Plan Review Details - Permit 13040680
Plan Review Stops For Permit 13040680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-17 Cont ID  
Sent By J WITMER Date 2013-06-17 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2013-06-17 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-25 Cont ID  
Sent By jwitmer Date 2013-04-25 Time 12:53 Rev Time 0.00
Received By jwitmer Date 2013-04-25 Time 12:00 Sent To  
Notes
2013-04-25 12:18:22BUILDING PLAN REVIEW
 PERMIT: 13040680
 ADD:310 N OLIVE AVE FLOOR LEVEL
 CONT: COUNIHAW CONSTRUCTION LLC
 TEL: (561)722-6266
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 4/25/2013
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH ADMINISTRATIVE CODE CHAPTER 1,
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 1) WHICH FLOOR IS THIS WORK TO BE COMPLETED ON?
 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 OCCUPANCY LOAD.
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
 FIRE-RESISTANT SEPARATIONS CORRIDORS T 1018.1.
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED
 5) IS THE BUILDING FIRE SPRINKLERED?
 FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
  
 2) 2010 F BC-B 1031.3 1031.3
 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR SHALL BE
 RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR TRAFFIC;
 ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES (3.1 RAD)
 TO STOP AGAINST THE WALL. DOORS IN ANY POSITION SHALL
 NOT REDUCE THE REQUIRED CORRIDOR WIDTH BY MORE THAN
 ONE-HALF.
  
 3) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 4) IF THE BUILDING IS NOT FIRE SPRINKLERED, THEN THE
 CORRIDORS WILL NEED TO BE 1 HOUR FIRE RATERD, THE
 MECHANICAL PLANS DO NOT INDICATE FIRE DAMPERS IN THE
 CORRIDOR WALLS.FBC-B 716.5.2 FIRE BARRIERS. DUCTS AND
 AIR TRANSFER OPENINGS OF FIRE BARRIERS SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS INSTALLED IN
 ACCORDANCE WITH THEIR LISTING. DUCTS AND AIR TRANSFER
 OPENINGS SHALL NOT PENETRATE EXIT ENCLOSURES AND EXIT
 PASSAGEWAYS EXCEPT AS PERMITTED BY SECTIONS 1022.4 AND
 1023.6, RESPECTIVELY.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-20 Cont ID  
Sent By D HARVEY Date 2013-06-20 Time 10:34 Rev Time 0.00
Received By dharvey Date 2013-06-20 Time 10:21 Sent To  
Notes
2013-06-20 10:34:57RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 11:49 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 11:49 Sent To  
Notes
2013-05-07 11:50:555-7-13
 1. PROVIDE ONE LINE ELECTRICAL RISER DIAGRAM PER NEC
 215.5
 2. SHOW SQUARE FOOTAGE OF BLDG ON DRAWINGS
 3. PROVIDE LIGHTING CONTROLS PER ENERGY CODE SECTION
 5.2.2
 4. ALL DEMO ELECTRICAL CONDUCTORS SHALL BE REMOVED BACK
 TO THE SOURCE IF NOT BEING RE-USED. CONDUIT SHALL BE
 CUT FLUSH AND CAPPED.
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-15 Cont ID  
Sent By W JOLIN Date 2013-06-15 Time 12:12 Rev Time 0.00
Received By wjolin Date 2013-06-15 Time 12:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-24 Cont ID  
Sent By wjolin Date 2013-04-24 Time 11:48 Rev Time 0.00
Received By wjolin Date 2013-04-24 Time 11:22 Sent To  
Notes
2013-04-24 11:48:11310 NORTH OLIVE AVENUE
 PERMIT #13040680
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY."
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 SHEET A-2: PROVIDE AN OCCUPANT LOAD CALCULATION FOR THE
 NEW CLASSROOM SPACES.
  
 SHEET A-2: PLANS INDICATE NEW FIRE RATED DOORS AND
 DUCTWORK FIRE DAMPERS; HOWEVER, THE WALL DETAIL DOES
 NOT INDICATE THIS WALL IS TO BE CONSTRUCTED WITH A
 1-HOUR FIRE RESISTANCE RATING.
  
 SHEET A-2: IF NEW WALLS ARE INTENDED TO HAVE A FIRE
 RATING THEN EACH FIRE BARRIER SHALL BE PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE
 BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT
 LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 NO ENGINEERED FIRE ALARM DRAWINGS SUBMITTED. PER FBC
 SECTION 907.1.1 CONSTRUCTION DOCUMENTS - "CONSTRUCTION
 DOCUMENTS FOR FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE, THE FLORIDA
 FIRE PREVENTION CODE, AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL."
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-06-20 Cont ID  
Sent By dharvey Date 2013-06-20 Time 10:35 Rev Time 0.00
Received By dharvey Date 2013-06-07 Time 13:19 Sent To  
Notes
2013-06-10 13:19:57B22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-07 Cont ID  
Sent By shill Date 2013-05-07 Time 12:03 Rev Time 0.00
Received By shill Date 2013-04-18 Time 15:45 Sent To  
Notes
2013-04-19 15:47:28B--12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-06-17 Cont ID  
Sent By H MOSER Date 2013-06-17 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2013-06-17 Time 15:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By hmoser Date 2013-05-06 Time 10:05 Rev Time 0.00
Received By hmoser Date 2013-05-06 Time 09:18 Sent To  
Notes
2013-05-06 10:05:23PLANS DENIED
 1) PROVIDE DUCT SIZE IN CLASS ROOM # 4. PER
 SECTION 107 FBC 2010
 2) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S.
 2010 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS
 606.3 INSTALLATION AND 606.4.1 SUPERVISION 2010 FBC (M)
 4) PROJECT SUMMARY MUST BE SIGNED AND SEALED BY AN
 ENGINEER
 PER SECTION 503.2.1 FLORIDA ENERGY CODE 2010.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  