Plan Review Details - Permit 13040565
Plan Review Stops For Permit 13040565
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-05-10 Cont ID  
Sent By Mgonzale Date 2013-05-10 Time   Rev Time 1.00
Received By mgonzale Date 2013-05-10 Time   Sent To I
Notes
2013-05-10 08:52:01NO OBJECTION.
 PLANS WHERE APPROVED THRU ESD.
  
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By wjolin Date 2013-04-24 Time 14:56 Rev Time 0.00
Received By wjolin Date 2013-04-24 Time 14:45 Sent To M
Notes
2013-04-24 14:50:371801 PALM BEACH LAKES BOULEVARD
 PERMIT #13040565
 MASTER #12100555 (POSSIBLY ADDRESSED AS 1721 PBL BLVD)
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS*****
  
 SUBMIT PRODUCT DATA CUTSHEETS FOR BACKFLOW PREVENTERS.
 DEVICES SHALL BE LISTED FOR FIRE PROTECTION USE.
  
 INSTALLATION, FLUSHING AND TESTING OF UNDERGROUND FIRE
 MAINS SHALL COMPLY WITH NFPA 24 (2007 EDITION).
  
 FIRE MAINS AND FIRE DEPARTMENT CONNECTION LINES SHALL
 HYDROSTATICALLY TESTED FOR 2-HOURS AT 200 PSI.
  
 HYDRANTS AND ADEQUATE WATER SUPPLY ARE REQUIRED PRIOR
 TO BUILDING CONSTRUCTION OR STORAGE OF COMBUSTIBLES.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-05-10 Cont ID  
Sent By swurafti Date 2013-05-10 Time 11:38 Rev Time 0.00
Received By swurafti Date 2013-04-15 Time 09:14 Sent To  
Notes
2013-04-16 09:14:38SENT TO C15 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-04-30 Cont ID  
Sent By hmoser Date 2013-04-30 Time 09:18 Rev Time 0.00
Received By hmoser Date 2013-04-30 Time 09:05 Sent To  
Notes
***NONE***