Plan Review Details - Permit 13040497
Plan Review Stops For Permit 13040497
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-04-24 Cont ID  
Sent By shill Date 2013-04-24 Time 17:30 Rev Time 0.00
Received By shill Date 2013-04-24 Time 17:30 Sent To  
Notes
2013-04-24 17:31:20VERIFIED THAT PARCEL IS NOT LOCATED IN SPECIAL HAZARD
 FLOOD ZONE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-04-25 Cont ID  
Sent By wjolin Date 2013-04-25 Time 08:46 Rev Time 0.00
Received By wjolin Date 2013-04-25 Time 08:28 Sent To  
Notes
2013-04-25 08:46:006610 NORTH JOG ROAD
 PERMIT #13040497
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL TRAILERS SHALL BE INDENTIFIED WITH A LETTER OR
 NUMBERS TO PREVENT DELAYED RESPONSE FROM EMERGENCY
 PERSONNEL. BUILDING ADDRESS SHALL BE VISIBLE FROM THE
 STREET. LETTERS OR NUMBERS SHALL BE ATTACHED TO THE
 BUILDING AND BE AT LEAST SIX-INCHES IN HEIGHT WITH
 1-INCH STROKE AND SHALL CONTRAST THE BACKGROUND.
  
 PROVIDE EGRESS STAIRS OR RAMPS. STAIR RISERS SHALL BE
 BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS SHALL
 BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH OF 11
 INCHES AND PREVENT THE ACCUMULATION OF WATER. HANDRAILS
 ARE REQUIRED ON BOTH SIDES OF THE STAIR. HANDRAILS
 SHALL BE LOCATED NOT LESS THAN 34 INCHES AND NOT MORE
 THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, MEASURED
 VERTICALLY TO THE TOP OF THE RAIL FROM THE LEADING EDGE
 OF THE TREAD. HANDRAIL ENDS SHALL BE RETURNED TO THE
 WALL OR FLOOR OR SHALL TERMINATE AT NEWEL POSTS.
 HANDRAIL CROSS SECTION SHALL HAVE A DIAMETER OF NOT
 LESS THAN 1.25 INCHES AND NOT MORE THAN 2 INCHES AND
 SHALL BE GRASPABLE ALONG ITS ENTIRE LENGTH. GUARDS, AT
 LEAST 42-INCHES TALL, SHALL BE PROVIDED AT THE OPEN
 SIDES OF STAIRS THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE.
  
 ALL TRAILERS SHALL BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-04-25 Cont ID  
Sent By wjolin Date 2013-04-25 Time 08:46 Rev Time 0.00
Received By wjolin Date 2013-04-12 Time 16:15 Sent To  
Notes
2013-04-24 17:31:494/24 TO FIRE
2013-04-12 16:24:18INCOMING SENT TO ZONING BOX. JW

Review Stop Z ZONING
Rev No 1 Status P Date 2013-04-24 Cont ID  
Sent By eschneid Date 2013-04-24 Time 15:18 Rev Time 0.25
Received By eschneid Date 2013-04-17 Time 10:42 Sent To B
Notes
***NONE***