Plan Review Details - Permit 13041167
Plan Review Stops For Permit 13041167
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-14 Cont ID  
Sent By jwitmer Date 2013-05-14 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2013-05-14 Time 10:12 Sent To  
Notes
2013-05-14 10:57:01BUILDING PROVISO:
 SHEET A2.1 ENLARGED DETAILS 3 & 4 ACCESSIBLE RESTROOMS
 FOR PRE-K CLASSROOM RESTROOMS
 THE LAVS ARE INDICATED TO BE 24" TO THE TOP OF THE
 BOWL, THE CHILDREN USING THE LAVS ARE PRE-K OR YOUNGER
 THAN 5 AND ARE TO USE A SIDE APPROACH PER 2010 FL
 ACCESSIBILITY CODE 606.2 EXCEPTION # 5. RED LINED
 DRAWINGS LAV WILL NEED TO BE CENTERED 2'-0" CENTERED
 OFF THE SIDE WALL. THE OVER ALL DIMENSION OF THE BACK
 WALL HAD TO INCREASE 2 INCHES TO ACCOMIDATE THE SIDE
 APPROACH. THE 60 INCH CLEANCE REQUIRED FOR THE WATER
 CLOSET WAS REDUCED TO 54 INCHES SINCE THIS DEMINISON IS
 TAKEN WITH THE WATER CLOSET AT 18 INCHES OFF THE WALL.
 WITH THE LOCATION OF THE WATER CLOSET AT 12 INCHES OFF
 THE WALL WE CAN USE THE 54 INCH CLEARANCE REQUIREMENT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-15 Cont ID  
Sent By dharvey Date 2013-05-15 Time 13:46 Rev Time 0.00
Received By dharvey Date 2013-05-15 Time 13:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-06 Cont ID  
Sent By wjolin Date 2013-05-06 Time 11:52 Rev Time 0.00
Received By wjolin Date 2013-05-06 Time 10:24 Sent To  
Notes
2013-05-06 11:52:45807 NORTH FLAGLER DRIVE
 PERMIT #13041167
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET M1.1: EXHAUST DUCT SHALL NOT BE ROUTED THROUGH
 THE EXIT STAIR UNLESS THE DUCTWORK IS SEPARATED FROM
 THE STAIR BY A FIRE-RATED BARRIER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 07:54 Rev Time 0.00
Received By hmoser Date 2013-04-30 Time 11:18 Sent To  
Notes
2013-05-01 11:20:07INCOMING SENT TO C14. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-31 Cont ID  
Sent By hmoser Date 2013-05-31 Time 10:48 Rev Time 0.00
Received By hmoser Date 2013-05-30 Time 11:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-14 Cont ID  
Sent By lwagner Date 2013-05-14 Time 12:10 Rev Time 0.00
Received By lwagner Date 2013-05-06 Time 14:11 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-05-03 Cont ID  
Sent By ajones Date 2013-05-03 Time 15:40 Rev Time 0.00
Received By ajones Date 2013-05-03 Time 15:40 Sent To  
Notes
***NONE***