Plan Review Details - Permit 13041056
Plan Review Stops For Permit 13041056
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-14 Cont ID  
Sent By dharvey Date 2013-05-14 Time 13:37 Rev Time 0.00
Received By dharvey Date 2013-05-14 Time 13:37 Sent To  
Notes
2013-05-14 13:38:215-14-13
 CORRECTIONS MADE - VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 10:50 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 10:50 Sent To  
Notes
2013-05-06 10:53:365-6-13
 1. PROVIDE ENGINEERED MOUNTING DETAILS FOR 75 KVA
 CEILING HUNG TRANSFORMER
 2. PROVIDE ELECTRICAL RISER DIAGRAM AND FAULT CURRENTS
 - NEC 110.9, 110.10, 215.5
 3. PROVIDE PANEL SCHEDULES PER NEC 408.4 FOR
 CLARIFICATION PURPOSES
  
 VB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-14 Cont ID  
Sent By shill Date 2013-05-14 Time 15:48 Rev Time 0.00
Received By shill Date 2013-05-14 Time 13:19 Sent To  
Notes
2013-05-14 13:19:40TO ELEC
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-07 Cont ID  
Sent By shill Date 2013-05-07 Time 11:34 Rev Time 0.00
Received By shill Date 2013-04-26 Time 08:48 Sent To  
Notes
2013-04-26 08:49:04IN ELECTRIC BOX