Plan Review Details - Permit 13040905
Plan Review Stops For Permit 13040905
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-07-16 Cont ID  
Sent By JWITMER Date 2013-07-16 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2013-07-16 Time 12:00 Sent To  
Notes
2013-07-16 12:32:42BUILDING PLAN REVIEW
 REVISION: 13040905
 PERMIT: 12100898
 ADD: 500 PALM ST # 32
 CONT: LIVINGSTON BUILDERS
 TEL: (561)373-6552
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: JULY 16/2013
 ACTION: DENIED
  
 1) THE REVISION HAS REMOVED THE ACCESSIBLE RESTROOM.
 2010 FL ACCESSIBILTY CODE 202.3.1. PROHIBITED REDUCTION
 IN ACCESS.
 AN ALTERATION THAT DECREASES OR HAS THE EFFECT OF
 DECREASING THE ACCESSIBILITY OF A BUILDING OR FACILITY
 BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME
 OF THE ALTERATION IS PROHIBITED.
 ADVISORY 202.3.1 PROHIBITED REDUCTION IN ACCESS.
 DEPARTMENT OF JUSTICE REGULATIONS 28 CFR 35.133 FOR
 PUBLIC ENTITIES (TITLE II) AND 28 CFR 36.211 FOR
 PRIVATE ENTITIES (TITLE III) CLARIFY THAT REDUCTION OF
 ACCESSIBILITY IS BENCHMARKED TO THE 2010 ADA STANDARDS
 FOR ACCESSIBLE DESIGN AS ADOPTED BY THIS CODE. THOSE
 REGULATIONS STATE: ?IF THE 2010 STANDARDS REDUCE THE
 TECHNICAL REQUIREMENTS OR THE NUMBER OF REQUIRED
 ACCESSIBLE ELEMENTS BELOW THE NUMBER REQUIRED BY THE
 1991 STANDARDS, THE TECHNICAL REQUIREMENTS OR THE
 NUMBER OF ACCESSIBLE ELEMENTS IN A FACILITY SUBJECT TO
 THIS PART MAY BE REDUCED IN ACCORDANCE WITH THE
 REQUIREMENTS OF THE 2010 STANDARDS.?
  
 1A) 2010 FL ACCESS CODE REVIEW 604.3.2. FIGURE
 604.8.1.6.
  
 1B) 2010 FL ACCESS CODE 606.1-5 LAVATORIES.
  
 1C) 2010 ACCESS CODE 604.5 .1 GRAB BARS SIDE WALL
 604.5.2 REAR WALL.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-08-15 Cont ID  
Sent By DHARVEY Date 2013-08-15 Time 18:34 Rev Time 0.00
Received By dharvey Date 2013-08-15 Time 18:17 Sent To  
Notes
2013-08-15 18:27:29HEIGHT OF ELECTRICAL RECEPTACLES IS AT THE LIMIT OF A
 CLASSIFIED AREA (ZONE).
 LOCATION MAY BE A CLASSIFIED AREA AS CLASS 1 DIVISION
 2, AND ALSO MAY FALL UNDER NEC ARTICLE 511.
 PROVIDE INFORMATION AND LOCATION OF EXISTING AND
 PROPOSED CONDUITS, SEALOFFS AND OTHER ITEMS RELATED THE
 CLASSIFIED LOCATION.
 PROVIDE DETAILS OF MATERIALS AND WIRING METHODS
 SPECIFIED AND REQUIRED.
 IF AREA IS TO BE UNCLASSIFIED, PLEASE PROVIDE
 DOCUMENTATION MEETING THE REQUIREMENTS OF THE NEC TO
 SHOW COMPLIANCE.
 IF AREA IS USED FOR NON-TRADITIONAL FUELS, SUCH AS
 HYDROGEN, ADDRESS AREA WITHIN 18" OF THE CEILING.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-21 Cont ID  
Sent By dharvey Date 2013-05-21 Time 07:06 Rev Time 0.00
Received By dharvey Date 2013-05-21 Time 07:05 Sent To  
Notes
2013-05-21 07:06:24DESIGNER HAS CHANGED - NEED DOCUMENTATION OF DESIGN
 PROFESSIONAL CHANGE
 PLANS DO NOT MATCH ORIGINAL FLOOR PLAN. NEED BUILDING,
 MECHANICAL AND PLUMBING PLANS
 NO REVIEW DONE
  
 ORIGINALLY FILED UNDER MASTER #. NOTES ADDED TO THIS
 FILE THIS DAY.
  
 FILED IN DENIED UNDER "L" DH

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-07-13 Cont ID  
Sent By WJOLIN Date 2013-07-13 Time 18:13 Rev Time 0.00
Received By wjolin Date 2013-07-13 Time 18:00 Sent To  
Notes
2013-07-13 18:13:25500 PALM STREET - #32
 TRACKING #13040905
 PERMIT #12100898
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT SHOW THE KITCHENETTE AND FRONT OFFICE
 SHOWN UNDER THE ORIGINAL PERMIT (#12100898)?
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-16 Cont ID  
Sent By shill Date 2013-08-16 Time 14:53 Rev Time 0.00
Received By shill Date 2013-07-08 Time 08:15 Sent To  
Notes
2013-08-15 18:34:35PLACED IN DENIED UNDER "L" DH
2013-07-09 08:17:41B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-21 Cont ID  
Sent By rmcdouga Date 2013-05-21 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2013-04-23 Time 13:38 Sent To  
Notes
2013-04-23 15:00:10GAVE TO DOUG HARVEY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-09 Cont ID  
Sent By HMOSER Date 2013-08-09 Time 15:20 Rev Time 0.00
Received By hmoser Date 2013-08-09 Time 14:56 Sent To  
Notes
2013-08-09 15:20:51PLAN DENIED
 1) PROVIDE NOA ON CONDENSER STAND .
 PER SECTION 107 FBC 2010
 2) PROVIDE A DETAIL FROM THE ENGINEER
 ON THE CONDENSER STAND TO ROOF TIEDOWN
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-07-15 Cont ID  
Sent By LWAGNER Date 2013-07-15 Time 09:10 Rev Time 0.00
Received By lwagner Date 2013-07-15 Time 09:10 Sent To  
Notes
2013-07-15 09:19:40FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVISION #1
 DENIED:
  
 SHEET A-1: THE DETAIL FOR ACCESSIBILITY HAS BEEN
 REMOVED. THE RESTROOM APPEARS TO HAVE NO GRAB BARS AND
 THE LAVITORY IS SHOWN IN THE 60" CLEAR SPACE FOR THE
 WATER CLOSET.
 604.8.1.5 GRAB BARS.
 GRAB BARS SHALL COMPLY WITH 609. A SIDE-WALL GRAB BAR
 COMPLYING WITH 604.5.1 SHALL BE PROVIDED AND SHALL BE
 LOCATED ON THE WALL CLOSEST TO THE WATER CLOSET. IN
 ADDITION, A REAR-WALL GRAB BAR COMPLYING WITH 604.5.2
 SHALL BE PROVIDED.
 604.8.1.6 LAVATORY.
 IN NEW CONSTRUCTION, THE WHEELCHAIR ACCESSIBLE TOILET
 COMPARTMENT SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN
 IT, WHICH MUST BE AT LEAST 19 INCHES WIDE BY 17 INCHES
 DEEP, NOMINAL SIZE, AND WALL-MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 604 FOR THE WHEELCHAIR
 ACCESSIBLE TOILET COMPARTMENT AND SHALL COMPLY WITH
 SECTION 606. SUCH LAVATORIES SHALL BE COUNTED AS PART
 OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE
 ALSO SECTION 213.3.4.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  