| 2013-05-24 13:46:31 | PROVISO: |
| | PROVIDE DOCUMENTATION THAT ELECTRIC LOCK MEETS THE |
| | FOLLOWING CODE COMPLIANCE: |
| | 2010 FBC-B 1008.1.4.4. ACCESS-CONTROLLED EGRESS DOORS. |
| | THE ENTRANCE DOORS IN A MEANS OF EGRESS IN BUILDINGS |
| | WITH AN OCCUPANCY IN GROUP A, B, D, E, I-2, M, R-1 OR |
| | R-2 AND ENTRANCE DOORS TO TENANT SPACES IN OCCUPANCIES |
| | IN GROUPS A, B, D, E, I-2, M, R-1 AND R-2 ARE PERMITTED |
| | TO BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS |
| | ACCESS CONTROL SYSTEM WHICH SHALL BE INSTALLED IN |
| | ACCORDANCE WITH ALL OF THE FOLLOWING CRITERIA: |
| | |
| | 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE |
| | ARRANGED TO DETECT AN OCCUPANT APPROACHING THE DOORS. |
| | THE DOORS SHALL BE ARRANGED TO UNLOCK BY A SIGNAL FROM |
| | OR LOSS OF POWER TO THE SENSOR. |
| | |
| | 2. LOSS OF POWER TO THAT PART OF THE ACCESS CONTROL |
| | SYSTEM WHICH LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK |
| | THE DOORS. |
| | |
| | 3. THE DOORS SHALL BE ARRANGED TO UNLOCK FROM A MANUAL |
| | UNLOCKING DEVICE LOCATED 40 INCHES TO 48 INCHES (1016 |
| | MM TO 1219 MM) VERTICALLY ABOVE THE FLOOR AND WITHIN 5 |
| | FEET (1524 MM) OF THE SECURED DOORS. READY ACCESS SHALL |
| | BE PROVIDED TO THE MANUAL UNLOCKING DEVICE AND THE |
| | DEVICE SHALL BE CLEARLY IDENTIFIED BY A SIGN THAT READS |
| | ?PUSH TO EXIT.? WHEN OPERATED, THE MANUAL UNLOCKING |
| | DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF POWER TO |
| | THE LOCK?INDEPENDENT OF THE ACCESS CONTROL SYSTEM |
| | ELECTRONICS?AND THE DOORS SHALL REMAIN UNLOCKED FOR A |
| | MINIMUM OF 30 SECONDS. |
| | |
| | 4. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM, IF |
| | PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOORS, AND THE |
| | DOORS SHALL REMAIN UNLOCKED UNTIL THE FIRE ALARM SYSTEM |
| | HAS BEEN RESET. |
| | |
| | 5. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER OR |
| | FIRE DETECTION SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY |
| | UNLOCK THE DOORS. THE DOORS SHALL REMAIN UNLOCKED UNTIL |
| | THE FIRE ALARM SYSTEM HAS BEEN RESET. |
| | |
| | 6. ENTRANCE DOORS IN BUILDINGS WITH AN OCCUPANCY IN |
| | GROUP A, B, E OR M SHALL NOT BE SECURED FROM THE EGRESS |
| | SIDE DURING PERIODS THAT THE BUILDING IS OPEN TO THE |
| | GENERAL PUBLIC |