Plan Review Details - Permit 13040963
Plan Review Stops For Permit 13040963
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-04-30 Cont ID  
Sent By dharvey Date 2013-04-30 Time 13:37 Rev Time 0.00
Received By dharvey Date 2013-04-30 Time 13:37 Sent To  
Notes
2013-04-30 13:43:29AHU 1 - MAX BREAKER SHOULD BE 50 AMP, DRAWINGS SHOW 60
 AMP
 AHU2 - MAX BREAKER SHOULD BE 30 AMO, DRAWINGS SHOW 60
 AMP
  
 BOTH AHU'S LABELED #1
  
 CU1 - MAX BREAKER SHOULD BE 25 AMP, DRAWINGS SHOW 40
 AMP
 CU2 - MAX BREAKER SHOULD BE 30 AMP, DRAINGS SHOW 30 AMP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-01 Cont ID  
Sent By hmoser Date 2013-05-01 Time 10:04 Rev Time 0.00
Received By hmoser Date 2013-04-24 Time 09:23 Sent To  
Notes
2013-04-25 09:24:09EXPEDITED
 GAVE TO HAROLD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-05-01 Cont ID  
Sent By hmoser Date 2013-05-01 Time 10:04 Rev Time 0.00
Received By hmoser Date 2013-05-01 Time 09:32 Sent To  
Notes
***NONE***