Plan Review Details - Permit 13050597
Plan Review Stops For Permit 13050597
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-24 Cont ID  
Sent By jwitmer Date 2013-05-24 Time 13:44 Rev Time 0.00
Received By jwitmer Date 2013-05-24 Time 13:44 Sent To  
Notes
2013-05-24 13:46:31PROVISO:
 PROVIDE DOCUMENTATION THAT ELECTRIC LOCK MEETS THE
 FOLLOWING CODE COMPLIANCE:
 2010 FBC-B 1008.1.4.4. ACCESS-CONTROLLED EGRESS DOORS.
 THE ENTRANCE DOORS IN A MEANS OF EGRESS IN BUILDINGS
 WITH AN OCCUPANCY IN GROUP A, B, D, E, I-2, M, R-1 OR
 R-2 AND ENTRANCE DOORS TO TENANT SPACES IN OCCUPANCIES
 IN GROUPS A, B, D, E, I-2, M, R-1 AND R-2 ARE PERMITTED
 TO BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS
 ACCESS CONTROL SYSTEM WHICH SHALL BE INSTALLED IN
 ACCORDANCE WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE
 ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS.
 THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM
 OR LOSS OF POWER TO THE SENSOR.
  
 2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL
 SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS.
  
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A MANUAL
 UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES (1016
 MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND WITHIN 5
 FEET (1524 MM) OF THE SECURED DOORS. READY ACCESS SHALL
 BE PROVIDED TO THE MANUAL UNLOCKING DEVICE AND THE
 DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN THAT READS
 ?PUSH TO EXIT.? WHEN OPERATED, THE MANUAL UNLOCKING
 DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO
 THE LOCK?INDEPENDENT OF THE ACCESS CONTROL SYSTEM
 ELECTRONICS?AND THE DOORS SHALL REMAIN UNLOCKED FOR A
 MINIMUM OF 30 SECONDS.
  
 4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF
 PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE
 DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM
 HAS BEEN RESET.
  
 5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR
 FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY
 UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL
 THE FIRE ALARM SYSTEM HAS BEEN RESET.
  
 6. ENTRANCE DOORS IN BUILDINGS WITH AN OCCUPANCY IN
 GROUP A, B, E OR M SHALL NOT BE SECURED FROM THE EGRESS
 SIDE DURING PERIODS THAT THE BUILDING IS OPEN TO THE
 GENERAL PUBLIC

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 17:25 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 16:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-23 Cont ID  
Sent By dharvey Date 2013-05-23 Time 12:58 Rev Time 0.00
Received By dharvey Date 2013-05-23 Time 12:58 Sent To  
Notes
2013-05-23 13:08:395-23-13
  
 1. SHOW ALL RECEPTACLES WITHIN 6 FT OF SINKS TO BE GFCI
 TYPE
 2. LIGHTING LOAD CALCULATIONS REQUIRED PER FLORIDA
 ENERGY CODE SECTION 505
 3. LIGHTING CONTROLS REQUIRED AS PER FLORIDA ENERGY
 CODE SECTION 505
 4. CONDUCTORS AND CABLES INSTALLED IN SLAB TO BE WET
 LOCATION RATED
 5. FLUORESCENT FIXTURES MUST COMPLY TO NEC 410.130G FOR
 INTERNAL DISCONNECTS
 VB
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-07-24 Cont ID  
Sent By wjolin Date 2013-07-24 Time 11:00 Rev Time 0.00
Received By wjolin Date 2013-07-24 Time 10:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-18 Cont ID  
Sent By wjolin Date 2013-05-18 Time 18:37 Rev Time 0.00
Received By wjolin Date 2013-05-18 Time 18:12 Sent To  
Notes
2013-05-18 18:37:55319 CLEMATIS STREET
 TRACKING #13050597
 PERMIT #12110638
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET LS-1: COMBINING SUITE #500 WITH #502 APPEARS TO
 RESULT IN AN OCCUPANT LOAD OF 50+ PERSONS. DOUBLE
 EGRESS DOORS IN RECEPTION #01 WILL BE REQUIRED TO SWING
 WITH THE FLOW OF TRAFFIC.
  
 SHEET E-3: PROVIDE FIRE ALARM NOTIFICATION APPLIANCE IN
 CONFERENCE ROOM.
  
 SHEET E-3: DOORS WITH MAGNETIC LOCKS:
 PER NFPA 101, SECTION 7.2.1.6.2, ACCESS-CONTROLLED
 EGRESS DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF
 THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-15 Cont ID  
Sent By dharvey Date 2013-08-15 Time 17:26 Rev Time 0.00
Received By dharvey Date 2013-07-03 Time 10:58 Sent To  
Notes
2013-08-15 17:26:15TO S HILL
2013-07-24 15:25:46B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 14:19 Rev Time 0.00
Received By hmoser Date 2013-05-17 Time 15:40 Sent To  
Notes
2013-05-17 15:40:39SENT TO B22 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-08-09 Cont ID  
Sent By hmoser Date 2013-08-09 Time 14:41 Rev Time 0.00
Received By hmoser Date 2013-08-09 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 14:19 Rev Time 0.00
Received By hmoser Date 2013-05-31 Time 14:02 Sent To  
Notes
2013-05-31 14:19:07PLANS DENIED MISSING FIRE DAMPERS.
 PER SECTION 607.5.1 FIRE WALLS
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805 6676