Plan Review Details - Permit 13050465
Plan Review Stops For Permit 13050465
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-06-12 Cont ID  
Sent By shill Date 2014-06-12 Time 17:12 Rev Time 0.00
Received By shill Date 2014-06-12 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-02-09 Cont ID  
Sent By shill Date 2014-02-09 Time 13:10 Rev Time 0.00
Received By shill Date 2014-02-09 Time 13:10 Sent To  
Notes
2014-02-09 13:11:03CERTIFIED APPRAISAL SUBMITTED ON 2/4/14
  
 PROPOSED IMPROVEMENT EXCEEDS 50% - RECOMMENDED THAT
 PROPERTY OWNER REDUCE SCOPE
  
 SEE EMAIL AND SPREADSHEET IN FILE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-01 Cont ID  
Sent By shill Date 2013-06-01 Time 11:53 Rev Time 0.00
Received By shill Date 2013-06-01 Time 11:53 Sent To  
Notes
2013-06-01 12:16:02****CORRECTIONS****
 ****REVISED 3/14/14****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 PLEASE CONTACT 561-233-5025 FOR MORE INFORMATION.
  
 2. AS THIS PARCEL IS LOCATED IN SPECIAL HAZARD FLOOD
 ZONE A5, THE PROVISIONS OF FBC R 322 AND CITY OF WEST
 PALM BEACH MUNICIPAL CODE 94-546(B)* SHALL APPLY.
 (**SEE BUILDING REVIEW #2)
  
 3. PAPA VALUE FOR THE STRUCTURE IS $98,459. AS THIS IS
 AN OVER 50% IMPROVEMENT, THIS IS CONSIDERED A
 SUBSTANTIAL IMPROVEMENT PER NFIP GUIDELINES. FINISHED
 FLOOR AND EQUIPMNT TO COMPLY WITH THE 7'6" MINIMUM
 REQUIREMENT. UNINHABITABLE SPACE(S) TO COMPLY WITH
 MINIMUM ELEVATION REQUIREMENT OR PROVIDE FLOOD VENTS.
  
 4. ***DISREGARD FOLLOWING COMMENT - RETAINED FOR
 INFORMATION PURPOSES SEE COMMENT #3 AND FBC 107.2.3.
 REVISE PLAN TO INCLUDE EXISTING AND PROPOSED
 ELEVATIONS. PROVIDE AN ELEVATION CERTIFICATE,
 "CONSTRUCTION DRAWINGS." TWO ADDITIONAL CERTIFICATES
 WILL BE REQUIRED; "BUILDING UNDER CONSTRUCTION" AND
 "FINISHED CONSTRUCTION."
  
 AN ELEVATION CERTIFICATE MAY BE SENT VIA EMAIL FOR
 PRELIMINARY REVIEW PRIOR TO RESUBMITTAL AT CONTRACTOR'S
 DISCRETION.
  
 PLEASE FEEL FREE TO CONTACT ME REGARDING FLOOD HAZARD
 REQUIREMENTS.
  
 ****CONTRACTOR WILL REDUCE SCOPE, RENOVATION WILL NOT
 BE A SUBSTANTIAL IMPROVEMENT, SO NO ELEVATION
 CERTIFICATE REQUIRED
  
 5. CU DETAIL, A7, PROVIDE A SPECIFICATION FOR
 ATTACHMENT TO RESIST WIND LOADS FBC R 301.
  
 6. A7, ICYNENE SHOWN AS AN OPTION, AND ATTIC VENTING
 NOT SHOWN. ENERGY CALCS SHOW ICYNENE PROPOSED. NOT
 CLEAR WHICH OPTION IS ELECTED FOR THIS JOB; PLEASE
 CORRELATE FBC 107.
  
 7. FBC 107.3.4., THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 8. THIS PARCEL APPEARS TO BE LOCATED IN EXPOSURE D, SEE
 FBC R 301.2.1.4.3. EITHER REVISE WIND DESIGN CRITERIA
 AND C&C PRESSURES, OR PROVIDE AERIALS WITH DIMENSIONS
 AND JUSTIFICATION FOR EXPOSURE C. THIS ALSO MAY BE
 EMAILED PRIOR TO RESUBMITTAL.
  
 9. FAC9N-3, PROVIDE PRODUCT APPOVALS FOR THE ROOF TILE
 AND FOAM ADHESIVE, FBC R 301.
  
 10. THIS PROPERTY HAS TWO EXPIRED PERMITS; PLEASE
 ADVISE AS TO HOW THEY WILL BE RESOLVED.
  
 11. VALUE APPEARS LOW. PLEASE PROVIDE A COPY OF THE
 CONTRACT FOR THIS JOB. VALUE TO INCLUDE ALL LABOR AND
 MATERIALS, EVEN IF PROVIDED BY OTHERS, FBC 109.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-03 Cont ID  
Sent By dhayes Date 2014-07-03 Time 16:39 Rev Time 0.00
Received By dhayes Date 2014-07-03 Time 16:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-05-15 Cont ID  
Sent By dahayes Date 2014-05-15 Time 18:09 Rev Time 0.00
Received By albarran Date 2014-05-15 Time 16:20 Sent To  
Notes
2014-05-15 18:53:26THIS PERMIT FAILED THE SECOND ELECTRICAL REVIEW AS
 MENTIONED BELOW:
  
 1. PER THE FBC-R 314 & 315 YOU SHALL INSTALL
 INTER-CONNECTED & BATTERY BACK UP SMOKE/CARBON MONOXIDE
 DETECTORS THROUGHOUT THE WHOLE HOUSE AS IF NEW
 CONSTRUCTION. ACCORDING TO THE SUBMITTED PLANS, THE
 HOUSE CURRENTLY DOES NOT HAVE AND WILL NOT HAVE A
 GARAGE. THE ANTICIPATED GARAGE AREA CONTINUES TO BE A
 HABITABLE AREA W/A CLOSET; PROBABLE SLEEPING ROOM AND
 THEREFORE SMOKE/CARBON MONOXIDE DETECTION AS ABOVE IS
 REQUIRED.
 2. ADJUST THE DRAWING SO THAT THE DISCONNECT OR THE
 SERVICE OUTLET FOR THE NEW CONDENSING UNIT ARE NOT
 BLOCKED BY THE UNIT IN VIOLATION OF NEC 110.26(A).
 3. BOXES USED IN THE CEILING FOR THE FANS OR ANY OTHER
 LUMINAIRE SHALL BE LISTED TO SUPPORT A MIN OF 50# AS
 STATED IN NEC 314.27.
 4. THE NEW ELECTRICAL PANEL "B" IS INSIDE A WIC IN
 VIOLATION OF NEC 240.24(D)&(E).
 5. AS INDICATED IN NEC 210.8(A)(7), THE OUTLETS IN THE
 LAUNDRY SHALL BE GFCI PROTECTED.
 6. WHEN "NEW" IS MENTIONED FOR METERS & PANELS "A" &"B"
 YOU SHALL INDICATE IF THIS IS A REPLACEMENT FOR AN
 OLDER UNIT OR IS THIS A NEW UNIT IN A NEW LOCATION. IF
 EXISTING METER AND PANELS ARE ELSEWHERE THAN WHERE
 INDICATED ON THE PLANS, THE EXISTING LOCATION SHALL BE
 REFLECTED ON THE PLANS.
 7. AS INDICATED BY NEC 230.70 YOU SHALL PROVIDE A
 SERVICE DISCONNECT ON THE EXTERIOR OF THE HOME AT A
 POINT ADJACENT TO THE METER.
 8. CORRECT THE ELECTRICAL LOAD CALCS AND RISER DIAGRAM
 TO INCLUDE THE POOL PANEL AND IT'S RESPECTIVE LOAD. LET
 THE CORRECTED RISER DIAGRAM REFLECT THE REQUIRED
 DISCONNECTS ON THE EXTERIOR OF THE HOME.
 NOTE: YOU WILL NOT NEED TO USE A MAIN BREAKER PANEL
 WHEN THE MAINS ARE OUTSIDE. YOU CAN GET BY WITH A MAIN
 LUG ONLY.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 08:57 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 08:57 Sent To  
Notes
2013-05-21 09:06:075-21-13
  
 NOTE: ALL ELECTRIC PER THE 2008 NEC
  
 1. GARAGE DOOR OPENER TO BE GFI TYPE. ALL GARAGE
 RECEPTS REQUIRE GFI. THERE ARE NO EXCEPTIONS LISTED IN
 THE NEC
 2. ALL RECEPTS TO BE TAMPER RESISTANT TYPE PER NEC
 406.11
 3. BATHROOM WHIRLPOOL TUB TO BE BONDED PER NEC 680.74
 4. PLEASE CLARIFY PANEL SCHEDULE REGARDING AC#2. BOTH
 2/4 AND 6/8 ARE LABELED THE SAME. ALSO, PLEASE PROVIDE
 AC EQUIPMENT SCHEDULE SHOWING
 NECESSARY ELECTRICAL DATA TO COMPARE WITH CIRCUIT
 BREAKER SIZING. ALSO, THE TERM "GENERAL LIGHTING" DOES
 NOT MEET NEC 406.4. CIRCUITS MUST BE MARKED FOR THEIR
 CLEAR, EVIDENT AND SPECIFIC PURPOSE.
 5. BALANCE OF HOME MUST ALSO HAVE SMOKE ALARMS INSALLED
 PER RESIDENTIAL CODE 314/315 IF NOT EXISTING WHETHER
 WORK IS DONE IN THESE AREAS OR NOT.
 6. PLEASE CHANGE ELECRICAL NOTE 32 FROM "BEDROOMS" TO
 "ALL AREAS" PER NEC 210.12B
 VB
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-07-09 Cont ID  
Sent By shill Date 2014-07-09 Time 14:41 Rev Time 0.00
Received By shill Date 2014-07-09 Time 13:49 Sent To  
Notes
2014-07-09 13:49:42TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-03 Cont ID  
Sent By dhayes Date 2014-07-03 Time 17:01 Rev Time 0.00
Received By dhayes Date 2014-06-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-18 Cont ID  
Sent By jgomez Date 2014-06-18 Time 10:40 Rev Time 0.00
Received By jgomez Date 2014-05-01 Time 14:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-07 Cont ID  
Sent By jgomez Date 2013-06-07 Time 14:15 Rev Time 0.00
Received By jgomez Date 2013-05-15 Time 15:46 Sent To  
Notes
2013-05-16 15:49:10R--2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-07-09 Cont ID  
Sent By shill Date 2014-07-09 Time 14:41 Rev Time 0.00
Received By shill Date 2014-07-09 Time 14:41 Sent To  
Notes
2014-07-09 14:41:42MU 2014 015253 0000
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-06-12 Cont ID  
Sent By shill Date 2014-06-12 Time 16:28 Rev Time 0.00
Received By shill Date 2014-06-12 Time 16:27 Sent To  
Notes
2014-06-12 16:28:50IMPACT FEE ASSESSMENT REQUIRED, 561-233-5025 FOR MORE
 INFORMATION
  
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 FEES DUE WERE PAID IS TO BE PROVIDED
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-06-01 Cont ID  
Sent By shill Date 2013-06-01 Time 12:16 Rev Time 0.00
Received By shill Date 2013-06-01 Time 12:16 Sent To  
Notes
2013-06-01 12:16:59SEE BUILDING COMMENTS
 IMPACT FEE ASSESSMENT REQUIRED, 561-233-5025
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-06-17 Cont ID  
Sent By hmoser Date 2014-06-17 Time 08:39 Rev Time 0.00
Received By hmoser Date 2014-06-17 Time 08:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-05-28 Cont ID  
Sent By hmoser Date 2014-05-28 Time 10:34 Rev Time 0.00
Received By hmoser Date 2014-05-28 Time 10:29 Sent To  
Notes
2014-05-28 10:34:29PLAN REVIEW BY JS. PX1328
  
 PLAN DENIED
 PROVIDE A PLAN SHOWING THE VENTILATION, CFM AT GRILLS
 EQUIPMENT SCHEDULE AND A SIGNATURE AND LIC# OF WHO DID
 THE PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-04 Cont ID  
Sent By hmoser Date 2013-06-04 Time 16:17 Rev Time 0.00
Received By hmoser Date 2013-06-04 Time 16:09 Sent To  
Notes
2013-06-04 16:17:07PLANS DENIED
 PROVIDE A COMPLETE SET OF A/C PLANS
 SHOWING DUCT LAYOUT EQUIPMENT SCHEDULE
 AND VENTILATION. PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2014-06-12 Cont ID  
Sent By shill Date 2014-06-12 Time 17:13 Rev Time 0.00
Received By shill Date 2014-06-12 Time 17:13 Sent To  
Notes
2014-06-12 17:13:40NOT A SUBSTANTIAL IMPROVEMENT. SEE APPRAISAL AND
 WORKSHEET IN FILE.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-06-19 Cont ID  
Sent By jgomez Date 2014-06-18 Time 10:40 Rev Time 0.00
Received By jgomez Date 2014-06-18 Time 10:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-06-07 Cont ID  
Sent By jgomez Date 2013-06-07 Time 14:15 Rev Time 0.00
Received By jgomez Date 2013-06-04 Time 16:09 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2014-06-12 Cont ID  
Sent By shill Date 2014-06-12 Time 10:45 Rev Time 0.00
Received By shill Date 2014-06-17 Time 10:45 Sent To  
Notes
2014-06-17 10:46:30ENTEGRA ROOF TILE SUBMITTED
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-06-01 Cont ID  
Sent By shill Date 2013-06-01 Time 12:16 Rev Time 0.00
Received By shill Date 2013-06-01 Time 12:16 Sent To  
Notes
2013-06-01 12:16:32SEE BUILDING COMMENTS
 ROOF PRODUCT APPROVALS REQUIRED
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-05-05 Cont ID  
Sent By dkittrid Date 2014-05-05 Time 10:48 Rev Time 0.00
Received By dkittred Date 2014-05-05 Time 09:57 Sent To  
Notes
2014-05-05 10:48:17PLANNING AND ZONING NOTES:
  
 5/5/2014 (APPROVED)
  
 1. REVISED PLANS DO NO ALTER P&Z'S ORIGINAL APPROVAL.
  
 2. SUFFICIENT LANDSCAPING EXISTS ON THE SITE TO MEET
 MINIMUM LANDSCAPE PLANTING REQUIREMENTS.
  
 3. IF ANY TREES NEED TO BE REMOVED OR RELOCATED FOR THE
 PROPOSED CONSTRUCTION, A TREE ALTERATION PERMIT THROUGH
 THE PLANNING DIVISION WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-05-02 16:13:355/2/14

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By avann Date 2013-05-28 Time 09:45 Rev Time 0.00
Received By ajones Date 2013-05-20 Time 15:41 Sent To  
Notes
***NONE***