Plan Review Details - Permit 13041122
Plan Review Stops For Permit 13041122
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-07-29 Cont ID  
Sent By jgomez Date 2013-07-29 Time 17:13 Rev Time 0.00
Received By jgomez Date 2013-07-29 Time 17:13 Sent To  
Notes
2013-07-29 18:01:03BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A)ALL
 SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE ENGINEER
 ON PLANS AND DETAILS (NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR). B)METAL SIDING AS SPECIFIED ON NOTE # 4 ON
 SHEET A2.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS
 SUBMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-07-11 Cont ID  
Sent By jgomez Date 2013-07-10 Time 09:16 Rev Time 0.00
Received By jgomez Date 2013-07-10 Time 09:16 Sent To  
Notes
2013-07-10 09:21:27RESIDENTIAL (R3) RENOVATIONS, BUILDING REVIEW SECOND
 CHECKLIST.
 CODE: 2010 FBC
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3:
 A) ROOF RIDGE VENT AS SPECIFIED ON THE HCD
 "SPECIFICATIONS" BOOKLET.
  
 B) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL
 FL14604-R2 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER ON SHEET A2 SUBMITTED. SEC.
 R301.1 OF 2010 FBC-RESIDENTIAL.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED BY THE
 ENGINEER ON PLANS AND DETAILS SUBMITTED.
  
 D) METAL SIDING AS SPECIFIED ON NOTE # 4 OF FRAMING
 LEGEND ON SHEET A2.
  
 2- ENGINEER WHO PRODUCED THE PLANS TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL THE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 3- ENGINEER TO PROVIDE SPECIFICATIONS ON PLANS FOR THE
 NEW ROOF RIDGE VENT AS SPECIFIED ON THE "HCD
 SPECIFICATIONS BOOKLET". SEE SEC. R806 OF 2010
 FBC-RESIDENTIAL.
  
 4- ORIGINAL COMMENT: CITY HCD "SPECIFICATIONS" SPECIFY
 NEW PULL DOWN STAIRS FOR ATTIC ACCESS. CLARIFY IF THERE
 IS AN EXISTING PULL DOWN STAIRS. IF NOT, THEN NEED TO
 PROVIDE ENGINEERING SHOWING THAT EXISTING ATTIC IS
 ADEQUATE TO RECEIVE THE NEW STAIRS AND THAT THE ATTIC
 IS DESIGNED TO RESIST THE NEW STORAGE LOAD REQUIRED BY
 TABLE R301.5 OF 2010 FBC-RESIDENTIAL. SEC. 107.2.1.3 OF
 CITY AMENDMENTS TO FBC.
  
 RESPONSE: THERE IS NO RESPONSE TO THIS ITEM. ENGINEER'S
 PLANS SUBMITTED DIDN'T ADDRESS THIS ISSUE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 15:00 Rev Time 0.00
Received By jgomez Date 2013-05-16 Time 14:24 Sent To  
Notes
2013-05-16 15:23:42RESIDENTIAL (R3) REPAIRS BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW TO DO ALL THE WORK SPECIFIED ON THE
 "SPECIFICATIONS" BOOKLET SUBMITTED. SEC. 109.3 CITY
 AMENDMENTS TO FBC.
 *** PROVIDE COPY OF SIGNED CONTRACT WITH CITY HOUSING
 AND COMMUNITY DEVELOPMENT AGENCY (HCD).
  
 2- BEDROOM WINDOWS: SPECIFY TYPE AND SIZE OF EXISTING
 WINDOWS AND TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY
 COMPLIANCE WITH SEC. 601.2 AND SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3:
 A) ROOF RIDGE VENT AS SPECIFIED ON THE HCD
 "SPECIFICATIONS" BOOKLET.
  
 B) SINGLE HUNG WINDOWS. NOA 10-0428.02 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
  
 C) WINDOW MULLIONS IF THERE ARE ANY WINDOWS THAT ARE
 GOING TO BE MULLED TOGETHER.
  
 4- CITY HCD "SPECIFICATIONS" SPECIFY NEW PULL DOWN
 STAIRS FOR ATTIC ACCESS. CLARIFY IF THERE IS AN
 EXISTING PULL DOWN STAIRS. IF NOT, THEN NEED TO PROVIDE
 ENGINEERING SHOWING THAT EXISTING ATTIC IS ADEQUATE TO
 RECEIVE THE NEW STAIRS AND THAT THE ATTIC IS DESIGNED
 TO RESIST THE NEW STORAGE LOAD REQUIRED BY TABLE R301.5
 OF 2010 FBC-RESIDENTIAL. SEC. 107.2.1.3 OF CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-08-07 Cont ID  
Sent By dharvey Date 2013-08-07 Time 17:22 Rev Time 0.00
Received By dharvey Date 2013-08-07 Time 17:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-07-02 Cont ID  
Sent By dharvey Date 2013-07-02 Time 09:30 Rev Time 0.00
Received By dharvey Date 2013-07-02 Time 09:30 Sent To  
Notes
2013-07-02 09:31:1713041122
 716 48TH ST.
 REWIRE EXISTING HOUSE
  
 PLEASE PROVIDE DETAILED ELECTRICAL PLAN FOR ALL
 IMPROVEMENTS.
  
 INDICATE THE SIZE, RATING, LOCATION OF THE EXISTING
 SERVICE, MAIN DISCONNECT AND PANELBOARD. SHOW SERVICE
 AND PANEL BOARD LOCATIONS. SHOW NEW AND EXISTING
 OUTLETS. INCLUDE A PANEL SCHEDULE. NEC 215.5
  
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI PROTECTED.
 NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS. IF THE
 RESIDENCE HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A
 FIRE PLACE A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. FBC
 R313
  
 ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE BEDROOMS
 AND HALLWAY. ADD RECEPTACLES SO THAT NO WALL SPACE IS
 MORE THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES
 MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 THE LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR LIGHT
 AND SWITCH CONTROLLED OUTSIDE LIGHTS. NEC 210.70
  
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8
  
 PROVIDE TWO OR MORE 20- AMPERE SMALL APPLIANCE BRANCH
 CIRCUITS. NEC 210.52
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 09:58 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 09:58 Sent To  
Notes
2013-05-03 09:59:13PLEASE PROVIDE AN ENGINEERED DRAWING SHOWING ALL WORK
 TO BE DONE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-07 Cont ID  
Sent By shill Date 2013-08-07 Time 17:30 Rev Time 0.00
Received By shill Date 2013-07-19 Time 16:54 Sent To  
Notes
2013-07-19 16:55:03R-05

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-11 Cont ID  
Sent By jgomez Date 2013-07-11 Time 16:05 Rev Time 0.00
Received By jgomez Date 2013-06-17 Time 09:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-28 Cont ID  
Sent By lmartine Date 2013-05-28 Time 14:21 Rev Time 0.00
Received By lmartine Date 2013-04-29 Time 09:48 Sent To  
Notes
2013-04-30 09:48:41R12

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2013-08-12 Cont ID  
Sent By jgomez Date 2013-08-12 Time 11:30 Rev Time 0.00
Received By jgomez Date 2013-08-12 Time 11:30 Sent To  
Notes
2013-08-12 11:30:40PROVIDE COMPLETE INFORMATION UNDER A SEPARATE PERMIT.
 JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2013-07-29 Cont ID  
Sent By jgomez Date 2013-07-29 Time 18:30 Rev Time 0.00
Received By jgomez Date 2013-07-29 Time 18:12 Sent To  
Notes
2013-07-29 18:45:40RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER SHOWN ON THE A/C PLAN TITLE BLOCK TO SIGN
 AND DATE DRAWING AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 2- A/C PLAN: SPECIFY THE CFM FOR EACH ROOM TO VERIFY
 COMPLIANCE WITH THE BALANCED RETURN AREA SEC. M1602.4
 OF 2010 FBC-RESIDENTIAL.
  
 3- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC.
 M1602.2 OF 2010 FBC-RESIDENTIAL. CLEARLY SHOW ON A/C
 PLAN RETURN AIR LOCATION AND SIZE.
  
 4- EQUIPMENT SIZING CALCULATIONS SPECIFY UNVENTED
 ATTIC. THIS ATTIC IS VENTED. SEE PLANS SUBMITTED.
 REVISE AS REQUIRED. ALSO, SHOW ON A/C PLAN THE SEER
 REQUIRED BY THE EQUIPMENT SIZING CALCULATIONS
 SUBMITTED. SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2013-07-11 Cont ID  
Sent By jgomez Date 2013-07-11 Time 15:38 Rev Time 0.00
Received By jgomez Date 2013-07-11 Time 15:38 Sent To  
Notes
2013-07-11 16:04:291- NO INFORMATION SUBMITTED NOW. PROVIDE COMPLETE A/C
 INFORMATION UNDER A SEPARATE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 14:33 Rev Time 0.00
Received By jgomez Date 2013-05-16 Time 14:33 Sent To  
Notes
2013-05-16 14:40:44RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE A/C PLANS AND COMPLETE EQUIPMENT
 SIZING CALCULATIONS (2 COPIES). SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-16 Cont ID  
Sent By jgomez Date 2013-05-16 Time 15:00 Rev Time 0.00
Received By jgomez Date 2013-05-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-28 Cont ID  
Sent By avann Date 2013-05-28 Time 10:25 Rev Time 0.00
Received By ajones Date 2013-05-28 Time 10:24 Sent To  
Notes
2013-05-28 10:25:06HCD PROJECT 50% RULE DOES NOT APPLY
2013-05-06 10:36:335/3/13