Plan Review Details - Permit 13040804
Plan Review Stops For Permit 13040804
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-28 Cont ID  
Sent By dharvey Date 2013-05-28 Time 10:43 Rev Time 0.00
Received By dharvey Date 2013-05-28 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dharvey Date 2013-04-22 Time 12:51 Sent To  
Notes
2013-04-22 12:56:31WIRE SIZE NOT PER NEC 310-15
 SHOW DETAILS OF INSTALLATION INCLUDING SIDE VIEW WITH
 CLEARANCES 230.9, 230.24
 WHAT IS THE PURPOSE OF THE RELOCATION?
 WHERE WILL FEEDER CONDUIT BE LOCATED? ABOVE GROUND,
 UNDERGROUND, ATTIC, ETC. MUST MEET NEC REQUIREMENTS FOR
 INSTALLATION
 WHERE IS THE MAIN DISCONNECT? ARTICLE 230
 IS METER TO BE RELOCATED OR NEW? DRAWING SHOWS BOTH
 PROVIDE WIRE SIZE FOR GES 250 PART III
 PROVIDE INTERSYSTEM BONDING POINT 250.94
 CHANGES TO PLANS MAY REQUIRE ADDITIONAL INFORMATION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-28 Cont ID  
Sent By dharvey Date 2013-05-28 Time 10:43 Rev Time 0.00
Received By dharvey Date 2013-05-28 Time 10:43 Sent To  
Notes
2013-05-25 12:14:02UNDER 5 K ELECTICAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-25 Cont ID  
Sent By lmartine Date 2013-04-22 Time 12:12 Rev Time 0.00
Received By lmartine Date 2013-04-22 Time 12:07 Sent To  
Notes
2013-04-22 12:07:57TO ELEC < $5K