Plan Review Details - Permit 13040598
Plan Review Stops For Permit 13040598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-05-23 Cont ID  
Sent By JWITMER Date 2013-05-23 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By jwitmer Date 2013-04-24 Time 07:20 Rev Time 0.00
Received By jwitmer Date 2013-04-23 Time 16:46 Sent To  
Notes
2013-04-23 16:58:14BUILDING PLAN REVIEW
 PERMIT: 13040598
 ADD: 2427 PRESIDENTIAL WAY # 1104
 CONT: MAKI CONSTRUCTION
 TEL: (561)622-4654
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: APRIL 24/ 2013
 ACTION:BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1)2010 FBC-B : COMBUSTIBLE MATERIALS IN TYPE I AND II
 CONSTRUCTION 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3
 2.THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 100. PLREASE
 PROVIDE MANUFACTURERS TEST DATA BY FRAMING INSPECTION..
  
 2) 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.PLEASE PROVIDE MANUFACTURERS TEST DATA BY FRAMING
 INSPECTION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-05-23 Cont ID  
Sent By DHARVEY Date 2013-05-23 Time 14:55 Rev Time 0.00
Received By dharvey Date 2013-05-23 Time 14:55 Sent To  
Notes
2013-05-23 14:55:595-23-13
 CORRECTIONS MADE
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-05-06 Cont ID  
Sent By dharvey Date 2013-05-06 Time 09:43 Rev Time 0.00
Received By dharvey Date 2013-05-06 Time 09:43 Sent To  
Notes
2013-05-06 09:45:075-6-13
 1. SHOW ALL REQUIRED RECEPTACLES AND CIRCUIT NUMBERS ON
 FLOOR PLAN
 2. NOTE USE OF TAMPER RESISTANT RECPTACLES AS PER NEC
 406.11
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2013-05-30 Cont ID  
Sent By WJOLIN Date 2013-05-30 Time 12:52 Rev Time 0.00
Received By jgomez Date   Time   Sent To  
Notes
2013-05-30 12:52:54APPROVED BY WESLEY 4/20/13. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-04-20 Cont ID  
Sent By wjolin Date 2013-04-20 Time 13:43 Rev Time 0.00
Received By wjolin Date 2013-04-20 Time 13:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-05-30 Cont ID  
Sent By jgomez Date 2013-05-30 Time 12:53 Rev Time 0.00
Received By jgomez Date 2013-05-20 Time 13:21 Sent To  
Notes
2013-05-21 13:21:22B02

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-06 Cont ID  
Sent By lmartine Date 2013-05-06 Time 10:05 Rev Time 0.00
Received By lmartine Date 2013-04-16 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-05-23 Cont ID  
Sent By LWAGNER Date 2013-05-23 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2013-05-23 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-04-19 Cont ID  
Sent By lwagner Date 2013-04-19 Time 15:59 Rev Time 0.00
Received By lwagner Date 2013-04-19 Time 15:51 Sent To  
Notes
***NONE***