Plan Review Details - Permit 13050203
Plan Review Stops For Permit 13050203
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-13 Cont ID  
Sent By jwitmer Date 2013-05-13 Time 07:33 Rev Time 0.00
Received By dharvey Date 2013-05-14 Time 08:33 Sent To  
Notes
2013-05-13 07:18:53BUILDING PLAN REVIEW
 PERMIT: 13050203
 ADD: 529 S FLAGLER SUITE # BH
 CONT: R & D CONSTRUCTORS
 TEL: (561)889-1751
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY MAY 13/2013
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 SUBMIT DOCUMENTS TO THE DESIGNER OF RECORD FOR SHOP
 DRAWING REVIEW AND APPROVAL, THEN TO THE BUILDING
 DEPARTMENT FOR APPROVAL BEFORE THE WALL FRAMING
 INSPECTION.
  
 1) FBC-B 2010 FBC-B 603.2
 1) FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 2) 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-05 Cont ID  
Sent By dharvey Date 2013-06-05 Time 12:03 Rev Time 0.00
Received By dharvey Date 2013-06-05 Time 12:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-14 Cont ID  
Sent By dharvey Date 2013-05-14 Time 08:34 Rev Time 0.00
Received By dharvey Date 2013-05-14 Time 08:34 Sent To  
Notes
2013-05-14 08:46:385-14-13
  
 1 PROVIDE PANEL DIRECTORY WITH UPDATED INFORMATION PER
 NEC 408.4.A
  
 2. ADD NOTE TO DRAWING - ALL ELECTRIC TO MEET 2008 NEC
  
 3. SHOW CIRCUITRY ON DRAWINGS
  
 4. ADD THE FOLLOWINT NOTES:
 A. ALL NEW RECEPTS TO BE TAMPER RESISTANT PER NEC
 406.11
 B. ALL NEW WIRING MUST BE PROTECTED WITH AFCI BREAKERS
 PER NEC 210.12.B
  
 5. SHOW SMOKE ALARMS PE FBC RESIDENTIAL 314.3.1
  
 6. SHOW "NEW" AND "EXISTING" DEVICES ON PLAN
  
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-11 Cont ID  
Sent By wjolin Date 2013-05-11 Time 19:35 Rev Time 0.00
Received By wjolin Date 2013-05-11 Time 19:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-05 Cont ID  
Sent By dharvey Date 2013-06-05 Time 12:04 Rev Time 0.00
Received By dharvey Date 2013-06-05 Time 12:04 Sent To  
Notes
2013-06-05 11:47:17INCOMING SENT TO VINNYS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-21 Cont ID  
Sent By hmoser Date 2013-05-21 Time 09:42 Rev Time 0.00
Received By hmoser Date 2013-05-07 Time 11:22 Sent To  
Notes
2013-05-07 11:22:45SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-05-21 Cont ID  
Sent By hmoser Date 2013-05-21 Time 09:41 Rev Time 0.00
Received By hmoser Date 2013-05-21 Time 09:29 Sent To  
Notes
2013-05-21 09:41:40NO MECHANICAL PLANS SUBMITTED. CALLED DARIN
 THE CONTRACTOR A/C CONTRACTOR IS GOING TO SUBMIT
 HIS OWN APPLICATION AND PLANS FOR PERMIT.
 PLAN REVIEW BY HAROLD MOSER.
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-08 Cont ID  
Sent By lwagner Date 2013-05-08 Time 14:18 Rev Time 0.00
Received By lwagner Date 2013-05-08 Time 13:10 Sent To  
Notes
***NONE***