Plan Review Details - Permit 13040663
Plan Review Stops For Permit 13040663
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-01-08 Cont ID  
Sent By jgomez Date 2014-01-08 Time 16:41 Rev Time 0.00
Received By jgomez Date 2014-01-08 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 14:01 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 14:01 Sent To  
Notes
2013-12-03 16:40:38BUILDING REVISION THIRD CHECKLIST.
 CODE: 2007 FBC.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS.
  
 DRAWINGS SUBMITTED (DWG NO 08-00125) ARE NOT A PRODUCT
 APPROVAL. IF THERE IS NOT A CURRENT PRODUCT APPROVAL,
 THEN MANUFACTURER MAY APPLY FOR A LOCAL PRODUCT
 APPROVAL. PLEASE, CALL ME FOR INSTRUCTIONS ON HOW TO
 APPLY FOR LOCAL PRODUCT APPROVAL.
  
 B) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR.
  
 INFORMATION SUBMITTED ARE NOT A PRODUCT APPROVAL. IF
 THERE IS NOT A CURRENT PRODUCT APPROVAL, THEN
 MANUFACTURER MAY APPLY FOR A LOCAL PRODUCT APPROVAL.
 PLEASE CALL ME FOR INSTRUCTIONS ON HOW TO APPLY FOR
 LOCAL PRODUCT APPROVAL.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) ENGINEER TO SIGN AND SEAL DOCUMENTS AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 B) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. N1100.2.2 OF 2007 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-27 Cont ID  
Sent By jgomez Date 2013-09-27 Time 08:51 Rev Time 0.00
Received By jgomez Date 2013-09-27 Time 08:51 Sent To  
Notes
2013-09-27 09:02:52BUILDING REVISION SECOND CHECKLIST.
 CODE: 2007 FBC.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) EXTERIOR INSWING DOORS AS SHOWN ON PLANS BY THE
 KITCHEN AREA. (ONLY PRODUCT APPROVAL FOR OUTSWING DOOR
 WAS PROVIDED AT THIS TIME).
  
 B) WINDOW MULLIONS. (STILL NONE SUBMITTED AT THIS
 TIME).
  
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 PROVIDE ONLY THE COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR. (STILL NONE SUBMITTED AT THIS
 TIME).
  
 D) PROVIDE INFORMATION SHOWING THAT DRAWINGS SUBMITTED
 FOR DOUBLE HUNG WINDOWS ARE PART OF A FLORIDA BUILDING
 COMMISSION (FBC) APPROVAL PACKAGE. IF THERE IS NOT
 CURRENT PRODUCT APPROVAL, THEN NEED TO APPLY FOR LOCAL
 PRODUCT APPROVAL AS REQUIRED BY DCA RULE 9N-3.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 (A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM. (NO
 DONE).
 (B) ENGINEER TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES. (NO DONE).
 (C) COORDINATE DOOR AND WINDOW MATERIAL WITH MATERIALS
 SHOWN ON PRODUCT APPROVALS SUBMITTED. (NO DONE).
  
 ****NOTE: NEW ITEMS:
 D) PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE
 WINDOWS AND GLASS IN DOORS SHOWING COMPLIANCE WITH THE
 U FACTOR AND SHGC FACTOR SHOWN ON ITEM #7. (SEC.
 13-601.AB.1 OF 2007 FBC.
  
 F) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
  
  
 4- OWES $103.00 REVISION FEES FOR TOTAL NUMBER OF
 DRAWINGS AND PRODUCT APPROVALS SUBMITTED (7 TOTAL).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By jgomez Date 2013-04-22 Time 13:50 Rev Time 0.00
Received By jgomez Date 2013-04-22 Time 11:42 Sent To  
Notes
2013-04-22 12:39:48BUILDING REVISION CHECKLIST.
  
 1- GARAGE DOOR PRODUCT APPROVAL FL5684-R5 SUBMITTED
 DOESN'T MEET THE DESIGN PRESSURES THAT WERE CALCULATED
 BY THE ARCHITECT. NEED TO PROVIDE PRODUCT APPROVAL THAT
 MEETS THE CALCULATED DESIGN PRESSURES. SEC. 107.2.1
 CITY AMENDMENTS TO FBC.
  
 2- ARCHITECT OF RECORD NEED TO REVIEW AN APPROVE IN
 WRITING (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 3- NEED TO PROVIDE ALL THE INFORMATION THAT WAS
 REQUESTED ON PROVISO DATED 7/27/10 TO AVOID ANY DELAYS
 OR CONFLICTS ON FINAL INSPECTION. INFORMATION WAS NEVER
 SUBMITTED FOR REVIEW. SEE COPY OF PROVISO BELOW:
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 -1- PROVIDE PRODUCT APPROVALS FOR: (A) GARAGE DOOR THAT
 MEETS THE DESIGN PRESSURES CALCULATED ON SHEET A-2.0.
 (B) EXTERIOR INSWING AND OUTSWING DOORS. (C) WINDOW
 MULLIONS. (D)STRUCTURAL CONNECTORS. (E) CURRENT ROOF
 TILE AND POLYFOAM ADHESIVE. NOA 07-1023.11 WAS CLOSED
 BY MIAMI-DADE. (F) FLAT ROOF. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS.
 -2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS.
 -3- ARCHITECT TO COORDINATE WINDOW MATERIAL SPECIFIED
 ON PLANS AND PRODUCT APPROVAL SUBMITTED TO MATCH.
 -4- ENERGY CALCULATIONS: (A) PROVIDE COMPLETE
 INFORMATION ON TOP OF FORM. (B) ENGINEER TO PROVIDE ALL
 HIS INFORMATION AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES. (C) REVISE TYPE OF ROOF SHOWN ON PAGE 2 OF
 ENERGY CALCULATIONS TO MATCH PLANS. (D) COORDINATE
 WINDOW MATERIAL WITH REVISED WINDOW MATERIAL REQUESTED
 ON ITEM #3 ABOVE.
 -5- OUTDOOR FIREPLACE: (A) PROVIDE COMPLETE FRAMING
 DETAILS FOR FIREPLACE AND CHIMNEY. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301. (B) DESIGNER OF RECORD
 TO REVIEW AND APPROVE IN WRITING OUTDOOR FIREPLACE
 COMPLETE PACKAGE PRIOR TO SUBMITTAL TO THIS OFFICE.
 -6- GUARDRAILS AND HANDRAILS: (A) MISSING GUARDRAILS
 AND HANDRAILS ON WEST STAIRS. SEE SHEET A-1. (B) REVISE
 DETAIL #12 ON SHEET A-1.1. REVISE PICKET SPACING. A 4"
 SPHERE SHALL NOT PASS TRU. SEC. R312.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-01-08 Cont ID  
Sent By jgomez Date 2014-01-08 Time 17:11 Rev Time 0.00
Received By jgomez Date 2013-12-26 Time 16:05 Sent To  
Notes
2014-01-08 16:06:09SENT TO J. GOMEZ' DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 17:06 Rev Time 0.00
Received By jgomez Date 2013-11-12 Time 19:52 Sent To  
Notes
2013-11-12 19:52:55SENT TO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-27 Cont ID  
Sent By jgomez Date 2013-09-27 Time 11:29 Rev Time 0.00
Received By jgomez Date 2013-09-24 Time 17:23 Sent To  
Notes
2013-09-24 17:24:05TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-22 Cont ID  
Sent By jgomez Date 2013-04-22 Time 14:00 Rev Time 0.00
Received By jgomez Date 2013-04-17 Time 16:04 Sent To  
Notes
2013-04-17 16:04:58SENT TO GOMEZ