Plan Review Details - Permit 13040816
Plan Review Stops For Permit 13040816
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-01 Cont ID  
Sent By rmcdouga Date 2013-08-01 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2013-07-29 Time 16:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By rmcdouga Date 2013-05-31 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2013-05-31 Time 09:36 Sent To  
Notes
2013-05-31 11:24:192010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SOIL INVESTIGATION REPORT
 FROM A FLORIDA LICENSED GEOTECHNICAL ENGINEER. FBC
 R401.4
  
 2) THE PLANS INDICATE ASPHALT SHINGLES ON THE 1-3/4" /
 12" SLOPE AT THE COVERED PORCH AND DEN SECTIONS. FBC
 R905.2.2 STATES THAT ASPHALT SHINGLES SHALL ONLY BE
 USED ON ROOF SLOPES OF 2" / 12" OR GREATER. PLEASE
 CORRECT.
  
 3) THE EXISTING CONCRETE SLAB AT THE COVERED PORCH
 SHOULD BE REMOVED OR PROPERLY TIED TO THE NEW SLAB TO
 PREVENT UNEVEN SETTLEMENT. ACI 318 AND ACI 302.1
  
 4) SHOW COMPLIANCE WITH FBC R404.1.6 WHICH REQUIRES
 CONCRETE FOUNDATION WALLS TO EXTEND A MINIMUM OF 4
 INCHES ABOVE THE FINISHED ADJACENT GRADE WHERE MASONRY
 IS USED.
  
 6) THE ENERGY FORM 402 - 2010 CONTAINS SOME INCORRECT
 INFORMATION. THE WINDOWS ARE REQUIRED TO HAVE A SOLAR
 HEAT GAIN COEFFICIENT OF 0.30 OR LESS AND THE MASS WALL
 INSULATION IS REQUIRED TO BE A MINIMUM OF R-7.8 IF MORE
 THAN HALF OF THE INSULATION IS ON THE INTERIOR OF THE
 MASS WALL. FBC ENERGY TABLE 402.1.1
  
 7) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. CITY AMENDMENTS 107.3.4.1
  
 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 SIMPSON FSA, MSTAM24, AND H2.5 ANCHORS SPECIFIED ON THE
 PLANS. DCA RULE 9N-3
  
 9) THE PRODUCT APPROVAL FOR THE STORM PANELS (NOA NO.
 09-0330.04) HAS BEEN SUPERSEDED. PLEASE SUBMIT THE
 CURRENT PRODUCT APPROVAL.
  
 10) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 OPENINGS THAT THE STORM PANELS WILL BE INSTALLED ON.
 CITY AMENDMENTS 107.2.1
  
 11) THE PRODUCT APPROVALS FOR THE STEEL DOOR NOA NO.
 08-0208.07 AND SINGLE HUNG WINDOWS FL 239-R1 ARE
 EXPIRED. PLEASE SUBMIT THE CURRENT PRODUCT APPROVAL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 14:09 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-08-06 Cont ID  
Sent By rmcdouga Date 2013-08-06 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-05 Time 13:25 Sent To  
Notes
2013-08-05 13:26:06TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-01 Cont ID  
Sent By rmcdouga Date 2013-08-01 Time 10:41 Rev Time 0.00
Received By rmcdouga Date 2013-07-15 Time 14:51 Sent To  
Notes
2013-07-15 14:51:43INCOMING SENT TO R. MCDOUGALS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By rmcdouga Date 2013-05-31 Time 09:37 Rev Time 0.00
Received By rmcdouga Date 2013-04-22 Time 15:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-08-06 Cont ID  
Sent By rmcdouga Date 2013-08-06 Time 11:10 Rev Time 0.00
Received By rmcdouga Date 2013-08-06 Time 11:10 Sent To  
Notes
2013-08-06 11:13:11MU-2013-016905

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-05-31 Cont ID  
Sent By rmcdouga Date 2013-05-31 Time 08:59 Rev Time 0.00
Received By rmcdouga Date 2013-05-31 Time 08:59 Sent To  
Notes
2013-05-31 08:59:43AN IMPACT FEE REVIEW BY PALM BEACH COUNTY IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By rmcdouga Date 2013-05-31 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2013-05-31 Time 09:35 Sent To  
Notes
2013-05-31 09:36:58NO MECHANICAL WORK INDICATED ON THE PLANS. A SEPARATE
 PERMIT, APPLICATION AND REVIEW IS REQUIRED FOR HVAC.

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-05-31 Cont ID  
Sent By rmcdouga Date 2013-05-31 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2013-05-31 Time 09:36 Sent To  
Notes
2013-05-31 09:37:26NO PLUMBING WORK INDICATED ON THE PLANS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-08-01 Cont ID  
Sent By rmcdouga Date 2013-08-01 Time 10:46 Rev Time 0.00
Received By rmcdouga Date 2013-08-01 Time 10:46 Sent To  
Notes
2013-08-01 10:57:38GAF ROYAL SOVERIGN ASPHALT SHINGLES FL10124-R9, NOA
 NO.12-1127.03

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-06 Cont ID  
Sent By mdekle Date 2013-05-06 Time   Rev Time  
Received By mdekle Date 2013-05-06 Time   Sent To  
Notes
2013-05-06 13:42:17 
  
  