| 2013-04-22 12:39:48 | BUILDING REVISION CHECKLIST. |
| | |
| | 1- GARAGE DOOR PRODUCT APPROVAL FL5684-R5 SUBMITTED |
| | DOESN'T MEET THE DESIGN PRESSURES THAT WERE CALCULATED |
| | BY THE ARCHITECT. NEED TO PROVIDE PRODUCT APPROVAL THAT |
| | MEETS THE CALCULATED DESIGN PRESSURES. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 2- ARCHITECT OF RECORD NEED TO REVIEW AN APPROVE IN |
| | WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 3- NEED TO PROVIDE ALL THE INFORMATION THAT WAS |
| | REQUESTED ON PROVISO DATED 7/27/10 TO AVOID ANY DELAYS |
| | OR CONFLICTS ON FINAL INSPECTION. INFORMATION WAS NEVER |
| | SUBMITTED FOR REVIEW. SEE COPY OF PROVISO BELOW: |
| | |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | -1- PROVIDE PRODUCT APPROVALS FOR: (A) GARAGE DOOR THAT |
| | MEETS THE DESIGN PRESSURES CALCULATED ON SHEET A-2.0. |
| | (B) EXTERIOR INSWING AND OUTSWING DOORS. (C) WINDOW |
| | MULLIONS. (D)STRUCTURAL CONNECTORS. (E) CURRENT ROOF |
| | TILE AND POLYFOAM ADHESIVE. NOA 07-1023.11 WAS CLOSED |
| | BY MIAMI-DADE. (F) FLAT ROOF. PROVIDE SIGNED AND SEALED |
| | RAS 117 CALCULATIONS. |
| | -2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. |
| | -3- ARCHITECT TO COORDINATE WINDOW MATERIAL SPECIFIED |
| | ON PLANS AND PRODUCT APPROVAL SUBMITTED TO MATCH. |
| | -4- ENERGY CALCULATIONS: (A) PROVIDE COMPLETE |
| | INFORMATION ON TOP OF FORM. (B) ENGINEER TO PROVIDE ALL |
| | HIS INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES. (C) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF |
| | ENERGY CALCULATIONS TO MATCH PLANS. (D) COORDINATE |
| | WINDOW MATERIAL WITH REVISED WINDOW MATERIAL REQUESTED |
| | ON ITEM #3 ABOVE. |
| | -5- OUTDOOR FIREPLACE: (A) PROVIDE COMPLETE FRAMING |
| | DETAILS FOR FIREPLACE AND CHIMNEY. SPECIFY ALL FRAMING |
| | MEMBERS AND CONNECTORS TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301. (B) DESIGNER OF RECORD |
| | TO REVIEW AND APPROVE IN WRITING OUTDOOR FIREPLACE |
| | COMPLETE PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | -6- GUARDRAILS AND HANDRAILS: (A) MISSING GUARDRAILS |
| | AND HANDRAILS ON WEST STAIRS. SEE SHEET A-1. (B) REVISE |
| | DETAIL #12 ON SHEET A-1.1. REVISE PICKET SPACING. A 4" |
| | SPHERE SHALL NOT PASS TRU. SEC. R312. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |