Plan Review Details - Permit 13041087
Plan Review Stops For Permit 13041087
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-10 Cont ID  
Sent By rmcdouga Date 2013-06-10 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2013-06-10 Time 07:16 Sent To  
Notes
2013-06-10 08:54:362010 FBC
  
 REVISIONS REQUIRED
  
 THE WORK ON THIS PROJECT WAS DONE WITHOUT PERMITS OR
 INSPECTIONS. THE FOLLOWING ITEMS WILL BE SUBMITTED AND
 APPROVED PRIOR TO FINAL INSPECTION.
  
 1) ENERGY CALCULATIONS (FBC ENERGY 402)
  
 2) FOUNDATION DETAILS (FBC R403)
  
 3) PRODUCT APPROVALS FOR STRUCTURAL CONNECTORS (DCA
 RULE 9N-3)
  
 4) PRODUCT APPROVALS FOR METAL ROOF (DCA RULE 9N-3)
  
 4) EXTERIOR WALL SHEATHING (FBC R703.1.2)
  
 5) EXTERIOR WALL WATER RESISTIVE BARRIER (FBC R703.2)
  
 6) DETAILS OF UNDER FLOOR SPACE SHOWING COMPLIANCE WITH
 VENTILATION AND ACCESS REQUIREMENTS (FBC R408).

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-14 Cont ID  
Sent By rmcdouga Date 2013-05-14 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2013-05-13 Time 12:48 Sent To  
Notes
2013-05-13 13:03:232010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 ADDITIONS AS REQUIRED BY FBC ENERGY 101.4.3.
  
 2) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION.
  
 3) PROVIDE ADDITIONAL DETAILS OF THE FOUNDATIONS FOR
 THE ADDITIONS SHOWING THAT THEY COMPLY WITH FBC R403.1,
 R403.1.1, R403.1.2, R403.1.4, R404.1.6, R408.1 AND
 R408.4.
  
 4) SHOW COMPLIANCE WITH FBC R317.1 FOR PROTECTION OF
 WOOD JOISTS AND WOOD STRUCTURAL FLOOR MEMBERS.
  
 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE
 PROTECTION.
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS, AS REQUIRED BY
 DCA RULE 9N-3, FOR THE SIMPSON CONNECTORS AND THE METAL
 ROOF SPECIFIED IN ITEM #2 UNDER BUILDING ENVELOPE IN
 THE SCOPE OF WORK ON SHEET SP-1.
  
 7) THE WALL SECTION APPEARS TO SHOW STRUCTURAL WALL
 SHEATHING BEHIND THE HARDI-BOARD SIDING. PLEASE CLARIFY
 AND SPECIFY THE SHEATHING MATERIAL. CITY AMENDMENTS
 107.2.1
  
 8) SHOW COMPLIANCE WITH R703.2 FOR WEATHER-RESISTANT
 SHEATHING PAPER ON EXTERIOR WALLS.
  
 9) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 MODIFIED BITUMEN ROOF SYSTEM HAS A FLORIDA COVERSHEET
 (FL# 5680) ATTACHED TO A MIAMI-DADE NOA. THE
 INSTALLATION REQUIREMENTS ARE DIFFERENT FOR EACH OF
 THESE. PLEASE CHOOSE THE ONE THAT YOU WANT TO USE AND
 SUBMIT IT. IF ENHANCED FASTENING OF THE BASE SHEET IS
 REQUIRED TO ACHIEVE HIGHER UPLIFT FOR THE CORNER AND
 PERIMETER ROOF AREAS, THEN SUBMIT TWO SETS OF SIGNED
 AND SEALED RAS 117 CALCULATIONS. DCA RULE 9N-3.
  
 10) SUBMIT TWO SETS OF A KEY PLAN AND AN INSTALLATION
 SCHEDULE FOR THE STORM PANELS (FL# 10905-R1) THAT WERE
 SUBMITTED.
  
 11) SHOW COMPLIANCE WITH FBC R314.3.1 FOR INSTALLATION
 OF SMOKE ALARMS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-07 Cont ID  
Sent By dharvey Date 2013-06-07 Time 10:34 Rev Time 0.00
Received By dharvey Date 2013-06-07 Time 10:34 Sent To  
Notes
2013-06-07 10:34:506-7-13
 CORRECTIONS MADE
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-03 Cont ID  
Sent By dharvey Date 2013-05-03 Time 09:26 Rev Time 0.00
Received By dharvey Date 2013-05-03 Time 09:26 Sent To  
Notes
2013-05-03 09:29:011. PROVIDE TYPICAL PANEL SCHEDULE SHOWING CIRCUITS AND
 WIRE SIZES
 2. ALL NEW DEVICES SHALL COMPLY WITH NEC 406.11
 3. ALL NEW WIRING MUST COMPLY WITH NEC 210.12B

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-10 Cont ID  
Sent By rmcdouga Date 2013-06-10 Time 08:04 Rev Time 0.00
Received By rmcdouga Date 2013-06-07 Time 10:07 Sent To  
Notes
2013-06-07 12:29:286/6 TO RM DESK
2013-06-07 10:07:23TO VB DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-14 Cont ID  
Sent By rmcdouga Date 2013-05-14 Time 16:26 Rev Time 0.00
Received By rmcdouga Date 2013-04-26 Time 17:16 Sent To  
Notes
2013-04-26 17:16:42EXPEDITED
 R--4

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-05-13 Cont ID  
Sent By rmcdouga Date 2013-05-13 Time 10:19 Rev Time 0.00
Received By rmcdouga Date 2013-05-13 Time 10:19 Sent To  
Notes
2013-05-13 10:19:38MU-2013-8463

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-10 Cont ID  
Sent By rmcdouga Date 2013-06-10 Time 07:29 Rev Time 0.00
Received By rmcdouga Date 2013-06-10 Time 07:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-13 Cont ID  
Sent By rmcdouga Date 2013-05-13 Time 10:19 Rev Time 0.00
Received By rmcdouga Date 2013-05-13 Time 10:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-06-28 Cont ID  
Sent By rmcdouga Date 2013-06-28 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2013-06-28 Time 11:20 Sent To  
Notes
2013-06-28 11:24:52NOA NO. 12-0202.04 GAF LIBERTY SBS SELF-ADHERING
 BITUMEN ROOF SYSTEM WAS SUBMITTED. SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED AND WERE NOT
 SUBMITTED. WORK WAS DONE WITHOUT PERMITS OR
 INSPECTIONS.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-06 Cont ID  
Sent By mdekle Date 2013-05-06 Time   Rev Time  
Received By mdekle Date 2013-05-06 Time   Sent To  
Notes
2013-05-06 11:45:59APPROVED VIA ZBA3294. PROJECT #Z13020002
2013-05-06 10:35:435/3/13