Plan Review Details - Permit 13040580
Plan Review Stops For Permit 13040580
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-04-16 Cont ID  
Sent By shill Date 2013-04-16 Time 11:38 Rev Time 0.00
Received By shill Date 2013-04-16 Time 11:38 Sent To  
Notes
2013-04-16 11:41:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 THE DOCUMENTS PROVIDED DO NOT INCLUDE A PRODUCT NAME.
 SHOW COMPLIANCE FOR THE FOLLOWING REQUIREMENTS FOR THE
 PROPOSED UNDERLAYMENT:
  
 1. FBC 1207.2 AND 1207.3, THE TEST DATA SUBMITTED IS
 MISSING PAGE 1.
  
 2. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-16 Cont ID  
Sent By shill Date 2013-04-16 Time 11:41 Rev Time  
Received By shill Date   Time   Sent To  
Notes
***NONE***