Plan Review Details - Permit 13041098
Plan Review Stops For Permit 13041098
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-16 Cont ID  
Sent By dharvey Date 2013-05-16 Time 10:07 Rev Time 0.00
Received By dharvey Date 2013-05-16 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-16 Cont ID  
Sent By wjolin Date 2013-05-16 Time 09:45 Rev Time 0.00
Received By wjolin Date 2013-05-16 Time 08:46 Sent To E
Notes
2013-05-16 09:35:284847 FRED GLADSTONE DRIVE
 PERMIT #13041098
 MASTER #12030044
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 SHEET FA-1: THE TWO WALL MOUNTED NOTIFICATION
 APPLIANCES (LOCATED AT THE EAST END OF CORRIDOR #143)
 ARE SPACED AT A DISTANCE THAT WILL PREVENT ADEQUATE
 STROBE INTENSITY IN THE CORRIDOR. ROTATE (90 DEGRESS)
 NOTIFICATION APPLIANCE #N5.1 OR ADD A STROBE DEVICE IN
 THE CORRIDOR. TYPICAL ALL THREE FLOORS.
  
 SHEET FA-1: THE TWO WALL MOUNTED NOTIFICATION
 APPLIANCES (LOCATED AT THE NORTH END OF CORRIDOR #114)
 ARE SPACED AT A DISTANCE THAT WILL PREVENT ADEQUATE
 STROBE INTENSITY IN THE CORRIDOR. ROTATE (90 DEGRESS)
 NOTIFICATION APPLIANCE #N1.15 OR ADD A STROBE DEVICE IN
 THE CORRIDOR. TYPICAL ALL THREE FLOORS.
  
 SHEET FA-1: THE TWO WALL MOUNTED NOTIFICATION
 APPLIANCES (LOCATED AT THE NORTH END OF CORRIDOR #174)
 ARE SPACED AT A DISTANCE THAT WILL PREVENT ADEQUATE
 STROBE INTENSITY IN THE CORRIDOR. ADD A STROBE DEVICE
 IN THE CORRIDOR. TYPICAL ALL THREE FLOORS.
  
 SHEET FA-1: NONE OF THE PATIENT UNITS ARE EQUIPPED WITH
 STROBE DEVICES TO ACCOMMODATE FOR ANY HEARING-IMPAIRED
 PATIENTS.
  
 SHEET FA-3: THE HYDRAULIC ELEVATORS SHOULD NOT HAVE
 FIRE SPRINKLERS LOCATED AT THE TOP OF THE ELEVATOR
 SHAFT; THEREFORE, THE HEAT AND SMOKE DETECTORS SHALL BE
 REMOVED FROM THE TOP OF THE ELEVATOR SHAFT.
  
 SHEET FA-4: THE HYDRAULIC ELEVATORS SHOULD NOT HAVE
 FIRE SPRINKLERS LOCATED AT THE TOP OF THE ELEVATOR
 SHAFT; THEREFORE, THE HEAT AND SMOKE DETECTORS SHALL BE
 REMOVED FROM THE TOP OF THE ELEVATOR SHAFT.
  
 FIRE ALARM MATRIX: PER LOCAL AHJ POLICY, DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM
 CONDITION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-16 Cont ID  
Sent By dharvey Date 2013-05-16 Time 10:07 Rev Time 0.00
Received By shill Date 2013-05-16 Time 10:07 Sent To  
Notes
2013-04-29 15:23:29SENT TO FIRE BOX.