Plan Review Details - Permit 13050475
Plan Review Stops For Permit 13050475
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 11:33 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 11:33 Sent To  
Notes
2013-05-15 11:34:325-15-13
  
 APPROVED AS NOTED.
  
 CONTRACTOR USING ALUMINUM FEEDERS. MUST INCRERASE
 CONDUCTORS TO SIZE 1/0 FOR 125 AMPS
  
 VB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 11:34 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 11:34 Sent To  
Notes
***NONE***