Plan Review Details - Permit 13050155
Plan Review Stops For Permit 13050155
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-23 Cont ID  
Sent By jwitmer Date 2013-05-23 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 11:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By jwitmer Date 2013-05-07 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 11:13 Sent To  
Notes
2013-05-07 11:15:49BUILDING PLAN REVIEW
 PERMIT: 13050155
 ADD: 2471 OKEECHOBEE BLVD SUITE # 2611
 CONT: ALLIED ROOFING
 TEL: (305)477-7810
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MAY 07/2013
 ACTION: DENIED
  
 1) THE ROOFING CONTRACTOR SUBMITTED A MIAMI-DADE NOA
 09-0811.16 PICKED THE SUB-SYSTEM LISTED ON PAGE 8 OF 13
 AND FASTENING OPTION # 4 WITH A MAXIMUM DESIGN PRESSURE
 OF -60 PSF AND GENERAL LIMITATION # 7. LIMITATION # 7
 REQUIRES ENHANCED FASTENING CALCULATIONS IN ZONES 2 & 3
 BY A REGISTERED ARCHITECT ARCHITECT OR ENGINEER. NOTE
 PARAPET ONLY ON THREE SIDES NOT FOR SO THERE IS A ZONE
 3.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved