| 2013-04-25 12:18:22 | BUILDING PLAN REVIEW |
| | PERMIT: 13040680 |
| | ADD:310 N OLIVE AVE FLOOR LEVEL |
| | CONT: COUNIHAW CONSTRUCTION LLC |
| | TEL: (561)722-6266 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: 4/25/2013 |
| | ACTION: DENIED |
| | |
| | 1) 2010 WEST PALM BEACH ADMINISTRATIVE CODE CHAPTER 1, |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 1) WHICH FLOOR IS THIS WORK TO BE COMPLETED ON? |
| | 2. OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | OCCUPANCY LOAD. |
| | 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| | INCLUDE THE FOLLOWING COMPONENTS: |
| | FIRE-RESISTANT SEPARATIONS CORRIDORS T 1018.1. |
| | FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| | PROTECTION OF OPENINGS AND PENETRATIONS OF RATED |
| | 5) IS THE BUILDING FIRE SPRINKLERED? |
| | FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: |
| | SCHEMATIC FIRE SPRINKLERS |
| | |
| | 2) 2010 F BC-B 1031.3 1031.3 |
| | DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR SHALL BE |
| | RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR TRAFFIC; |
| | ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES (3.1 RAD) |
| | TO STOP AGAINST THE WALL. DOORS IN ANY POSITION SHALL |
| | NOT REDUCE THE REQUIRED CORRIDOR WIDTH BY MORE THAN |
| | ONE-HALF. |
| | |
| | 3) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE |
| | AND SMOKE BARRIER ? PROTECT ALL OPENINGS.? |
| | |
| | 4) IF THE BUILDING IS NOT FIRE SPRINKLERED, THEN THE |
| | CORRIDORS WILL NEED TO BE 1 HOUR FIRE RATERD, THE |
| | MECHANICAL PLANS DO NOT INDICATE FIRE DAMPERS IN THE |
| | CORRIDOR WALLS.FBC-B 716.5.2 FIRE BARRIERS. DUCTS AND |
| | AIR TRANSFER OPENINGS OF FIRE BARRIERS SHALL BE |
| | PROTECTED WITH APPROVED FIRE DAMPERS INSTALLED IN |
| | ACCORDANCE WITH THEIR LISTING. DUCTS AND AIR TRANSFER |
| | OPENINGS SHALL NOT PENETRATE EXIT ENCLOSURES AND EXIT |
| | PASSAGEWAYS EXCEPT AS PERMITTED BY SECTIONS 1022.4 AND |
| | 1023.6, RESPECTIVELY. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |