Plan Review Details - Permit 13050642
Plan Review Stops For Permit 13050642
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 08:44 Rev Time 0.00
Received By shill Date 2013-09-14 Time 08:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 21:22 Rev Time 0.00
Received By shill Date 2013-08-22 Time 21:22 Sent To M
Notes
2013-08-22 21:23:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 ONLY ONE SET WAS REVISED. TWO SETS REQUIRED FOR PERMIT
 ISSUANCE, FBC 107.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-12 Cont ID  
Sent By shill Date 2013-08-12 Time 12:14 Rev Time 0.00
Received By shill Date 2013-08-12 Time 12:14 Sent To  
Notes
2013-08-12 12:29:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS PARCEL IS LOCATED IN THE 165 MPH WIND ZONE.
 SEE HTTP://WWW.ATCOUNCIL.ORG/WINDSPEED;
 LATITUDE/LONGITITUDE INFORMATION SHOWS THIS PARCEL AS
 168MPH MINIMUM, FBC R 301.
  
 2ND REVIEW, NOT ADDRESSED.
  
 2. SEE COMMENT #1, ROOF PRESSURES APPEAR LOW. CHECK ALL
 DESIGN PRESSURES. CALCULATIONS MAY BE REQUIRED. BASED
 ON FBC TABLE R 301.2(2), ZONE 3 FOR FLAT DECK SHOULD BE
 -95.7, BUT -84.1 SPECIFIED ON PLAN.
  
 2ND REVIEW, PRESSURES CHANGED IN SOME LOCATIONS AND NOT
 IN OTHERS. SEE DESIGN PRESSURES BY WINDOWS; THEY DO NOT
 CORRELATE WITH NEW PRESSURES ON THE CHART. SEE ALSO
 ITEM 1.
  
 3. REVISE THE FLOOR PLAN TO SHOW CLEAR OPENING (HEIGHT,
 WIDTH, TOTAL SF) FOR BEDROOM EGRESS WINDOWS. IF NON
 COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 PROVIDE DIMENSIONS FOR THE BEDROOM WINDOWS RATHER THAN
 "34" OR "22".
  
 4. SEE PAGE 9 OF THE FLAT DECK NOA AND "ENHANCED
 NAILING CALCULATIONS" . FASTENING FOR ZONE 1 PROPOSED
 BY ENGINEER NOT CONSISTENT WITH THE NOA (12" RATHER
 THAN 8"). NUMBER OF FIELD ROWS NOT SPECIFIED. IF USING
 GENERAL LIMITATION #6 IS PROPOSED, PROVIDE
 CALCULATIONS.
  
 5. FASTENING PATTERN "ENHANCED NAILING CALCULATIONS" DO
 NOT INCLUDE NUMBE OF ROWS. PLEASE REVISE AND BE CLEAR
 AS TO WHETHER THE NUMBER OF ROWS REQUIRED INCLUDES THE
 LAP ROW.
  
 NEW CALCS NOT REVIEWED AS THE WIND SPEED WAS NOT
 REVISED (STILL 165 MPH).
  
 6. OK
  
 7. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-01 Cont ID  
Sent By shill Date 2013-06-01 Time 10:17 Rev Time 0.00
Received By shill Date 2013-06-01 Time 09:32 Sent To  
Notes
2013-06-01 10:24:44****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS PARCEL IS LOCATED IN THE 165 MPH WIND ZONE.
 SEE HTTP://WWW.ATCOUNCIL.ORG/WINDSPEED;
 LATITUDE/LONGITITUDE INFORMATION SHOWS THIS PARCEL AS
 168MPH MINIMUM, FBC R 301.
  
 2. SEE COMMENT #1, ROOF PRESSURES APPEAR LOW. CHECK ALL
 DESIGN PRESSURES. CALCULATIONS MAY BE REQUIRED. BASED
 ON FBC TABLE R 301.2(2), ZONE 3 FOR FLAT DECK SHOULD BE
 -95.7, BUT -84.1 SPECIFIED ON PLAN.
  
 3. REVISE THE FLOOR PLAN TO SHOW CLEAR OPENING (HEIGHT,
 WIDTH, TOTAL SF) FOR BEDROOM EGRESS WINDOWS. IF NON
 COMPLIANT EMERGENCY ESCAPE AND RESCUE OPENINGS ARE
 PROPOSED, ALSO NOTE EXISTING CONDITIONS (TYPE OF
 WINDOW) AND EXISTING CLEAR OPENING SIZE AND PROPOSED
 CLEAR OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB
 604.1. THE CLEAR OPENING CANNOT BE REDUCED BY MORE THAN
 5%.
  
 4. SEE PAGE 9 OF THE FLAT DECK NOA AND "ENHANCED
 NAILING CALCULATIONS" . FASTENING FOR ZONE 1 PROPOSED
 BY ENGINEER NOT CONSISTENT WITH THE NOA (12" RATHER
 THAN 8"). NUMBER OF FIELD ROWS NOT SPECIFIED. IF USING
 GENERAL LIMITATION #6 IS PROPOSED, PROVIDE
 CALCULATIONS.
  
 5. FASTENING PATTERN "ENHANCED NAILING CALCULATIONS" DO
 NOT INCLUDE NUMBE OF ROWS. PLEASE REVISE AND BE CLEAR
 AS TO WHETHER THE NUMBER OF ROWS REQUIRED INCLUDES THE
 LAP ROW.
  
 6. ENERGY CALCS (FORM 402-2010) DO NOT INCLUDE A/C
 SYSTEM INFO, PLEASE REVISE.
  
 7. THE TWO FLORIDA STATE PRODUCT APPROVALS SUBMITTED
 (DOOR AND ANCHORS) INCLUDED ONLY THE COVER SHEET. THE
 EVALUATION REPORT AND INSTALLATION INSTRUCTIONS ARE
 REQUIRED, FBC R 301.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 16:19 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 15:59 Sent To  
Notes
2013-08-07 16:19:50RETURNED TO R3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-23 Cont ID  
Sent By dharvey Date 2013-05-23 Time 09:28 Rev Time 0.00
Received By dharvey Date 2013-05-23 Time 09:28 Sent To  
Notes
2013-05-23 09:36:115-23-13
  
 1. ELECTRICAL PERMIT REQUIRED
 2. PROVIDE CUT SHEETS FOR AIR CONDIRTIONING EQUIPMENT
 TO BE INSTALLED
 3. CORRECT AC CIRCUITS IN PANEL SCHEDULE TO "2-POLE"
 4. ALL NEW CIRCUITS TO BE AFCI PROTECTED PER NEC210.12B
 5. TAMPER RESISTANT RECEPTACLES REQUIED IF ANY NEW
 INSTALLED PER NEC 406.11
 VB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 09:04 Rev Time 0.00
Received By shill Date 2013-09-09 Time 09:08 Sent To  
Notes
2013-09-09 09:08:44SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-27 Cont ID  
Sent By hmoser Date 2013-08-27 Time 08:45 Rev Time 0.00
Received By hmoser Date 2013-08-16 Time 17:04 Sent To  
Notes
2013-08-16 17:05:11INCOMING SENT TO SAMANTHAS' BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-13 Cont ID  
Sent By hmoser Date 2013-08-13 Time 13:04 Rev Time 0.00
Received By hmoser Date 2013-07-25 Time 16:07 Sent To  
Notes
2013-07-26 16:07:51SENT TO R3 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-21 Cont ID  
Sent By shill Date 2013-06-17 Time 12:42 Rev Time 0.00
Received By shill Date 2013-05-21 Time 07:55 Sent To  
Notes
2013-05-21 07:56:34R09

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-08-27 Cont ID  
Sent By hmoser Date 2013-08-27 Time 08:45 Rev Time 0.00
Received By hmoser Date 2013-08-27 Time 08:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-08-13 Cont ID  
Sent By hmoser Date 2013-08-13 Time 13:04 Rev Time 0.00
Received By hmoser Date 2013-08-13 Time 12:41 Sent To  
Notes
2013-08-13 13:04:21PLANS DENIED
 1) PROVISO SIGNATURE AND LICENSE NUMBER OF WHO EVER DID
 THE PLANS ON THE PLANS.
 2) PROVIDE THE DUCT SIZE, GRILL SIZE AND CFM ON THE
 PLANS.
 3) PROVIDE SEER ON THE PLANS
 ALL PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By hmoser Date 2013-06-04 Time 15:54 Rev Time 0.00
Received By hmoser Date 2013-06-04 Time 15:34 Sent To  
Notes
2013-06-04 15:54:48PLANS DENIED
 THIS JOB IS NOT A CHANGE OUT .
 PROVIDE DUCT PLANS AND ENERGY CALCULATIONS
 FOR PERMIT. PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-17 Cont ID  
Sent By jgomez Date 2013-06-17 Time 09:37 Rev Time 0.00
Received By jgomez Date 2013-06-17 Time 09:37 Sent To  
Notes
2013-06-17 09:38:47TALKED TO CONTRACTOR (CARL WILSON). HE SAID ONLY
 REPLACING EXISTING PLUMBING FIXTURES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-06-07 Cont ID  
Sent By jgomez Date 2013-06-07 Time 15:16 Rev Time 0.00
Received By jgomez Date 2013-06-07 Time 15:16 Sent To  
Notes
2013-06-07 15:32:37RESIDENTIAL (R3) RENOVATION PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- FLOOR PLAN SUBMITTED IS INCOMPLETE. PROVIDE COMPLETE
 FLOOR PLAN SHOWING BATHROOMS, KITCHEN AND LAUNDRY ROOM
 LAYOUTS. CLARIFY WHAT IS NEW AND WHAT'S EXISTING. WHAT
 IS GOING TO BE EXACT FIXTURE REPLACEMENT TO CLARIFY
 SCOPE OF WORK. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PLUMBING RISER DIAGRAM. SEC. 107.3.5.3(11)
 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-17 Cont ID  
Sent By ajones Date 2013-06-17 Time 12:55 Rev Time 0.00
Received By ajones Date 2013-06-03 Time 10:45 Sent To  
Notes
2013-06-17 12:57:096/22/13 PASSED HCD PROJECTS ARE EXEMPT FROM THE 50%
 RULE.
  
 ANGELLA VANN
 PLANNING AND ZONING ADMINISTRATOR