Plan Review Details - Permit 13050588
Plan Review Stops For Permit 13050588
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-16 Cont ID  
Sent By jwitmer Date 2013-08-16 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2013-08-16 Time 07:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-28 Cont ID  
Sent By jwitmer Date 2013-05-28 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2013-05-28 Time 14:18 Sent To  
Notes
2013-05-28 15:57:30BUILDING PLAN REVIEW
 PERMIT: 13050588
 ADD: 1881 OKEECHOBEE RD BLDG # 3
 CONT: DUKE INDIANA
 TEL: (954)453-5660
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/28/2013
 ACTION: DENIED
  
 1) COVER SHEET (T) OCCUPANCY CLASSIFICATION INDICATES A
 1921 SQ. FT . AREA AS A BUSINESS OCCUPANCY. SHEET A1.1
 INDICATES THIS SAME AREA AS A SHOW ROOM, SHOW ROOMS OR
 SALES ROOMS ARE CONSIDERED MERCANTILE OCCUPANCIES
 (FBC-B 309.1) WITH AN OCCUPANT LOAD FIGURED ON 30 SQ FT
 PER PERSON. THIS AREA WOULD HAVE AN OCCUPANT LOAD OF 65
 FBC-B TABLE 1004.1.1. WITH THE OCCUPANT LOAD , THAN 49
 OCCUPANTS (FBC-B TABLE 1015.1) WILL REQUIRE 2 MEANS OF
 EGRESS PER FBC-B 1015.2.1 EX 2) 1/3RD OF THE LENGTH OF
 THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA
 SERVED. NOTE FBC-B 1014.2 EGRESS THROUGH INTERVENING
 SPACES, CAN NOT TAKE THE MERCANTILE OCCUPANCY THROUGH
 THE S1 OCCUPANCY.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-16 Cont ID  
Sent By dharvey Date 2013-08-16 Time 14:37 Rev Time 0.00
Received By dharvey Date 2013-08-16 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-06-19 Cont ID  
Sent By dharvey Date 2013-06-19 Time 16:05 Rev Time 0.00
Received By dharvey Date 2013-06-19 Time 07:42 Sent To  
Notes
2013-06-19 13:46:28REVIEW BY RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-08-17 Cont ID  
Sent By wjolin Date 2013-08-17 Time 16:15 Rev Time 0.00
Received By wjolin Date 2013-08-17 Time 16:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-06-12 Cont ID  
Sent By wjolin Date 2013-06-12 Time 14:06 Rev Time 0.00
Received By wjolin Date 2013-05-29 Time 14:13 Sent To  
Notes
2013-05-29 14:26:501881 OKEECHOBEE ROAD
 PERMIT #13050588
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "IN THE EVENT A FIRE
 PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
  
  
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-16 Cont ID  
Sent By dharvey Date 2013-08-16 Time 14:37 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 10:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-19 Cont ID  
Sent By rregueir Date 2013-06-19 Time 16:07 Rev Time 0.00
Received By rregueir Date 2013-05-20 Time 11:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-06-18 Cont ID  
Sent By rregueir Date 2013-06-18 Time 16:27 Rev Time 0.00
Received By rregueir Date 2013-06-18 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-29 Cont ID  
Sent By lwagner Date 2013-05-29 Time 10:14 Rev Time 0.00
Received By lwagner Date 2013-05-28 Time 15:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-08-20 Cont ID  
Sent By rregueir Date 2013-08-20 Time 12:01 Rev Time 0.00
Received By rregueir Date 2013-08-20 Time 12:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-20 Cont ID  
Sent By ajones Date 2013-05-20 Time 15:45 Rev Time 0.00
Received By ajones Date 2013-05-20 Time 15:45 Sent To  
Notes
2013-05-20 11:13:34DIGITAL