Plan Review Details - Permit 13040633
Plan Review Stops For Permit 13040633
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-06-14 Cont ID  
Sent By jwitmer Date 2013-06-14 Time 14:16 Rev Time 0.00
Received By jwitmer Date 2013-06-14 Time 14:16 Sent To  
Notes
2013-06-14 14:40:32BUILDING PROVISO:
 2010 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 FEET
 (9144 MM). THIS CATEGORY INCLUDES FLAT OPEN COUNTRY AND
 GRASSLANDS. THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO
 ANY BUILDING LOCATED WITHIN SURFACE ROUGHNESS B-TYPE
 TERRAIN WHERE THE BUILDING IS WITHIN 100 FEET
 HORIZONTALLY IN ANY DIRECTION OF OPEN AREAS OF SURFACE
 ROUGHNESS C OR D-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FEET IN
 THE UPWIND DIRECTION.
 WALL ZONE # 4 42.3/ -45.8
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-30 Cont ID  
Sent By jwitmer Date 2013-04-30 Time 11:15 Rev Time 0.00
Received By jwitmer Date 2013-04-30 Time 10:00 Sent To  
Notes
2013-04-30 11:40:35BUILDING PLAN REVIEW
 PERMIT: 13040633
 ADD: 804 SOUTHERN BLVD
 CONT: OTHRS CONSTRUCTION
 TEL: (561)262-4088
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 30/ 2013
 ACTION: DENIED
  
 1) THE PLANS SUBMITTED FOR PUBLIC RECORD APPEAR TO BE A
 STAMP SIGNATURE OF THE ARCHITECT OF RECORD. PLEASE
 REVIEW:
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
  
 2) THE TENANT SEPERATION WALLS, FIRE BARRIERS SHALL
 HAVE THE FOLLOWING INFORMATION STENCILLED:
 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.
  
 3) SHEET A1.1 IT APPEARS THERE IS A NEW DOOR AT THE
 BACK OF THE NEW TENANTACY. THE FOLLOWING INFORMATION IS
 REQUIRED:
 3A) WIND DESIGN CRITERIA 2010 FBC-B 1609.1.1
 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10.
  
 3B) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3C) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4) THE M1INDICATES THE 2 EXISTING UNITS ARE TO BE
 REPLACED IN THE SAME LOCATION, THE PERMIT APPLICATION
 INDICATES THERE TO BE A NEW UNIT.
 THE M1 SHEET INDICATES TO VERIFY THE EXISTING STRUCTURE
 IS CAPABLE OF SUPPORTING EACH RTU, 1685 LBS EACH,
 COORDINATE WITH STRUCTURAL ENGINEER IF REQUIRED. NO
 STRUCTURAL ENGINEER HAS PROVIDED CALCULATIONS THIS ROOF
 STRUCTURE WILL IN FACT TAKE THE ADDITIONAL LOAD, NOR
 HAS THERE BEEN A DESIGN FOR THE REINFORCEMENT OF THE
 BAR JOIST, NEW ROOF TOP PENETRATION AND THE TTIE DOWN
 OF THE RTU CURB TO THE ROOF FRAMING, NOR THE MECHANICAL
 CURB TO THE ROOF TOP RTU'S. 2010 FBC-B 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 5) SHEET A1.2 NOTE 2 & 3 BOTH INDICATE FIRE SPRINKLER
 PLANS ARE REQUIRED, BUT NO PLANS HAVE BEEN SUPPLIED IN
 THIS REVIEW FOR THE FIRE SPRINKLER MODIFICATION.
 107.3.5.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS:(5) FIRE SUPRESSION SYSTEMS SCHEMATIC FIRE
 SPRINKLERS.
 2010 WEST PALM BEACH ADMINISTRATIVE CODE, CHAPTER 1
 ADMINISTRATION.
  
 6) EVEN THOUGH THIS IS TO BE A WHITE BOX PERMIT, AND
 TENANT WILL COME IN UNDER ANOTHER PERMIT, NEITHER THE A
 NOR E SHEETS PROVIDE EXIT SIGNS SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT SOURCE 2010 FBC-B
 1006.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-06-25 Cont ID  
Sent By dharvey Date 2013-06-25 Time 09:35 Rev Time 0.00
Received By dharvey Date 2013-06-25 Time 09:25 Sent To  
Notes
2013-06-25 09:36:10RESTAMP RL
2013-05-30 16:09:21NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-05-07 Cont ID  
Sent By dharvey Date 2013-05-07 Time 13:01 Rev Time 0.00
Received By dharvey Date 2013-05-07 Time 13:01 Sent To  
Notes
2013-05-07 13:02:545-7-13
 ALL ELECTRICAL DEMO MUST BE MADE SAFE. CAP ALL UNUSED
 CONDUITS AND REMOVE ANY UNSED CONDUCTORS BACK TO THE
 SOURCE
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-06-08 Cont ID  
Sent By wjolin Date 2013-06-08 Time 11:21 Rev Time 0.00
Received By wjolin Date 2013-06-08 Time 11:18 Sent To  
Notes
2013-06-08 11:21:27804 SOUTHERN BOULEVARD
 PERMIT #13040633
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PERMIT FOR SHELL ONLY - TENANT FITOUT PERMIT WILL
 BE NEEDED FOR OCCUPANCY*****
  
 FIRE SPRINKLER SCOPE NOT INDICATED ON PLANS. EXISTING
 SPRINKLER COVERAGE WILL NEED TO BE ADJUSTED TO ACCOUNT
 FOR THE NEW TENANT SEPARATION WALL.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-04-22 Cont ID  
Sent By wjolin Date 2013-04-22 Time 13:13 Rev Time 0.00
Received By wjolin Date 2013-04-22 Time 12:57 Sent To  
Notes
2013-04-22 13:13:11804 SOUTHERN BOULEVARD
 PERMIT #13040633
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PERMIT FOR SHELL ONLY - TENANT FITOUT PERMIT WILL
 BE NEEDED FOR OCCUPANCY*****
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 IN WRITING (FAX: 561-804-4774) AND APPROVED BY THE
 OFFICE OF THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE
 HIGHWAY.?
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE A PLAN INDICATING EGRESS LIGHTING, EMERGENCY
 LIGHTING AND EXIT SIGN LOCATIONS.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 FIRE SPRINKLER SCOPE NOT INDICATED ON PLANS. EXISTING
 SPRINKLER COVERAGE WILL NEED TO BE ADJUSTED TO ACCOUNT
 FOR THE NEW TENANT SEPARATION WALL.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-07-03 Cont ID  
Sent By hmoser Date 2013-07-03 Time 10:49 Rev Time 0.00
Received By hmoser Date 2013-05-30 Time 16:12 Sent To  
Notes
2013-05-30 16:13:07SENT TO B6 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-07 Cont ID  
Sent By shill Date 2013-05-07 Time 13:35 Rev Time 0.00
Received By shill Date 2013-04-18 Time 08:55 Sent To  
Notes
2013-04-18 08:56:46B23

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-07-03 Cont ID  
Sent By hmoser Date 2013-07-03 Time 10:45 Rev Time 0.00
Received By hmoser Date 2013-07-03 Time 08:44 Sent To  
Notes
2013-07-03 10:45:30PASS PROVISO
 1) REFER TO SECTION 503.2.1 CALCULATION OF HEATING AND
 COOLING
 2010 FLORIDA ENERGY CODE SUBMIT AS A REVISION.
 2) PROVIDE A LETTER FROM THE ENGINEER SHOWING THE BOLT
 SIZE FOR THE CURB TO ROOF TIE DOWN AND RTU TO CURB TIE
 DOWN.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M).
 SUBMIT AS A REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By hmoser Date 2013-05-06 Time 14:04 Rev Time 0.00
Received By hmoser Date 2013-05-06 Time 13:19 Sent To  
Notes
2013-05-06 14:04:42PLANS DENIED
 1) CAN NOT READ ROOF CURB DETAIL ON THE PLANS.
 PROVIDE A LEGIBLE ROOF CURB DETAIL WITH BOLT SIZE.
 PROVIDE A RTU TO CURB DETAIL ALSO BY THE ENGINEER.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM, 606.3
 INSTALLATION AND 606.4.1 SUPERVISION.
 3) CHANGE OUT FORM IS REQUIRED
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-04-22 Cont ID  
Sent By lwagner Date 2013-04-22 Time 15:47 Rev Time 0.00
Received By lwagner Date 2013-04-22 Time 15:40 Sent To  
Notes
2013-04-22 15:48:25NO PLUMBING WORK SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-04-26 Cont ID  
Sent By ajones Date 2013-04-26 Time 15:29 Rev Time 0.00
Received By ajones Date 2013-04-26 Time 15:29 Sent To  
Notes
***NONE***