ON A-4.0 SHOW
 THE EXISTING EXTERIOR DOORS AND WINDOWS TO REMAIN AND
 THE EXTERIOR DOOR AND WINDOW SCHEDULE ON SHEET S-3
 SPECIFIES THAT THEY ARE BEING REPLACED. PLEASE CLARIFY.
 CITY AMENDMENTS 107.2.1
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR STOREFRONT DOORS AND WINDOWS AND ALL OTHER
 EXTERIOR WINDOWS AND DOORS THAT WILL BE REPLACED OR
 ADDED AS REQUIRED BY DCA RULE 9N-3.
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4
  
 8) IN ORDER TO SPEED THE REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS HAVE
 BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-07-23 Cont ID  
Sent By dharvey Date 2013-07-23 Time 18:42 Rev Time 0.00
Received By dharvey Date 2013-07-23 Time 17:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 15:25 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 15:25 Sent To  
Notes
2013-06-04 15:32:186-4-13
 FIRST REVIEW:
 1. PLEASE NOTE NEC 210.4.B FOR MULTI BRANCH CIRCUITS TO
 BE SIMULTANEOSLY DISCONNECTED AND 210.4D TO HAVE
 CONDUCTORS GROUPED TOGETHER. (IE; ZIP TIES)
 2. PER 680.22B POOL PUMPS TO HAVE GFCI CIRCUIT BREAKERS
 3. PLEASE REVIEW THE ENTIRE SCOPE FOR THE
 MECHANICAL/ELECTRICAL COORDINATION. IT DOES NOT MATCH.
 EXAMPLES; WHERE IS THE INFO FOR CU1 TO GO WITH AHU1?
 HOW COULD ONE 15A CIRCUIT BREAKER FEED AHU 4A, B AND C?
 THERES MORE. PLEASE REVIEW AND CORRECT.
 VB

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 14:49 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 14:49 Sent To  
Notes
2013-07-23 07:44:20A SEPARATE GAS APPLICATION AND SUB-PERMIT IS REQUIRED.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By fmittner Date 2013-07-02 Time 11:52 Rev Time 0.00
Received By fmittner Date 2013-07-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-05-20 Cont ID  
Sent By fmittner Date 2013-05-20 Time 16:50 Rev Time 0.00
Received By fmittner Date 2013-05-20 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-07-23 Cont ID  
Sent By dharvey Date 2013-07-23 Time 18:42 Rev Time 0.00
Received By dharvey Date 2013-07-10 Time 14:56 Sent To  
Notes
2013-07-10 14:56:44R20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-10 Cont ID  
Sent By rmcdouga Date 2013-07-10 Time 14:56 Rev Time 0.00
Received By rmcdouga Date 2013-07-02 Time 12:32 Sent To  
Notes
2013-07-05 12:33:34R20
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-07-02 Cont ID  
Sent By rmcdouga Date 2013-07-02 Time 14:06 Rev Time 0.00
Received By rmcdouga Date 2013-05-21 Time 09:57 Sent To  
Notes
2013-05-23 09:57:44R--20

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-07-01 Cont ID  
Sent By hmoser Date 2013-07-01 Time 10:34 Rev Time 0.00
Received By hmoser Date 2013-07-01 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 14:50 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 14:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-07-02 Cont ID  
Sent By fmittner Date 2013-07-02 Time 11:53 Rev Time 0.00
Received By fmittner Date 2013-07-02 Time 11:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-20 Cont ID  
Sent By fmittner Date 2013-05-20 Time 16:50 Rev Time 0.00
Received By fmittner Date 2013-05-20 Time 16:50 Sent To  
Notes
***NONE***