E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-04-30 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-04-30 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-04-30 |
Time |
13:37 |
Sent To |
|
|
| Notes |
| 2013-04-30 13:43:29 | AHU 1 - MAX BREAKER SHOULD BE 50 AMP, DRAWINGS SHOW 60 | | | AMP | | | AHU2 - MAX BREAKER SHOULD BE 30 AMO, DRAWINGS SHOW 60 | | | AMP | | | | | | BOTH AHU'S LABELED #1 | | | | | | CU1 - MAX BREAKER SHOULD BE 25 AMP, DRAWINGS SHOW 40 | | | AMP | | | CU2 - MAX BREAKER SHOULD BE 30 AMP, DRAINGS SHOW 30 AMP |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-05-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-05-01 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-04-24 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2013-04-25 09:24:09 | EXPEDITED | | | GAVE TO HAROLD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-05-01 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2013-05-01 |
Time |
10:04 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2013-05-01 |
Time |
09:32 |
Sent To |
|
|
| Notes |
|
|
|