| Plan Review Stops For Permit 13040804 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-05-28 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-05-28 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-05-28 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-04-22 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2013-04-22 12:56:31 | WIRE SIZE NOT PER NEC 310-15 | | | SHOW DETAILS OF INSTALLATION INCLUDING SIDE VIEW WITH | | | CLEARANCES 230.9, 230.24 | | | WHAT IS THE PURPOSE OF THE RELOCATION? | | | WHERE WILL FEEDER CONDUIT BE LOCATED? ABOVE GROUND, | | | UNDERGROUND, ATTIC, ETC. MUST MEET NEC REQUIREMENTS FOR | | | INSTALLATION | | | WHERE IS THE MAIN DISCONNECT? ARTICLE 230 | | | IS METER TO BE RELOCATED OR NEW? DRAWING SHOWS BOTH | | | PROVIDE WIRE SIZE FOR GES 250 PART III | | | PROVIDE INTERSYSTEM BONDING POINT 250.94 | | | CHANGES TO PLANS MAY REQUIRE ADDITIONAL INFORMATION |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-05-28 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-05-28 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-05-28 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2013-05-25 12:14:02 | UNDER 5 K ELECTICAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-05-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2013-04-22 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2013-04-22 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2013-04-22 12:07:57 | TO ELEC < $5K |
|
|
|