Plan Review Details - Permit 13050490
Plan Review Stops For Permit 13050490
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-16 Cont ID  
Sent By shill Date 2013-05-16 Time 16:37 Rev Time 0.00
Received By shill Date 2013-05-16 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2013-06-24 Cont ID  
Sent By dharvey Date 2013-06-24 Time 09:57 Rev Time 0.00
Received By dharvey Date 2013-06-24 Time 09:15 Sent To Z
Notes
2013-06-24 09:57:5613050490
 4001 NORTH SHORE
 LIGHT POLE INSTALLATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY (NRTL) FOR THE POLE TOP FIXTURE. NEC
 110.3
  
 WIND LOAD ENGINEERING FOR THE LIGHT POLES AND FIXTURES
 NEEDS TO REFERENCE THE ACTUAL FIXTURE TYPE OR MODEL
 WITH ITS EPA AND ALSO VERIFY THE EXITING FOOTER IS
 STRUCTURALLY ADEQUATE. FBC 1609.1
  
 ROBERT LECKY
 PLANS EXAMINER
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-05-28 Cont ID  
Sent By dharvey Date 2013-05-28 Time 11:26 Rev Time 0.00
Received By dharvey Date 2013-05-28 Time 11:26 Sent To  
Notes
2013-05-28 11:27:065-28-13
 RESUBMITTAL DID NOT INCLUDE SOUTH FLORIDA WIND LOAD
 DATA BY ENGINEER. PLEASE PROVIDE.
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-16 Cont ID  
Sent By dharvey Date 2013-05-16 Time 13:52 Rev Time 0.00
Received By dharvey Date 2013-05-16 Time 13:52 Sent To  
Notes
2013-05-16 13:53:095-16-13
  
 PROVIDE LIGHT FIXTURE SPECSIFICATIONS/CUT SHEETS
 SHOWING ALL ELECTRICAL DATA
  
 VB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2013-06-27 Cont ID  
Sent By ajones Date 2013-06-27 Time 09:08 Rev Time 0.00
Received By ajones Date 2013-06-14 Time 14:00 Sent To  
Notes
2013-06-14 14:01:05TO ELEC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-27 Cont ID  
Sent By ajones Date 2013-06-27 Time 09:08 Rev Time 0.00
Received By ajones Date 2013-05-24 Time 11:27 Sent To  
Notes
2013-05-25 11:27:58UNDER 5 K ELECTRICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-16 Cont ID  
Sent By shill Date 2013-05-16 Time 16:37 Rev Time 0.00
Received By shill Date 2013-05-15 Time 17:28 Sent To  
Notes
2013-05-15 17:28:33SENT TO ELECTRIC UNDER $5000 BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2013-06-27 Cont ID  
Sent By ajones Date 2013-06-27 Time 09:08 Rev Time 0.00
Received By ajones Date 2013-06-26 Time 11:07 Sent To  
Notes
***NONE***