Plan Review Details - Permit 13040935
Plan Review Stops For Permit 13040935
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2013-06-24 Time 14:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 16:52 Sent To  
Notes
2013-06-12 09:05:382010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE A SITE PLAN OR SURVEY THAT SPECIFIES THE
 DISTANCE TO THE PROPERTY LINE ON THE SIDE OF THE GARAGE
 WHERE THE PROPOSED WINDOW IS LOCATED. SEE FBCR302.1 AND
 TABLE R302.1 FOR REQUIRED FIRE SEPARATION DISTANCE FOR
 OPENINGS.
  
 2) THE OCCUPANCY, TYPE OF CONSTRUCTION AND LEVEL OF
 ALTERATION ON SHEET A-1 ARE INCORRECT. THIS IS A SINGLE
 FAMILY RESIDENCE WHICH IS AN R-3 OCCUPANCY (FBC SECTION
 310.1), THE TYPE OF CONSTRUCTION IS VB (FBC SECTION
 602) AND IT IS A LEVEL 2 ALTERATION PER FBC EXISTING
 BUILDING SECTION 404. PLEASE CORRECT.
  
 3) SPECIFY THE WINDSPEED AND EXPOSURE CATEGORY FOR THIS
 PROJECT ON THE PLANS. THE WINDSPEED IS 170 MPH VULT /
 132 VASD AND THE EXPOSURE CATEGORY IS C. FBC R301.2.1.1
 AND R301.2.1.4.3
  
 4) SHOW COMPLIANCE WITH FBC ENERGY SECTION 402 BY
 SUBMITTING THE REQUIRED ENERGY COMPLIANCE FORMS FOR THE
 PROPOSED HABITABLE SPACE.
  
 5) SHOW COMPLIANCE WITH FBC R314 .3.1 FOR REQUIRED
 SMOKE ALARMS.
  
 6) THE TITLE BLOCK ON THE PLAN SHEETS ARE MISSING SOME
 OF THE MINIMUM INFORMATION REQUIRED BY FAC 61G1-16.004.
 PLEASE INCLUDE THE LICENSE NUMBER OF THE ARCHITECTURAL
 FIRM AND THE PRINTED NAME OF THE PERSON SEALING THE
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-20 Cont ID  
Sent By dharvey Date 2013-05-20 Time 14:36 Rev Time 0.00
Received By dharvey Date 2013-05-20 Time 14:36 Sent To  
Notes
2013-05-20 14:36:445-20-13
 APPROVED WITH EXCEPTION.....
 SEE NOTES ON DRAWINGS.
 VB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 16:11 Rev Time 0.00
Received By rmcdouga Date 2013-06-14 Time 09:41 Sent To  
Notes
2013-06-14 09:42:05SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2013-04-23 Time 09:45 Sent To  
Notes
2013-06-10 09:49:296/10 - CHANGED INCOMING DATE TO DATE OF INITIAL
 APPLICATION AS APPLICANT WAS INFORMED THAT SUBMITTING
 ADDITIONAL PLANS WOULD NOT AFFECT PLAN REVIEW (AND WAS
 AT 30 DAYS AT TIME OF SUBMITTAL)
  
2013-05-24 14:24:46ADD DRIVEWAY PLAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 10:01 Rev Time 0.00
Received By rmcdouga Date 2013-04-23 Time 07:48 Sent To  
Notes
2013-04-24 07:51:07R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2013-06-24 Time 14:38 Sent To  
Notes
2013-06-24 16:15:06NO FEES WERE DUE

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-06-11 Cont ID  
Sent By rmcdouga Date 2013-06-11 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 16:52 Sent To  
Notes
2013-06-11 16:55:23IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED. ONE
 SET OF THE APPROVED PLANS IS TO BE SIGNED OUT AND TAKEN
 TO PALM BEACH COUNTY. THE STAMPED PLANS AND A COPY OF
 THE IMPACT FEE RECEIPT ARE TO BE RETURNED TO THE CITY
 BEFORE THE PERMIT IS ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2013-06-24 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-06-11 Cont ID  
Sent By hmoser Date 2013-06-11 Time 14:14 Rev Time 0.00
Received By hmoser Date 2013-06-11 Time 14:02 Sent To  
Notes
2013-06-11 14:14:17PLANS DENIED
 PROVIDE A PLAN SHOWING
 DUCT AND GRILL SIZE AND CFM
 PER SECTION 105 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-06-24 Cont ID  
Sent By rmcdouga Date 2013-06-24 Time 14:37 Rev Time 0.00
Received By rmcdouga Date 2013-06-24 Time 14:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-06-12 Cont ID  
Sent By rmcdouga Date 2013-06-12 Time 07:14 Rev Time 0.00
Received By rmcdouga Date 2013-06-11 Time 16:56 Sent To  
Notes
2013-06-12 07:14:012010 FBC
  
 DENIED BY PLUMBING
  
 1) AS A RESULT OF THIS PROJECT, THE WATER HEATER IS NOW
 LOCATED IN HABITABLE SPACE AND IS REQUIRED TO BE
 INSTALLED IN A METAL OR PLASTIC PAN WITH A DRAIN AND
 TERMINATION POINT IN COMPLIANCE WITH FBCR P2801.5,
 P2801.5.1 AND P2801.5.2.
  
 2) THE PRESSURE RELIEF VALVE DISCHARGE SHALL COMPLY
 WITH FBCR P2803.6.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-06-07 Cont ID  
Sent By ajones Date 2013-06-07 Time 12:41 Rev Time 0.00
Received By ajones Date 2013-05-28 Time 16:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By mdekle Date 2013-05-06 Time   Rev Time  
Received By mdekle Date 2013-05-06 Time   Sent To  
Notes
2013-05-06 14:10:27ZONING REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. THE APPLICANT MUST PROVIDE A SURVEY OR SITE PLAN
 DEPICTING THE DIMENSIONS OF THE EXISITING DRIVEWAY - IN
 ACCORDANCE WITH SECTION 94-482 (B) CONFIGURATION,
 REQUIRED OFF-STREET PARKING AREAS SHALL CONSIST OF A
 PARKING BAY, STALL, DRIVEWAY, GARAGE, OR COMBINATION
 THEREOF. THE SITE PLAN THAT WAS PROVIDED ON THE
 PROPOSED PLANS IS NOT TO SCALE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT THE CITY'S
 ZONING ADMINISTRATOR, ANGELLA VANN 561-822-1441 AND/OR
 CONSULT THE CITY?S ZONING AND LAND DEVELOPMENT
 REGULATIONS ONLINE @WWW.MUNICODE.COM.
  
  
  
  
  
  
  
2013-04-29 14:47:234/29/13