Plan Review Details - Permit 13040783
Plan Review Stops For Permit 13040783
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By jwitmer Date 2013-05-10 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2013-05-10 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-09 Cont ID  
Sent By dharvey Date 2013-05-09 Time 12:48 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 13:49 Sent To  
Notes
2013-05-09 12:48:39OK FOR FOUNDATION ONLY. ALL ITEMS TO BE ADDRESSED PRIOR
 TO ADDITIONAL PERMITTING.
  
  
 PLAN STATES THE BUILDING IS A CORROSIVE LOCATION.
 PLEASE DEFINE THE LEVEL OF HAZARD AND IF ANY GASSES OR
 DUST WILL BE PRESENT TO REQUIRE A CLASSIFICATION AS A
 HAZARDOUS LOCATION AND TO WHAT LEVEL THE HAZARD WILL
 EXIST.
 ALL CONDUIT IS BEING REQUIRED TO BE PVC COATED AND ALL
 PULL BOXES ARE BEING REQUIRED TO BE 316 STAINLESS. DOES
 THIS REQUIREMENT GO TO FIXTURES, DEVICES AND OTHER
 EQUIPMENT OR MATERIALS IN THE STRUCTURE?
 WILL SPLICES NEED TO BE ENCAPSULATED OR PROTECTED DUE
 TO HAZARDOUS ENVIRONMENT?
 REVIEW CANNOT BE COMPLETED UNTIL QUESTIONS ARE ANSWERED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By wjolin Date 2013-05-07 Time 09:43 Rev Time 0.00
Received By wjolin Date 2013-05-07 Time 09:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-05-30 Time   Rev Time 0.00
Received By rregueir Date 2013-04-19 Time 14:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By lwagner Date 2013-05-07 Time 12:55 Rev Time 0.00
Received By lwagner Date 2013-05-07 Time 10:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-07-01 Cont ID  
Sent By rregueir Date 2013-07-01 Time 16:41 Rev Time 0.00
Received By rregueir Date 2013-07-01 Time 16:41 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-05-29 Cont ID  
Sent By eschenid Date 2013-05-29 Time 19:32 Rev Time 0.25
Received By eschneid Date 2013-05-29 Time 19:32 Sent To  
Notes
2013-05-29 19:33:14PASSED W/PROVISO
  
 THE BUILDING FOOTPRINT DOES NOT EXACTLY MATCH THE
 APPROVED SITE PLAN - FINAL AS BUILT PLANS SHALL BE
 SUBMITTED AS A PLAN REVISION PRIOR TO C.O.