| Plan Review Stops For Permit 13041056 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-05-14 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-05-14 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-05-14 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2013-05-14 13:38:21 | 5-14-13 | | | CORRECTIONS MADE - VB |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-05-06 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-05-06 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-05-06 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2013-05-06 10:53:36 | 5-6-13 | | | 1. PROVIDE ENGINEERED MOUNTING DETAILS FOR 75 KVA | | | CEILING HUNG TRANSFORMER | | | 2. PROVIDE ELECTRICAL RISER DIAGRAM AND FAULT CURRENTS | | | - NEC 110.9, 110.10, 215.5 | | | 3. PROVIDE PANEL SCHEDULES PER NEC 408.4 FOR | | | CLARIFICATION PURPOSES | | | | | | VB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-05-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-05-14 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-05-14 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2013-05-14 13:19:40 | TO ELEC | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-05-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-05-07 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-04-26 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2013-04-26 08:49:04 | IN ELECTRIC BOX |
|
|
|