Plan Review Details - Permit 13050330
Plan Review Stops For Permit 13050330
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 10:52 Rev Time 0.00
Received By hmoser Date 2013-05-24 Time 11:47 Sent To  
Notes
2013-05-25 11:47:50UNDER 5 K MECHANICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By hmoser Date 2013-05-10 Time 10:52 Rev Time 0.00
Received By hmoser Date 2013-05-09 Time 07:46 Sent To  
Notes
2013-05-10 07:51:35SENT TO MECHANICAL BOX.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By hmoser Date 2013-05-28 Time 10:52 Rev Time 0.00
Received By hmoser Date 2013-05-28 Time 10:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-10 Cont ID  
Sent By hmoser Date 2013-05-10 Time 10:52 Rev Time 0.00
Received By hmoser Date 2013-05-10 Time 10:11 Sent To  
Notes
2013-05-10 10:52:26PLAN DENIED
 1) PROVIDE CFM ON THE PLAN AT EACH GRILLE.
 PER SECTION 107 FCB 2010
 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR
 EXCEPTION # 2 TRANSFER GRILLES.
 3) REFER TO FLORIDA STATUTES 471.003 ENGINEERING
 QUALFICATIONS FOR PRACTICE SECTION 2 H
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676