Plan Review Details - Permit 13050677
Plan Review Stops For Permit 13050677
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-22 Cont ID  
Sent By wjolin Date 2013-05-22 Time 10:00 Rev Time 0.00
Received By wjolin Date 2013-05-22 Time 09:56 Sent To  
Notes
2013-05-22 10:00:34105 EVERNIA STREET - "JERKFEST"
 PERMIT #13050677
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES
 SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET
 AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR
 ENCLOSURE.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-22 Cont ID  
Sent By wjolin Date 2013-05-22 Time 10:00 Rev Time 0.00
Received By wjolin Date 2013-05-20 Time 15:46 Sent To  
Notes
2013-05-20 15:47:10SENT TO TEMPORARY TENT BOX.