| 2013-05-08 18:26:57 | BUILDING PLAN REVIEW |
| | PERMIT: 13050055 |
| | ADD: 2744 HILLSBORO RD |
| | CONT: ARMOUR SCREEN CORP |
| | TEL: (561)841-8890 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 5/08/2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1 COVER SHEET, CODE SUMMARY: |
| | 1A) THE BUILDING IS INDICATED AS A TYPE IIA / |
| | UNSPRINKLERED WITH AN AREA OF 30,830 SQUARE FT. PLEASE |
| | PROVIDE AREA INCREASES TAKEN SINCE FOR A IIA BUILDING |
| | F1 OCCUPANCY ONLY ALLOWS 25,000 SQ FT. 2010 FBC-B TABLE |
| | 503 & 506.2 FRONTAGE INCREASES. |
| | |
| | 1B) SHEET A-1 COVER SHEET INDICATES THIS BUILDING |
| | DESIGN IS MIXED USE -SEPERATED OCCUPANCIES, 2010 FBC-B |
| | TABLE 508.4 DOES NOT REQUIRE FIRE SEPERATION BETWEEN |
| | THE BUSINESS OCCUPANCY AND THE F1 OR S1 OCCUPANCIES THE |
| | NFPA MAY BE MORE RESTRICTIVE AND THE MOST RESTRICTIVE |
| | CODE GOVERNS. |
| | |
| | 1C) THE FIRE AREA OF THE SEWING ROOM A F1 OCCUPANCY AND |
| | THE FABRICATION AREAS 1 & 2 COMBINED WITH THE SEWING |
| | ROOM ARE OVER 12,000 SQ FT WHICH WILL REQUIRE FIRE |
| | SPRINKLERS SEE 2010 FBC-B 903.2.4(1). |
| | |
| | 2) BOTH SHEET A-2 & A-3 INDICATE IN THE FACTORY AREA AS |
| | WELL AS STORAGE AREA WHAT APPEARS TO BE EXISTING |
| | COLUMNS, THE PLANS DO NOT INDICATE HOW THE SUPPORTING |
| | COLUMNS WALLS AND ROOF CONSTRUCTION ARE 1 HOUR FIRE |
| | RATED PROTECTED PER 2010 FBC-TABLE 601. ALSO SEE |
| | FOOTNOTES. |
| | |
| | 3) BOTH SHEETS A-2 & A-3 INDICATE A FENCED IN AREA |
| | LABELED DEALER AREA? 107.2.1.3. ADDITIONAL INFORMATION |
| | IS REQUIRED. |
| | |
| | 4) SHEET A-2 & A-3 DO NOT INDICATE AN ACCESSIBLE |
| | ENTRANCE, PLEASE REVIEW: |
| | 2010 FL ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE |
| | COST. |
| | ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL TO THE ALTERED AREA WILL BE DEEMED |
| | DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE |
| | COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE |
| | PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | |
| | 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF |
| | DISPROPORTIONALITY. |
| | WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| | OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| | DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| | THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| | EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| | DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| | ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| | ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| | FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| | ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| | ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| | RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| | DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| | ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| | ALARMS. |
| | |
| | PLEASE PROVIDE A COST BREAK DOWN WHERE AN ADDITIONAL |
| | $14,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE UPGRADES |
| | STARTING WITH A ACCESSBILE RAMP FOR THE FRONT ENTRY. |
| | |
| | 5) PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING THE |
| | EQUIPMENT LOCATION AND SHOWING : |
| | 5A) COMMON PATH OF TRAVEL (1014.3), |
| | 5B) EXIT ACCESS TRAVEL DISTANCE (TABLE 1016.1) |
| | 5C) AMOUNT OF OCCUPANTS THAT CAN TRAVEL THROUGH EXITS |
| | 1005.1. |
| | 5D) SHOW COMPLIANCE WITH 1014,2 THE BUSINESS OCCUPANCY |
| | NOT GOING THROUGH EITHER THE F1 OR S1 OCCUPANCIES. |
| | 5E) PROVIDE OCCUPANT LOAD FOR EACH TYPE OF OCCUPANCY |
| | TABLE 1004.1.1. |
| | |
| | 6) SHEET A-8 THE ACCESSIBLE RESTROOM DETAIL INDICATES |
| | THE COMMON WALL OF THE WATER CLOSET AND LAV TO BE 6'-9" |
| | LONG PLEASE REVIEW 604.3.2 & FIGURE 604.8.1.6 THE |
| | ACCESIBLE WATER CLOSET REQUIRES 60 INCHES CLEAR WIDTH |
| | THE MINIMUM DIMENSION IS 7'-1". |
| | |
| | 7) SHEET A-7 INDICATES NEW EXTERIOR OPENINGS, 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | |
| | 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 9) THE COVER SHEET INDICATES PRESSURES FOR COMPONENTS |
| | AND CLADDING BUT DOES NOT INDICATE FOR WHAT SIZE |
| | OPENINGS THESE PRESSURES ARE SUPPOSE TO CORRELATE: |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 10) SHEET A-7 THE FRONT ELEVATION INDICATES THREE NEW |
| | FRAMED ENTRY BROW, NO DETAILS ON THE PLANS SUPPORTING |
| | THE TYPE OF MATERIALS INSTALLED, OR ANCHORAGE OF THE |
| | ENTRY BROW. 107.2.1.3. ADDITIONAL INFORMATION REQUIRED. |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |