| 2013-05-01 16:01:48 | BUILDING PLAN REVIEW |
| | PERMIT: 13040851 |
| | ADD: 4200 N FLAGLER |
| | CONT: MILLER CONSTRUCTION |
| | TEL: (561)847-0692 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MAY 01/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE CORRECT THE PERMIT APPLICATION ADDRESS FIELD |
| | AS WELL AS ADDRESS ON THE PLANS. THE CORRECT PARCEL # |
| | IS 74-4343-03-26-003-0000 THE CORRESPONDING ADDRESS IS |
| | 4300 N FLAGLER DR. THE ORIGINAL BUILDING UNDER PERMIT # |
| | 06101058 WAS ALSO BUILT AND PERMITED UNDER 4300 N |
| | FLAGLER DR. NOTE THE ORIGINAL PLANS WERE NEVER |
| | CORRECTED FOR THE ADDRESS. |
| | |
| | 2) THE NEW 2ND FLOOR AREA THAT WAS PERMITED ORIGINALLY |
| | AS A OPEN MEZZANINE (06101058 SHEET 9/17), IT WILL NOW |
| | BECOME A TRUE SECOND FLOOR. WHILE MEZZANINES ARE ALOUD |
| | TO HAVE OPEN STAIRWAYS, A TRUE SECOND FLOOR WITH A |
| | OCCUPANT LOAD OF 107 OCCUPANTS WILL REQUIRE TWO EXIT |
| | ENCLOSURES PER 2010 FBC-B 1022.1. |
| | 1 HOUR FIRE RATING, EXIT ENCLOSURES SHALL LEAD DIRECTLY |
| | TO THE EXTERIOR OF THE BUILDING OR SHALL BE EXTENDED TO |
| | THE EXTERIOR OF THE BUILDING WITH AN EXIT PASSAGEWAY |
| | CONFORMING TO THE REQUIREMENTS OF SECTION 1023, EXCEPT |
| | AS PERMITTED IN SECTION 1027.1. AN EXIT ENCLOSURE SHALL |
| | NOT BE USED FOR ANY PURPOSE OTHER THAN MEANS OF EGRESS. |
| | |
| | 3) IN THE ORIGINAL BUILDING PERMIT # 06101058 THERE IS |
| | TWO INTERIOR STAIRS FOR THE PORTION OF BUILDING THAT |
| | WAS CONSIDERED 2 STORY, WITH THE ADDITIONAL SQUARE |
| | FOOTAGE BEING ADDED THE DISTANCE APART BETWEEN THE TWO |
| | STAIRS DOES NOT MEET THE 1/3RD OF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE AREA SERVED. |
| | SEE 2010 FBC-B 1015.2.1 EXCEPTION # 2. A THIRD ENCLOSED |
| | VERTICAL EXIT ENCLOSURE WILL BE REQUIRED TO BE ABLE TO |
| | MEET THE 1/3RD THE DISTANCE APART ON THE DIAGONAL. |
| | |
| | 4) SHEET A-121 KEY NOTE # 1 DENOTES NEW LOUVERED |
| | OPENINGS. NO PRODUCT APPROVALS WERE SUBMITTED FOR THE |
| | NEW EXTERIOR WALL LOUVERS. |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | 9N-3(31)(C) WALL LOUVERS. |
| | |
| | 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC... |
| | |
| | 6) SHEET A-111 2ND FLOOR LIFE SAFETY & A-122 2ND FLOOR |
| | EXSPANSION NEITHER SHEET INDICATES DIRECTIONAL, EXIT |
| | NEW OR EXISTING EXIT LIGHTS, OR NEW OR EXISTING |
| | EMERGENCY BATTERY LIGHTS. 2010 FBC-B 1006.1.2 & |
| | 1006.3.1. |
| | |
| | 7A) SHEET A-201 THE EAST ELEVATION INDICATES THE |
| | REMOVAL OF LOUVERS AND RELACEMENT WITH WINDOWS, NO |
| | PRODUCT APPROVAL WAS SUBMITTED WITH THIS REVIEW. 2010 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(B) WINDOWS |
| | |
| | 7B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 8) THE STRUCTURAL DRAWINGS REFLECT STRUCTURAL STEEL |
| | WORK WITH BOLT CONNECTIONS AS WELL AS FIELD WELDING, |
| | THIS WILL REQUIRE A RESIDENT INSPECTOR. |
| | 2010 WEST PALM BEACH ADMINISTRATIVE CODE CHAPTER 1 |
| | |
| | 110.3.9 OTHER INSPECTIONS SERVICES. THE BUILDING |
| | OFFICIAL MAY MAKE, OR CAUSE TO BE MADE |
| | BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. |
| | HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO |
| | THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE |
| | CALLED FOR BY ANY PROVISION OF THE TECHNICAL |
| | CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE |
| | SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN |
| | INSPECTION SERVICE IN THE FOLLOWING INSTANCES: |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 POUNDS PER SQUARE |
| | INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | PLEASE CONTACT KEN CONRAD FOR INFORMATION AND FORMS ON |
| | THE RESIDENT INSPECTOR PROGRAM AT 561-805-6666. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |