| 2013-05-16 12:50:22 | ****CORRECTIONS**** |
| | ****COURTESY REVIEW BASED ON EMAIL FROM UNDERLAYMENT |
| | SALES REP*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | COMMENT FROM PREVIOUS LIST: |
| | |
| | 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E-84. |
| | |
| | IF A DIFFERENT TEST IS USED, THIS IS TO BE SUBMITTED |
| | UNDER ALTERNATIVE MATERIALS AND METHODS, FBC 104.11. |
| | SUPPORTING DOCUMENTATION/ANALYSIS TO BE SUBMITTED. |
| | |
| | THE PRODUCT PROPOSED WAS TESTED USING DOC-FF-1-70. TO |
| | USE THIS STANDARD, IT MUST BE DEMONSTRATED THAT THIS |
| | MEETS OR EXCEEDS MINIMUM CODE REQUIREMENTS. |
| | |
| | 2. NEW COMMENTS REGARDING DATA SUBMITTED VIA EMAIL: |
| | |
| | REGARDING THE DOCUMENTS SUBMITTED: |
| | |
| | FLAMMABILITY STANDARDS SILENCER.JPG - TEST SHOWS A |
| | "PASS" BUT NOT A FLAME SPREAD RATING. REQUIREMENTS FOR |
| | UNDERLAYMENT VARY DEPENDING ON JOB CONDITIONS, SEE FBC |
| | 603.1. |
| | |
| | FLAMMABILITY STANDARDS.DOC - THE HEADING STATES |
| | "FEDERAL FLAMMABILITY STANDARDS DCC-FF-1-70 FOR |
| | ACOUSTICAL UNDERLAYMENTS AND CARPET CUSHIONS" (TYPO? OR |
| | ANOTHER TEST STANDARD? UNCLEAR). PLEASE PROVIDE A COPY |
| | OF THE TEST STANDARD WHICH REFERENCES ACOUSTICAL |
| | UNDERLAYMENTS AND PROVIDE INFORMATION REGARDING HOW |
| | THIS IS EQUIVALENT OR SUPERIOR TO THE FLAME SPREAD TEST |
| | OPTIONS CONTAINED IN THE FBC. I WAS UNABLE TO LOCATE A |
| | COPY OF THE PILL TEST WHICH STATED THAT THIS IS FOR |
| | UNDERLAYMENTS AS WELL AS CARPET. |
| | |
| | FLAMMABILITY TESTING METHOD.JPG - THIS DOCUMENT IS |
| | ILLEGIBLE AND DOES NOT APPEAR TO BE CONSISTENT WITH THE |
| | TEST STANDARD. NOTE THAT THIS DOCUMENT HAS A DATE OF |
| | MARCH 12, 1975. THE CURRENT STANDARD IS DATED 2007 OR |
| | LATER. |
| | |
| | IN ORDER FOR AN ALTERNATE STANDARD TO BE USED, A |
| | COMPARISON OF THE FLAME SPREAD TEST STANDARDS |
| | PRESCRIBED BY THE FLORIDA BUILDING CODE AND |
| | (INTERNATIONAL BUILDING CODE) AND THE TEST PERFORMED IS |
| | TO BE SUBMITTED. |
| | |
| | |
| | |
| | |
| | |