Plan Review Details - Permit 13050055
Plan Review Stops For Permit 13050055
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-03 Cont ID  
Sent By jwitmer Date 2013-06-03 Time 08:36 Rev Time 0.00
Received By jwitmer Date 2013-06-03 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-08 Cont ID  
Sent By jwitmer Date 2013-05-08 Time 18:27 Rev Time 0.00
Received By jwitmer Date 2013-05-08 Time 17:03 Sent To  
Notes
2013-05-08 18:26:57BUILDING PLAN REVIEW
 PERMIT: 13050055
 ADD: 2744 HILLSBORO RD
 CONT: ARMOUR SCREEN CORP
 TEL: (561)841-8890
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 5/08/2013
 ACTION: DENIED
  
 1) SHEET A-1 COVER SHEET, CODE SUMMARY:
 1A) THE BUILDING IS INDICATED AS A TYPE IIA /
 UNSPRINKLERED WITH AN AREA OF 30,830 SQUARE FT. PLEASE
 PROVIDE AREA INCREASES TAKEN SINCE FOR A IIA BUILDING
 F1 OCCUPANCY ONLY ALLOWS 25,000 SQ FT. 2010 FBC-B TABLE
 503 & 506.2 FRONTAGE INCREASES.
  
 1B) SHEET A-1 COVER SHEET INDICATES THIS BUILDING
 DESIGN IS MIXED USE -SEPERATED OCCUPANCIES, 2010 FBC-B
 TABLE 508.4 DOES NOT REQUIRE FIRE SEPERATION BETWEEN
 THE BUSINESS OCCUPANCY AND THE F1 OR S1 OCCUPANCIES THE
 NFPA MAY BE MORE RESTRICTIVE AND THE MOST RESTRICTIVE
 CODE GOVERNS.
  
 1C) THE FIRE AREA OF THE SEWING ROOM A F1 OCCUPANCY AND
 THE FABRICATION AREAS 1 & 2 COMBINED WITH THE SEWING
 ROOM ARE OVER 12,000 SQ FT WHICH WILL REQUIRE FIRE
 SPRINKLERS SEE 2010 FBC-B 903.2.4(1).
  
 2) BOTH SHEET A-2 & A-3 INDICATE IN THE FACTORY AREA AS
 WELL AS STORAGE AREA WHAT APPEARS TO BE EXISTING
 COLUMNS, THE PLANS DO NOT INDICATE HOW THE SUPPORTING
 COLUMNS WALLS AND ROOF CONSTRUCTION ARE 1 HOUR FIRE
 RATED PROTECTED PER 2010 FBC-TABLE 601. ALSO SEE
 FOOTNOTES.
  
 3) BOTH SHEETS A-2 & A-3 INDICATE A FENCED IN AREA
 LABELED DEALER AREA? 107.2.1.3. ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) SHEET A-2 & A-3 DO NOT INDICATE AN ACCESSIBLE
 ENTRANCE, PLEASE REVIEW:
 2010 FL ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE PROVIDE A COST BREAK DOWN WHERE AN ADDITIONAL
 $14,000.00 DOLLARS WILL BE SPENT IN ACCESSIBLE UPGRADES
 STARTING WITH A ACCESSBILE RAMP FOR THE FRONT ENTRY.
  
 5) PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING THE
 EQUIPMENT LOCATION AND SHOWING :
 5A) COMMON PATH OF TRAVEL (1014.3),
 5B) EXIT ACCESS TRAVEL DISTANCE (TABLE 1016.1)
 5C) AMOUNT OF OCCUPANTS THAT CAN TRAVEL THROUGH EXITS
 1005.1.
 5D) SHOW COMPLIANCE WITH 1014,2 THE BUSINESS OCCUPANCY
 NOT GOING THROUGH EITHER THE F1 OR S1 OCCUPANCIES.
 5E) PROVIDE OCCUPANT LOAD FOR EACH TYPE OF OCCUPANCY
 TABLE 1004.1.1.
  
 6) SHEET A-8 THE ACCESSIBLE RESTROOM DETAIL INDICATES
 THE COMMON WALL OF THE WATER CLOSET AND LAV TO BE 6'-9"
 LONG PLEASE REVIEW 604.3.2 & FIGURE 604.8.1.6 THE
 ACCESIBLE WATER CLOSET REQUIRES 60 INCHES CLEAR WIDTH
 THE MINIMUM DIMENSION IS 7'-1".
  
 7) SHEET A-7 INDICATES NEW EXTERIOR OPENINGS, 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) THE COVER SHEET INDICATES PRESSURES FOR COMPONENTS
 AND CLADDING BUT DOES NOT INDICATE FOR WHAT SIZE
 OPENINGS THESE PRESSURES ARE SUPPOSE TO CORRELATE:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 10) SHEET A-7 THE FRONT ELEVATION INDICATES THREE NEW
 FRAMED ENTRY BROW, NO DETAILS ON THE PLANS SUPPORTING
 THE TYPE OF MATERIALS INSTALLED, OR ANCHORAGE OF THE
 ENTRY BROW. 107.2.1.3. ADDITIONAL INFORMATION REQUIRED.
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-04 Cont ID  
Sent By dharvey Date 2013-06-04 Time 13:21 Rev Time 0.00
Received By dharvey Date 2013-06-04 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 11:50 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 11:50 Sent To  
Notes
2013-05-03 11:51:491. PROVIDE TYPICAL PANEL SCHEDULE AND IDENTIFY ALL
 CIRCUITS PER NEC 408.4
 2. SHOW CIRCUIT NUMBERS AT EACH NEW DEVICE LOCATION
 3. PROVIDE LIGHTING CONTROLS PER ENERGY CODE 505.2.2
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-08 Cont ID  
Sent By wjolin Date 2013-06-08 Time 09:04 Rev Time 0.00
Received By wjolin Date 2013-06-08 Time 09:00 Sent To  
Notes
2013-06-08 09:04:342744 HILLSBORO ROAD
 PERMIT #13050055
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS NEEDED FOR FIRE SPRINKLER
 AND FIRE ALARM SYSTEM INSTALLATION OR MODIFICATION.
  
 NOTE: SPRINKLER PROTECTION MAY BE NEEDED BELOW
 OBSTRUCTIONS WIDER THAN 4 FEET SUCH AS LARGE
 FABRICATION TABLES AND LARGE SEWING TABLES.
  
 NOTE: PLANS SHOW 12 FEET HIGH RACK STORAGE. ANY STORAGE
 GREATER THAN 12 FEET IN HEIGHT IS TREATED AS HIGH-PILED
 STORAGE AND MAY REQUIRE APPLICATION SPECIFIC SPRINKLERS
 TO PROPERLY PROTECT THE COMMODITY.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By wjolin Date 2013-05-06 Time 13:51 Rev Time 0.00
Received By wjolin Date 2013-05-06 Time 12:51 Sent To  
Notes
2013-05-06 13:51:192744 HILLSBORO ROAD
 PERMIT #13050055
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: ALL FIRE REVIEW COMMENTS REFERENCING NFPA 101
 REFER TO NFPA 101-THE LIFE SAFETY CODE (2009 EDITION
 WITH FLORIDA AMENDMENTS.)
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 THE PLANS INDICATE SEPARATED USE; HOWEVER, SEVERAL
 AREAS ARE NOT SEPARATED WITH FIRE BARRIERS. FOR
 EXAMPLE, THE FABRICATION AREAS (INDUSTRIAL USE) ARE NOT
 SEPARATED FROM THE STORAGE AREAS (STORAGE USE). ANOTHER
 EXAMPLE, BREAK ROOM #129 (ASSEMBLY USE) IS NOT
 SEPARATED FROM THE SEWING ROOM (INDUSTRIAL USE).
 ADEQUATE HOURLY FIRE SEPARATION SHALL BE PROVIDED IN
 ACCORDANCE WITH TABLE 6.1.14.4.1(A) AND (B).
  
 SEVERAL OCCUPANCIES SHOW EXIT ACCESS THROUGH AN
 ADJACENT OCCUPANCIES. PER SECTION 6.1.14.1.2, WHERE
 EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED (NON-SEPARATED) OCCUPANCY.
  
 PROVIDE AN OCCUPANT LOAD CALCULATION FOR ALL AREAS
 UTILIZING THE OCCUPANT LOAD FACTORS IN TABLE 7.3.1.2.
  
 THE COVER PAGE INDICATES THE BUILDING IS NOT PROTECTED
 BY AUTOMATIC SPRINKLERS; HOWEVER, SHEET A-5 INDICATES A
 TRAVEL DISTANCE OF 200 FEET FOR A BUILDING WITH
 SPRINKLER PROTECTION.
  
 THE PLANS SHOW LIMITED EMERGENCY LIGHTING. EMERGENCY
 ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1-1/2
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 PLANS SHOW RACK STORAGE. INDICATE THE STORAGE HEIGHT OF
 COMBUSTIBLES, THE COMMODITIES TO BE STORED, THE STORAGE
 ARRANGEMENT (SINGLE ROW RACK, DOUBLE ROW RACK, PALLETS,
 ETC.)
  
 NONE OF THE DOORS ON THE DOOR SCHEDULE ARE INDICATED AS
 HAVING A FIRE RESISTANCE RATING. ALSO, THE DOOR
 SCHEDULE INDICATES "SECURITY HARDWARE"; PLEASE INDICATE
 WHAT TYPE OF HARDWARE THIS IS.
  
 AT THIS TIME A COMPLETE AND THOROUGH PLAN REVIEW CANNOT
 BE PERFORMED DUE TO THE PLAN DESIGN COMBINING MULTIUSE
 (SEPARATED USE) AND MIXED USE (NON-SEPARATED USE)
 OCCUPANCIES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-08 Cont ID  
Sent By lmartine Date 2013-06-08 Time 10:26 Rev Time 0.00
Received By lmartine Date 2013-05-30 Time 10:52 Sent To  
Notes
2013-06-01 11:00:36*EXPEDITED*
 C--10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-08 Cont ID  
Sent By jwitmer Date 2013-05-08 Time 18:27 Rev Time 0.00
Received By jwitmer Date 2013-05-01 Time 12:17 Sent To  
Notes
2013-05-02 12:28:55EXPEDITED
 C--17

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-04 Cont ID  
Sent By lwagner Date 2013-06-04 Time 15:31 Rev Time 0.00
Received By lwagner Date 2013-06-04 Time 14:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By lwagner Date 2013-05-07 Time 10:16 Rev Time 0.00
Received By lwagner Date 2013-05-07 Time 08:25 Sent To  
Notes
2013-05-07 10:16:11FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A-8 RESTROOM DETAIL SHOWS A WIDTH OF 6' - 9".
 THE REQUIRED WIDTH WITH THIS CONFIGURATION WOULD BE 7'
 - 1"
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6.
  
 2. THE SINGLE DRINKING FOUNTAIN SHOWN ON A-8 WOULD NOT
 MEET THE REQUIREMENTS OF FBC ACCESSIBILITY 211.2 (HI/LO
 DRINKING FOUNTAINS WOULD MEET THE REQUIREMENT)
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 3. SHEET P-1 THE VENT SHOWN FOR THE SHOWER IS A
 HORIZONTAL DRY VENT.
 905.3 VENT CONNECTION TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A MINIMUM OF 6
 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 ***NOTES***
 1. COUNTER TOP HEIGHT FOR THE BREAKROOM SINKS IS 34"
 AFF MAX.
  
 2. THE SHOWER WILL MEET THE REQUIREMENTS OF FBC
 ACCESSIBILITY 608
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-03 Cont ID  
Sent By ajones Date 2013-05-03 Time 15:13 Rev Time 0.00
Received By ajones Date 2013-05-03 Time 15:13 Sent To  
Notes
***NONE***